Cool Roof Design
Cool Roof Design
Design Brief
Cool Roof Design Brief
Unlike conventional roofs, cool roofs stay A cool roof has a higher solar reflectance
at or near ambient temperatures even on and higher thermal emittance than a non-
the hottest summer day. Cool roofing is cool roof. High solar reflectance and high
defined by the radiative properties known thermal emittance of a cool roof combine
as solar reflectance and thermal emittance, to keep the roof surface much cooler than a
shown schematically in Figure 1, and traditional roof, with peak temperature re-
described in more detail below. ductions of 30°F -60°F [1]. Achieving this
type of drop in roof surface temperature
Roof Heat Transfer Mechanism
will reduce the overall heat gain through
Several phenomena occur to the incident the roof and reduce a building’s annual
cooling needs. Studies show cool roofs can
typically reduce summer air-conditioning
energy use by 10%-20% [1].
Solar Radiation Reflected Emitted Sky
Convection
Roof
Insulation
www.energydesignresources.com
is much cooler. Thus it is possible to have
relatively dark-colored roofs with relatively
1600
“cool” properties. Figure 3 illustrates the
influence of a roof coating on the solar
watts/meterˆ2/micrometer
0
100
0.3 0.5 0.7 0.9 1.1 1.3 1.5 1.7 1.9 2.1 2.3 2.5 UV Visible Infrared Different signatures in PR range
wavelength in micrometers 90
80
Figure 2: Solar Energy Distribution Infrared-Reflecting
70
Reflectance (%)
60
50
Solar Reflectance 40
www.energydesignresources.com
Cool Roofing Standards as 38% has been measured in a field test
According to California Title 24, the En- [5]. Demand savings are slightly higher.
ergy Efficiency Standards for Buildings in A reasonable energy savings expectation
California, a qualifying low-slope cool roof for a typical low-rise commercial building
for non-residential buildings must have an is 10% to 20% of the air-conditioning
initial solar reflectance of 0.70 or greater electricity usage [1].
and an initial thermal emittance of 0.75 or
greater, as rated by the Cool Roof Rating Monetary Savings
Council (CRRC). Title 24 requirements Reduced energy usage from the installa-
are more stringent than EPA’s Energy Star tion of a cool roof naturally translates into
program, which specifies a solar reflectance monetary savings for building owners.1
of 0.65 or higher for low-slope applica- Further, maintaining a roof system can
tions, with no specifications of thermal cost as much as 90% of the total envelope
emittance. The comparison of these two maintenance cost in spite of its relative low
definitions is shown in Table 1. initial construction cost [6]. Applying a
cool coating can reduce the peak tempera-
ture and daily temperature swing expe-
Benefits of Cool Roofing rienced by the roof membrane. Reduced
thermal cycling enhances the durability of
As outlined below, the installation of a some materials, and may extend the life of
cool roof can result in energy and demand the roof and produce less roofing waste.
savings, monetary savings, increased hu- These effects reduce the life cycle cost of
man comfort both indoors and outdoors, the roof. In addition, monetary savings can
and significant positive impacts on urban be achieved when installing or replacing
environmental quality. air-conditioning equipment. Since less
cooling is required with a cool roof, the
Energy and Demand Savings air-conditioning equipment can often be
downsized, resulting in lower procurement
Energy savings due to installation of
costs.
cool roofs have been demonstrated and
measured over a wide range of climates Increase in Human Comfort
and roof types. Typical air-conditioning
electrical savings have been in the range of Cool roofs reduce the heat transfer into a
7% to 34% [5]. Cooling energy savings building. For buildings with no air-condi-
are greater in hot and sunny locations. A tioning cooling, such as many warehouses,
cooling energy demand reduction as high it can significantly increase building
1
Energy savings accrue even though cool roofs cause a slightly increased need for heating
during the winter months. During winter or in a cold climate, use of a cool roof will increase
heating energy use by up to 3% [1]. In heating-dominated climates, reflective roofing can
create a very slight increase in heating demand. However, simulations show that air-condition-
ing savings easily outweigh the heating penalty, even in northerly climates. This is because
in summer the solar altitude is high, and shines mainly on the roof of a building, whereas in
winter the lower sun shines on the walls and through the windows. The roof plays less of a role
in winter than, for example, having large south-facing windows.
