STANDARD IPS GROOVE SPECIFICATIONS 25.

01
VICTAULIC® IS AN ISO 9001 CERTIFIED COMPANY

Standard Groove Specifications

STANDARD ROLL GROOVE SPECIFICATIONS FOR STEEL AND OTHER IPS PIPE †
B Standard Roll Groove Specifications
A B T 1 2 3 4 5 6 7 8
Dimensions – Inches/millimeters
Nom.
Pipe Pipe Outside Dia. O.D. Gasket Grv. Groove Dia. – C Groove Min. Max.
OD C Size Seat - A Width - B Tol. Depth Allow. Allow.
Inches Tolerance ±0.03 ±0.03 +0.000 D Wall Thk. Flare
mm Basic + – ±0,76 ±0,76 Basic +0,00 (ref.) T Dia.
3/ 1.050 0.010 0.010 0.625 0.281 0.938 –0.015 0.056 0.065 1.15
Exaggerated for Clarity 4
D 20 26,9 0,25 0,25 15,88 7,14 23,83 -0,38 1,42 1,65 29,2
Roll grooving removes no 1 1.315 0.013 0.013 0.625 0.281 1.190 –0.015 0.063 0.065 1.43
metal, cold forming a groove 25 33,7 0,33 0,33 15,88 7,14 30,23 -0,38 1,60 1,65 36,3
by the action of an upper male 11/4 1.660 0.016 0.016 0.625 0.281 1.535 –0.015 0.063 0.065 1.77
32 42,4 0,41 0,41 15,88 7,14 38,99 -0,38 1,60 1,65 45,0
roll being forced into pipe as it
is rotated by a lower female 11/2 1.900 0.019 0.019 0.625 0.281 1.775 –0.015 0.063 0.065 2.01
40 48,3 0,48 0,48 15,88 7,14 45,09 -0,38 1,60 1,65 51,1
drive roll.
2 2.375 0.024 0.024 0.625 0.344 2.250 –0.015 0.063 0.065 2.48
Roll groove configuration has 50 60,3 0,61 0,61 15,88 8,74 57,15 -0,38 1,60 1,65 63,0
rounded edges which reduce 21/2 2.875 0.029 0.029 0.625 0.344 2.720 –0.018 0.078 0.083 2.98
the available pipe end 65 73,0 0,74 0,74 15,88 8,74 69,09 -0,46 1,98 2,11 75,7
movement (expansion, 76,1 mm
3.000 0.030 0.030 0.625 0.344 2.845 –0.018 0.078 0.083 3.10
contraction and deflection). 76,1 0,76 0,76 15,88 8,74 72,26 -0,46 1,98 2,11 78,7
3 3.500 0.035 0.031 0.625 0.344 3.344 –0.018 0.078 0.083 3.60
Victaulic flexible coupling 80 88,9 0,89 0,79 15,88 8,74 84,94 -0,46 1,98 2,11 91,4
performance data reflects roll 31/2 4.000 0.040 0.031 0.625 0.344 3.834 –0.020 0.083 0.083 4.10
grooving specifications. For 90 101,6 1,02 0,79 15,88 8,74 97,38 -0,51 2,11 2,11 104,1
standard cut grooved pipe the 4 4.500 0.045 0.031 0.625 0.344 4.334 –0.020 0.083 0.083 4.60
Allowable Pipe End 100 114,3 1,14 0,79 15,88 8,74 110,08 -0,51 2,11 2,11 116,8
Separation and Deflection 4.250 0.043 0.031 0.625 0.344 4.084 –0.020 0.083 0.083 4.35
108,0 mm
figures may be doubled. Refer 108,0 1,09 0,79 15,88 8,74 103,73 -0,51 2,11 2,11 110,5
to Notes with the specific type 41/2 5.000 0.050 0.031 0.625 0.344 4.834 –0.020 0.083 0.095 5.10
coupling used. 120 127,0 1,27 0,79 15,88 8,74 122,78 -0,51 2,11 2,41 129,5
5.250 0.053 0.031 0.625 0.344 5.084 –0.020 0.083 0.109 5.35
NOTE: Coatings applied to the interior 133,0 mm 133,0 1,35 0,79 15,88 8,74 129,13 -0,51 2,11 2,77 135,9
surfaces, including bolt pad mating sur-
faces, of our grooved and bolted plain 5.500 0.056 0.031 0.625 0.344 5.334 –0.020 0.083 0.109 5.60
139,7 mm
end couplings should not exceed 139,7 1,42 0,79 15,88 8,74 135,48 -0,51 2,11 2,77 142,2
0.010" (0,25 mm). Also, the coating 5 5.563 0.056 0.031 0.625 0.344 5.395 –0.022 0.084 0.109 5.66
thickness applied to the gasket seating 125 141,3 1,42 0,79 15,88 8,74 137,03 -0,56 2,13 2,77 143,8
surface and within the groove on the
pipe exterior should not exceed 0.010" 6.000 0.056 0.031 0.625 0.344 5.830 –0.022 0.085 0.109 6.10
152,4 mm
(0,25 mm). 152,4 1,42 0,79 15,88 8,74 148,08 -0,56 2,16 2,77 154,9
6.250 0.063 0.031 0.625 0.344 6.032 –0.030 0.085 0.109 6.35
159,0 mm 159,0 1,60 0,79 15,88 8,74 153,21 -0,76 2,16 2,77 161,3
6.500 0.063 0.031 0.625 0.344 6.330 –0.022 0.085 0.109 6.60
165,1 mm 165,1 1,60 0,79 15,88 8,74 160,78 -0,56 2,16 2,77 167,6
6 6.625 0.063 0.031 0.625 0.344 6.455 –0.022 0.085 0.109 6.73
150 168,3 1,60 0,79 15,88 8,74 163,96 -0,56 2,16 2,77 170,9
8.000 0.063 0.031 0.750 0.469 7.816 –0.025 0.092 0.109 8.17
203,2 mm 203,2 1,60 0,79 19,05 11,91 198,53 -0,64 2,34 2,77 207,5
† On roll grooved pipe, Allowable Pipe End Separation and Deflection from Centerline will be 1/2 values listed for cut grooved pipe.
For 30 - 42" (750 - 1050 mm) roll groove dimensions contact Victaulic.

COLUMN 1: Nominal IPS Pipe size.


COLUMN 2: IPS outside diameter. The outside diameter of roll grooved pipe shall not vary more than the tolerance listed. For IPS pipe
the maximum allowable tolerance from square cut ends is 0.030" for 3/4 - 31/2"; 0.045" for 4 - 6"; and 0.060" for sizes 8" O.D. and above
measured from true square line.
COLUMN 3: Gasket seat. The pipe surface shall be free from indentations, roll marks, and projections from the end of the pipe to the
groove, to provide a leak-tight seal for the gasket. All loose paint, scale, dirt, chips, grease and rust must be removed. It continues to be
Victaulic’s first recommendation that pipe be square cut. When using beveled pipe contact Victaulic for details. Square cut pipe must be
used with FlushSeal® and EndSeal® gaskets. Gasket seat “A” is measured from the end of the pipe. IMPORTANT: Roll grooving of beveled
end pipe may result in unacceptable pipe end flare. See column 8.
COLUMN 4: Groove width. Bottom of groove to be free of loose dirt, chips, rust and scale that may interfere with proper coupling as-
sembly. Corners at bottom of groove must be radiused. For IPS steel pipe, .06R on 3/4 - 11/2", .08R on 2 - 6", .05R on 8" and up.
COLUMN 5: Groove outside diameter. The groove must be of uniform depth for the entire pipe circumference. Groove must be main-
tained within the “C” diameter tolerance listed.
COLUMN 6: Groove depth. For reference only. Groove must conform to the groove diameter “C” listed.
COLUMN 7: Minimum allowable wall thickness. This is the minimum wall thickness which may be roll grooved.
COLUMN 8: Maximum allowable pipe end flare diameter. Measured at the most extreme pipe end diameter square cut or beveled.