www.energydesignresources.com
Prescriptive Approach: Envelope and improvements are made to the other
Component building envelope components to com-
Under the envelope component approach, pensate, this compliance approach must
each baseline component of the envelope be used. The required forms are ENV-1-C
assemblies (walls, roofs, floors, windows, Certificate of Compliance and ENV-3-C
skylights) must comply individually with Overall Envelope Method. In the case that
its requirement. If one component of the a non-qualifying cool roof is installed,
envelope does not comply, then the entire envelope insulation must be upgraded
envelope does not comply. So, for this to compensate. More about the trade-off
“prescriptive checklist” Title 24 compli- between a cool roof and the envelope will
ance method, a cool roof is required. The be discussed in the design consideration
cool roof requirement does not overlap the section.
insulation requirement of the roof. That is,
Performance Approach
the insulation requirements must be met
separately. The performance approach is the most
complicated method of complying with
This approach is the easiest way to comply Title 24, yet it permits the most trade-offs
with Title 24. It involves only complet- among all envelope components, as well as
ing a checklist and filling out two forms. trade-offs between the building envelope
This approach is generally the easiest and and mechanical and lighting systems. With
most expedient although it provides little this approach, building and HVAC systems
flexibility. working together meet or are better than
The required compliance forms for this ap- the baseline building’s total energy budget.
proach are ENV-1-C Certificate of Com- The performance approach requires use of
pliance; and ENV-2-C Envelope Compo- an approved computer software program
nent Method. A Cool Roof Rating Council that models the proposed building, deter-
(CRRC) label for the roof product must mines its allowed energy budget, calculates
be submitted. If a cool roof is installed and its energy use, and determines whether it
roof insulation is involved, the insulation complies with the budget.
level must be brought up to existing code. Some new construction projects take
advantage of roof space for other uses, such
Prescriptive Approach: Overall Envelope
as garden roofs, decks, patios, and photo-
The overall envelope approach allows the voltaic (PV) panels. For these applications,
performance of some building envelope the performance approach should be used.
components to be increased while the Cool roof regulations apply to PV systems
performance of others is reduced, as long that are embedded or integrated into the
as overall heat gain and loss are no greater roof, as well as designs in which PV panels
than a building in minimum compliance are mounted on racks above the roof
with the prescriptive requirements. The cal- surface. Note that the electricity produced
culations of overall heat gain and loss of the by PV solar electric systems cannot be used
proposed building must be considered. The as a trade-off in meeting a building’s energy
formula for calculating overall heat loss and budget.
gain for a standard building and for the
proposed building are provided in Equa-
tions 143-B, C, D, E of the Standards.
If the new roof is not a qualified cool roof,
2
American Society for Testing and Materials
www.energydesignresources.com
the building shell will result in 1 point; • Single-Ply Membranes are 35- to 60-
maintaining 100% of the building shell mil membranes made of various mate-
will result in more than 1 point. Details of rials, including EPDM, CSPE, PVC,
the LEED crediting system are available on and TPO. A number of bright white
the USGBC’s website at http://www.usgbc. Single-Plys are in the market which meet
com. A LEED-accredited professional the Title 24 definition for cool roofs
should be consulted in order to receive (CRRC reflectance ≥ 0.7, emittance ≥
project certification. 0.75); but traditional black, gray, and tan
membranes are generally not cool with
lower reflectance values. To secure the
Design Considerations membranes to the substrate, adhesive,
mechanically fastened, or ballasted meth-
To achieve compliance with the Title ods are used. Seams must be sealed with
24 Standards, the solar reflectance and thermoset or thermoplastic, adhesive
emittance of the roof product must have bond, heat-welded, or taped.
been tested and listed with the Cool Roof • Modified Bitumen Roofing is similar
Rating Council (CRRC) http://coolroofs. to both BUR and Single-Ply membrane.
org. CRRC is an advisory entity formed Materials are either plastic or rubber.
in 1998 responsible for establishing and The colors are black or gray with a solar
maintaining a rating system for cool roof reflectance of only about 0.05 to 0.2.
products. The initial values of solar reflec- Modified Bitumen Roofing consists
tance and thermal emittance of roofing of composite sheets of asphalt bitu-
materials are tested by CRRC-designated men modified with polymers. They are
agencies using ASTM procedures. CRRC installed in single or multiple layers, and
has listed over 600 rated roofing products the layers are adhered with hot asphalt,
as of early 2006. torching down, or cold adhesive.
www.energydesignresources.com 11
Cool Roof Coatings. Cool roof coatings
are commonly used in re-roofing projects.
They apply mostly bright white paint-like
materials to traditional roofs or metallic
surfaces. The coating extends the life of the
underlying roof materials and greatly in-
creases the solar reflectance. Cementitious
coatings use cement or ceramic particles
to enhance solar reflectance. They can be
sprayed, rolled, or brushed on the roof-
top. Properly selected and installed, they
perform well; however, they can be brittle
and crack, flake, or peel from surfaces over
time. An example is shown in Figure 6.
Thermoplastic coatings are new to the
California market. They have very good
UV resistance, a hard surface, and are dirt
resistant. The clear coat finish increases Figure 6: Cementitious Coating Cool Roof
durability and extends the life of the coat-
ing. These products have been used in
New Zealand and Australia for over 25
years. An example is shown in Figure 7.
Elastomeric coatings are also available, with
various polymers used for different types of
substrates.
www.energydesignresources.com 13
coatings made from cool-colored pigments and temperature have a significant impact
look similar to conventional tiles, but they on long-term performance. Generally,
offer improved solar reflectance values. manufacturers and roofing consultants
The steep-slope non-white roof can have a have the ability to select materials and
solar reflectance around 40% or 50%, but product formulations based upon known
that is not sufficient to qualify it as a cool local conditions.
roof under the 2005 Title 24 standards
At present, Title 24 requires initial mini-
[11]. The overall envelope approach or the
mum values (only) for solar reflectance
performance approach can be used to allow
and thermal emittance. In the cool roof
this kind of roof to be used to achieve Title
rulemaking, a degradation allowance for
24 compliance. In future updates of Title
performance was included: that is, in
24, a separate definition of “cool roof ”
determining cost-effectiveness, the CEC
applicable to steep slope buildings—a
assumed a long-term solar reflectance value
definition with a much lower reflectance
of 0.55, rather than a nominal value of
requirement—could be considered.
0.70, in calculating energy savings over the
life of the product. For minimally-compli-
ant materials rated at 0.70, this reduction
Long-Term Performance is about 21%; for materials initially rated at
0.80, this reduction amounts to about 31%
Cool roofs, like traditional ones, will suffer degradation. This approach is expected to
weathering and wear. Over time, the solar be conservative based upon extant research.
reflectance will gradually degrade. Various Once three-year values become available
studies show that a cool roof can lose up to based on the CRRC rating program, the
30% of its reflectance over a period of two CRRC database will include both initial
years, although considerably less degrada- and three year values for solar reflectance
tion is typical for most materials [10]. and thermal emittance.
The consensus view based on a number of
research findings is that the largest portion Washing a cool roof can effectively restore
of the reflectance loss happens relatively its performance, but the cost of wash-
quickly, such that most of the ultimate ing could be higher than the value of the
long-term loss occurs within the first year energy savings. “Self-cleaning” roofing
or two. products show promise for maintenance of
surfaces.
Example 1:
Re-roof (Coating) Application
www.energydesignresources.com 15
Example 2:
New Construction Application
Acknowledgments
Energy Design Resources provides information and design tools to architects, engineers,
lighting designers, and building owners and developers. Energy Design Resources is funded
by California utility customers and administered by Pacific Gas and Electric Company, San
Diego Gas and Electric, and Southern California Edison under the auspices of the Califor-
nia Public Utilities Commission. To learn more about Energy Design Resources, please visit
the Web site at www.energydesignresources.com.
This design brief was prepared for Energy Design Resources by Nexant, Inc., San Francisco,
CA. The authors cordially thank Dr. Lisa Gartland, PositivEnergy, and Mr. Peter Turnbull,
PG&E.
www.energydesignresources.com 17
References