® REGISTERED TRADEMARK OF VICTAULIC – © COPYRIGHT 2001 VICTAULIC – PRINTED IN U.S.A. 1687 REV C

Victaulic Company of America • Phone: 1-800-PICK-VIC (1-800-742-5842) • Fax: 610-250-8817 • e-mail:[email protected]


Victaulic Company of Canada • Phone: 905-884-7444 • Fax: 905-884-9774 • e-mail: [email protected]
Victaulic Europe • Phone:32-9-381-1500 • Fax: 32-9-380-4438 • e-mail: [email protected] R

Victaulic America Latina • Phone: 610-559-3300 • Fax: 610-559-3608 • e-mail: [email protected]


Victaulic Asia Pacific • Phone: 65-6235-3035 • Fax: 65-6235-0535 • e-mail: [email protected]
25.01
Standard Roll Groove Specifications
1 2 3 4 5 6 7 8
Dimensions – Inches/millimeters
Nom.
Pipe Pipe Outside Dia. O.D. Gasket Grv. Groove Dia. – C Groove Min. Max.
Size Seat - A Width - B Tol. Depth Allow. Allow.
Inches Tolerance ±0.03 ±0.03 +0.000 D Wall Thk. Flare
mm Basic + – ±0,76 ±0,76 Basic +0,00 (ref.) T Dia.
8 8.625 0.063 0.031 0.750 0.469 8.441 –0.025 0.092 0.109 8.80
200 219,1 1,60 0,79 19,05 11,91 214,40 -0,64 2,34 2,77 223,5
10.000 0.063 0.031 0.750 0.469 9.812 –0.027 0.094 0.134 10.17
254,0 mm 254,0 1,60 0,79 19,05 11,91 249,23 -0,69 2,39 3,40 258,3
10 10.750 0.063 0.031 0.750 0.469 10.562 –0.027 0.094 0.134 10.92
250 273,0 1,60 0,79 19,05 11,91 268,28 -0,69 2,39 3,40 277,4
12.000 0.063 0.031 0.750 0.469 11.781 –0.030 0.109 0.156 12.17
304,8 mm 304,8 1,60 0,79 19,05 11,91 299,24 -0,76 2,77 3,96 309,1
12 12.750 0.063 0.031 0.750 0.469 12.531 –0.030 0.109 0.156 12.92
300 323,9 1,60 0,79 19,05 11,91 318,29 -0,76 2,77 3,96 328,2
14 14.000 0.063 0.031 0.938 0.469 13.781 –0.030 0.109 0.156 14.16
350 355,6 1,60 0,79 23,83 11,91 350,04 -0,76 2,77 3,96 359,7
15 15.000 0.063 0.031 0.938 0.469 14.781 –0.030 0.109 0.165 15.16
375 381,0 1,60 0,79 23,83 11,91 375,44 -0,76 2,77 4,19 385,1
16 16.000 0.063 0.031 0.938 0.469 15.781 –0.030 0.109 0.165 16.16
100 406,4 1,60 0,79 23,83 11,91 400,84 -0,76 2,77 4,19 410,5
18 18.000 0.063 0.031 1.000 0.469 17.781 –0.030 0.109 0.165 18.16
450 457,2 1,60 0,79 25,40 11,91 451,64 -0,76 2,77 4,19 461,3
20 20.000 0.063 0.031 1.000 0.469 19.781 –0.030 0.109 0.188 20.16
500 508,0 1,60 0,79 25,40 11,91 502,44 -0,76 2,77 4,78 512,1
22 22.000 0.063 0.031 1.000 0.500 21.656 –0.030 0.172 0.188 22.20
550 559,0 1,60 0,79 25,40 12,70 550,06 -0,76 4,37 4,78 563,9
24 24.000 0.063 0.031 1.000 0.500 23.656 –0.030 0.172 0.218 24.20
600 610,0 1,60 0,79 25,40 12,70 600,86 -0,76 4,37 5,54 614,7
26 O.D. 26.00 0.093 0.031 1.75 0.625 25.50 –0.063 0.250 0.250 26.20
650 660,4 2,36 0,79 44,45 15,88 647,7 –1,60 6,35 6,35 665,5
28 O.D. 28.00 0.093 0.031 1.75 0.625 27.50 –0.063 0.250 0.250 28.20
700 711,0 2,36 0,79 44,45 15,88 698,50 –1,60 6,35 6,35 716,3
30 O.D. 30.00 0.093 0.031 1.75 0.625 29.50 –0.063 0.250 0.250 30.20
750 762,0 2,36 0,79 44,45 15,88 749,30 –1,60 6,35 6,35 767,1
32 O.D. 32.00 0.093 0.031 1.75 0.625 31.50 –0.063 0.250 0.250 32.20
800 813,0 2,36 0,79 44,45 15,88 800,10 –1,60 6,35 6,35 817,9
36 O.D. 36.00 0.093 0.031 1.75 0.625 35.50 –0.063 0.250 0.250 36.20
900 914,0 2,36 0,79 44,45 15,88 901,70 –1,60 6,35 6,35 919,5
42 O.D. 42.00 0.093 0.031 2.00 0.625 41.50 –0.063 0.250 0.250 42.20
1050 1067,0 2,36 0,79 50,80 15,88 1054,10 –1,60 6,35 6,35 1071,8
† On roll grooved pipe, Allowable Pipe End Separation and Deflection from Centerline will be 1/2 values listed for cut grooved pipe.
For 30 - 42" (750 - 1050 mm) roll groove dimensions contact Victaulic.

COLUMN 1: Nominal IPS Pipe size.


COLUMN 2: IPS outside diameter. The outside diameter of roll grooved pipe shall not vary more than the tolerance listed. For IPS pipe
the maximum allowable tolerance from square cut ends is 0.030" for 3/4 - 31/2"; 0.045" for 4 - 6"; and 0.060" for sizes 8" O.D. and above
measured from true square line.
COLUMN 3: Gasket seat. The pipe surface shall be free from indentations, roll marks, and projections from the end of the pipe to the
groove, to provide a leak-tight seal for the gasket. All loose paint, scale, dirt, chips, grease and rust must be removed. It continues to be
Victaulic’s first recommendation that pipe be square cut. When using beveled pipe contact Victaulic for details. Square cut pipe must be
used with FlushSeal® and EndSeal® gaskets. Gasket seat “A” is measured from the end of the pipe. IMPORTANT: Roll grooving of beveled
end pipe may result in unacceptable pipe end flare. See column 8.
COLUMN 4: Groove width. Bottom of groove to be free of loose dirt, chips, rust and scale that may interfere with proper coupling as-
sembly. Corners at bottom of groove must be radiused. For IPS steel pipe, .06R on 3/4 - 11/2", .08R on 2 - 6", .05R on 8" and up.
COLUMN 5: Groove outside diameter. The groove must be of uniform depth for the entire pipe circumference. Groove must be main-
tained within the “C” diameter tolerance listed.
COLUMN 6: Groove depth. For reference only. Groove must conform to the groove diameter “C” listed.
COLUMN 7: Minimum allowable wall thickness. This is the minimum wall thickness which may be roll grooved.
COLUMN 8: Maximum allowable pipe end flare diameter. Measured at the most extreme pipe end diameter square cut or beveled.

2 Standard Groove Specifications


25.01

STANDARD CUT GROOVE SPECIFICATIONS FOR STEEL AND OTHER IPS PIPE
Standard Cut Groove Specifications
B
A B T 1 2 3 4 5 6 7
Dimensions – Inches/millimeters
Nom.
Pipe Pipe Outside Dia. O.D. Gasket Seat Grv. Groove Dia. – C Groove Min.
OD C Size -A Width - B Tol. Depth Allow.
Inches Tolerance ±0.03 ±0.03 +0.000 D Wall Thk.
mm Basic + – ±0,76 ±0,76 Basic +0,00 (ref.) T
3/ 1.050 0.010 0.010 0.625 0.313 0.938 –0.015 0.056 0.113
4

Exaggerated for Clarity 20 26,9 0,25 0,25 15,88 7,95 23,83 –0,38 1,42 2,87
D
1 1.315 0.013 0.013 0.625 0.313 1.190 –0.015 0.063 0.133
Cut grooving standard steel 25 33,7 0,33 0,33 15,88 7,95 30,23 –0,38 1,60 3,38
pipe removes less metal, to 11/4 1.660 0.016 0.016 0.625 0.313 1.535 –0.015 0.063 0.140
less depth, than threading, 32 42,4 0,41 0,41 15,88 7,95 38,99 –0,38 1,60 3,56
maintaining the desired 11/2 1.900 0.019 0.019 0.625 0.313 1.775 –0.015 0.063 0.145
integrity of the pipe. 40 48,3 0,48 0,48 15,88 7,95 45,09 –0,38 1,60 3,68
Victaulic flexible coupling 2 2.375 0.024 0.024 0.625 0.313 2.250 –0.015 0.063 0.154
performance data reflects roll 50 60,3 0,61 0,61 15,88 7,95 57,15 –0,38 1,60 3,91
grooving specifications. For 21/2 2.875 0.029 0.029 0.625 0.313 2.720 –0.018 0.078 0.188
standard cut grooved pipe the 65 73,0 0,74 0,74 15,88 7,95 69,09 –0,46 1,98 4,78
Allowable Pipe End 76,1 mm
3.000 0.030 0.030 0.625 0.313 2.845 –0.018 0.078 0.188
Separation and Deflection 76,1 0,76 0,76 15,88 7,95 72,26 –0,46 1,98 4,78
figures may be doubled. Refer 3 3.500 0.035 0.031 0.625 0.313 3.344 –0.018 0.078 0.188
80 88,9 0,89 0,79 15,88 7,95 84,94 –0,46 1,98 4,78
to Notes with the specific type
coupling used. 31/2 4.000 0.040 0.031 0.625 0.313 3.834 –0.020 0.083 0.188
90 101,6 1,02 0,79 15,88 7,95 97,38 –0,51 2,11 4,78
4 4.500 0.045 0.031 0.625 0.375 4.334 –0.020 0.083 0.203
100 114,3 1.14 0.79 15.88 9.53 110.08 –0.51 2.11 5.16
41/2 5.000 0.050 0.031 0.625 0.375 4.834 –0.020 0.083 0.203
120 127,0 1,27 0,79 15,88 9,53 122,78 –0,51 2,11 5,16
5.500 0.056 0.031 0.625 0.375 5.334 –0.020 0.083 0.203
139,7 mm 139,7 1,42 0,79 15,88 9,53 135,48 –0,51 2,11 5,16
5 5.563 0.056 0.031 0.625 0.375 5.395 –0.020 0.084 0.203
125 141,3 1,42 0,79 15,88 9,53 137,03 –0,51 2,13 5,16
6.000 0.056 0.031 0.625 0.375 5.830 –0.022 0.085 0.219
152,4 mm 152,4 1,42 0,79 15,88 9,53 148,08 –0,56 2,16 5,56
6.500 0.063 0.031 0.625 0.375 6.330 –0.022 0.085 0.219
165,1 mm 165,1 1,60 0,79 15,88 9,53 160,78 –0,56 2,16 5,56
6 6.625 0.063 0.031 0.625 0.375 6.455 –0.022 0.085 0.219
150 168,3 1,60 0,79 15,88 9,53 163,96 –0,56 2,16 5,56
8.000 0.063 0.031 0.750 0.438 7.816 –0.022 0.092 0.238
203,2 mm 203,2 1,60 0,79 19,05 11,13 198,53 –0,56 2,34 6,05
8 8.625 0.063 0.031 0.750 0.438 8.441 –0.025 0.092 0.238
200 219,1 1,60 0,79 19,05 11,13 214,40 –0,64 2,34 6,05
10.000 0.063 0.031 0.750 0.500 9.812 –0.025 0.094 0.250
254,0 mm 254,0 1,60 0,79 19,05 12,70 249,23 –0,64 2,39 6,35
10 10.750 0.063 0.031 0.750 0.500 10.562 –0.027 0.094 0.250
250 273,0 1,60 0,79 19,05 12,70 268,28 –0,69 2,39 6,35
12.000 0.063 0.031 0.750 0.500 11.781 –0.027 0.109 0.279
304,8 mm 304,8 1,60 0,79 19,05 12,70 299,24 –0,69 2,77 7,09
12 12.750 0.063 0.031 0.750 0.500 12.531 –0.030 0.109 0.279
300 323,9 1,60 0,79 19,05 12,70 318,29 –0,76 2,77 7,09
14 14.000 0.063 0.031 0.938 0.500 13.781 –0.030 0.109 0.281
350 355,6 1,60 0,79 23,83 12,70 350,04 –0,76 2,77 7,14
15 15.000 0.063 0.031 0.938 0.500 14.781 –0.030 0.109 0.312
375 381,0 1,60 0,79 23,83 12,70 375,44 –0,76 2,77 7,92
* 9/16" (14 mm) width groove is required in sizes 22 - 24" (550 - 600 mm) in order to obtain the maximum allowable pipe end movement
listed in Performance Data Charts. 1/2" (12 mm) width groove will give 1/2 the maximum allowance shown for 22 - 24" (550 - 600 mm). For
double groove tool bit information, contact Victaulic.

COLUMN 1: Nominal IPS Pipe size.


COLUMN 2: IPS outside diameter. The outside diameter of cut grooved pipe shall not vary more than the tolerance listed. For IPS pipe
the maximum allowable tolerance from square cut ends to 0.030" for 3/4 - 31/2"; 0.045" for 4 - 6"; and 0.060" for sizes 8" O.D. and above
measured from true square line.
COLUMN 3: Gasket seat. The pipe surface shall be free from indentations, roll marks, and projections from the end of the pipe to the
groove, to provide a leak-tight seal for the gasket. All loose paint, scale, dirt, chips, grease and rust must be removed. It continues to be
Victaulic’s first recommendation that pipe be square cut. When using beveled pipe contact Victaulic for details. Square cut pipe must be
used with FlushSeal® and EndSeal® gaskets. Gasket seat “A” is measured from the end of the pipe.
COLUMN 4: Groove width. The bottom of groove to be free of loose dirt, chips, rust and scale that may interfere with proper coupling
assembly. Maximum permissible radius at bottom of groove is .015".
COLUMN 5: Groove outside diameter. The groove must be of uniform depth for the entire pipe circumference. Groove must be main-
tained within the “C” diameter tolerance listed.
COLUMN 6: Groove depth. For reference only. Groove must conform to the groove diameter “C” listed.
COLUMN 7: Minimum allowable wall thickness. This is the minimum wall thickness which may be cut grooved.

Standard Groove Specifications 3


25.01
Standard Cut Groove Specifications
1 2 3 4 5 6 7
Dimensions – Inches/millimeters
Nom.
Pipe Pipe Outside Dia. O.D. Gasket Seat Grv. Groove Dia. – C Groove Min.
Size -A Width - B Tol. Depth Allow.
Inches Tolerance ±0.03 ±0.03 +0.000 D Wall Thk.
mm Basic + – ±0,76 ±0,76 Basic +0,00 (ref.) T
16 16.000 0.063 0.031 0.938 0.500 15.781 –0.030 0.109 0.312
100 406,4 1,60 0,79 23,83 12,70 400,84 –0,76 2,77 7,92
18 18.000 0.063 0.031 1.000 0.500 17.781 –0.030 0.109 0.312
450 457,2 1,60 0,79 25,40 12,70 451,64 –0,76 2,77 7,92
20 20.000 0.063 0.031 1.000 0.500 19.781 –0.030 0.109 0.312
500 508,0 1,60 0,79 25,40 12,70 502,44 –0,76 2,77 7,92
22 22.000 0.063 0.031 1.000 0.563* 21.656 –0.030 0.172 0.375
550 559,0 1,60 0,79 25,40 14,30 550,06 –0,76 4,37 9,53
24 24.000 0.063 0.031 1.000 0.563* 23.656 –0.030 0.172 0.375
600 610,0 1,60 0,79 25,40 14,30 600,86 –0,76 4,37 9,53
26 O.D. 26.00 0.093 0.031 1.75 0.625 25.50 –0.063 0.250 0.625
650 660,4 2,36 0,79 44,45 15,88 647,7 –1,60 6,35 15,88
28 O.D. 28.00 0.093 0.031 1.75 0.625 27.50 –0.063 0.250 0.625
700 711,0 2,36 0,79 44,45 15,88 698,50 –1,60 6,35 15,88
30 O.D. 30.00 0.093 0.031 1.75 0.625 29.50 –0.063 0.250 0.625
750 762,0 2,36 0,79 44,45 15,88 749,30 –1,60 6,35 15,88
32 O.D. 32.00 0.093 0.031 1.75 0.625 31.50 –0.063 0.250 0.625
800 813,0 2,36 0,79 44,45 15,88 800,10 –1,60 6,35 15,88
36 O.D. 36.00 0.093 0.031 1.75 0.625 35.50 –0.063 0.250 0.625
900 914,0 2,36 0,79 44,45 15,88 901,70 –1,60 6,35 15,88
42 O.D. 42.00 0.093 0.031 2.00 0.625 41.50 –0.063 0.250 0.625
1050 1067,0 2,36 0,79 50,80 15,88 1054,10 –1,60 6,35 15,88
* 9/16" (14 mm) width groove is required in sizes 22 - 24" (550 - 600 mm) in order to obtain the maximum allowable pipe end movement
listed in Performance Data Charts. 1/2" (12 mm) width groove will give 1/2 the maximum allowance shown for 22 - 24" (550 - 600 mm). For
double groove tool bit information, contact Victaulic.

COLUMN 1: Nominal IPS Pipe size.


COLUMN 2: IPS outside diameter. The outside diameter of cut grooved pipe shall not vary more than the tolerance listed. For IPS pipe
the maximum allowable tolerance from square cut ends to 0.030" for 3/4 - 31/2"; 0.045" for 4 - 6"; and 0.060" for sizes 8" O.D. and above
measured from true square line.
COLUMN 3: Gasket seat. The pipe surface shall be free from indentations, roll marks, and projections from the end of the pipe to the
groove, to provide a leak-tight seal for the gasket. All loose paint, scale, dirt, chips, grease and rust must be removed. It continues to be
Victaulic’s first recommendation that pipe be square cut. When using beveled pipe contact Victaulic for details. Square cut pipe must be
used with FlushSeal® and EndSeal® gaskets. Gasket seat “A” is measured from the end of the pipe.
COLUMN 4: Groove width. The bottom of groove to be free of loose dirt, chips, rust and scale that may interfere with proper coupling
assembly. Maximum permissible radius at bottom of groove is .015".
COLUMN 5: Groove outside diameter. The groove must be of uniform depth for the entire pipe circumference. Groove must be main-
tained within the “C” diameter tolerance listed.
COLUMN 6: Groove depth. For reference only. Groove must conform to the groove diameter “C” listed.
COLUMN 7: Minimum allowable wall thickness. This is the minimum wall thickness which may be cut grooved.

This product shall be manufactured by Victaulic Company. All products shall be installed in accordance with current Victaulic installation/assembly instructions.