Anybus Communicator - PROFIBUS DP Interface Installation Sheet

This document provides an installation summary for the Anybus Communicator PROFIBUS DP Interface module. The summary includes: - Mounting the Communicator on a DIN rail and connecting it to the PROFIBUS network and subnetwork. - Powering on the Communicator and connecting it to a PC using a configuration cable. - Configuring the module using Anybus Configuration Manager software, including setting the node address with switches. - Including the Communicator's GSD file in the PROFIBUS configuration tool and configuring/starting the network. The document also lists required accessories and provides LED indicator meanings and locations for the module connectors, switches, and certification information.

Uploaded by

Johan Fourie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
233 views2 pages

Anybus Communicator - PROFIBUS DP Interface Installation Sheet

This document provides an installation summary for the Anybus Communicator PROFIBUS DP Interface module. The summary includes: - Mounting the Communicator on a DIN rail and connecting it to the PROFIBUS network and subnetwork. - Powering on the Communicator and connecting it to a PC using a configuration cable. - Configuring the module using Anybus Configuration Manager software, including setting the node address with switches. - Including the Communicator's GSD file in the PROFIBUS configuration tool and configuring/starting the network. The document also lists required accessories and provides LED indicator meanings and locations for the module connectors, switches, and certification information.

Uploaded by

Johan Fourie
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Anybus Communicator - PROFIBUS DP Interface Installation Sheet

Module Front LED Indicators Accessories Checklist


LED no Indication Meaning
1 (Online) Green Online
LED Indicators Off Not online The following items are required for installation:
1 2 2 (Offline) Red Offline
Off Not offline
3 (Not used) - - • Anybus Communicator Resource CD (Includes configuration
3 4 4 (Fieldbus Diagnostics) Off No diagnostics present software, manuals, GSD file and application notes)
Red, flashing 1Hz Configuration error • RS232 configuration cable
Red, flashing 2Hz User parameter data error • Subnetwork connector
Red, flashing 4Hz Initialization error
5 6 • PROFIBUS network cable and connector (not included)
5 (Subnet Status) Flashing green Running, but one or more transaction errors
Green Running
A Red Transaction error/timeout or subnet stopped Installation and Startup Summary
Configuration Switches 6 (Device Status) Off Power off
Alternating red/green Invalid or missing configuration
Green Initializing • Mount the Communicator on the DIN-rail.
B Flashing green Running • Connect the Communicator to the PROFIBUS network.
Red Bootloader mode
Flashing red Note the flash sequence pattern and contact • Connect the Communicator to the subnetwork.
the HMS support department • Power on the Communicator (+24 V DC).
• Connect the configuration cable between the Communicator
and the PC containing the Anybus Configuration Manager
PROFIBUS Connector Configuration Switches software (ACM).
A B
• Configure the module using ACM.
Set the PROFIBUS node address by using the switches as follows: • Include the Anybus Communicator GSD file in the
Node address = (switch B * 10) + (switch A * 1) PROFIBUS configuration tool.
• Configure and start the PROFIBUS network.

Switch A 2
Example:
Setting node address 42

Switch B 4

Bottom View
PC Connector: Subnetwork Connector
1. GND Pin no. Description
2. GND
1
PROFIBUS Connector
3. RS232 Rx 1 +5V OUT
4
4. RS232 Tx 2 RS232 Rx Pin no Description
3 RS232 Tx 1 Shield
9
5 5 (female) 1
4 NC 3 B-line

6
5 Signal GND 4 RTS
1

6 RS422 Rx+ 9 6 5 GND bus


Power:
1. +24 V DC 7 RS422 Rx- 6 +5V bus out
1
2. GND 8 RS485+ / RS422 Tx+ 8 A-line
2 Further information and documents about this product can be
9 RS485- / RS422 Tx- 2, 7, 9 NC
found at the product pages on www.anybus.com.

SP0632, rev. 1.20, Mar 2015 www.anybus.com


Anybus Communicator Installation Sheet

UL Certification Additional installation and operating EMC Compliance (CE)


instructions

IND: CONT. EQ.


Max Ambient Temperature: 55°C (for Hazloc environments)
FOR HAZ LOC.
CL I, DIV 2
GP A,B,C,D Field wiring terminal markings (wire type (Cu only, 14-30 AWG)).
TEMP
CODE
E203225
Use 60/75 or 75°C copper (Cu) wire only.

Terminal tightening torque must be between 5-7 lb-in (0.5 - 0.8


Warnings Nm). This product is in accordance with the EMC directive 89/336/EEC,
with amendments 92/31/EEC and 93/68/EEC through conformance
• WARNING - EXPLOSION HAZARD - SUBSTITUTION OF Use in overvoltage category 1 pollution degree 2 environment. with the following standards:
ANY COMPONENTS MAY IMPAIR SUITABILITY FOR
CLASS I, DIVISION 2. Installed in an enclosure considered representative of the in- • EN 50082-2 (1993)
tended use. EN 55011 (1990) Class A
• WARNING - EXPLOSION HAZARD - WHEN IN
HAZARDOUS LOCATIONS, TURN OFF POWER BEFORE Secondary circuit intended to be supplied from an isolating • EN 61000-6-2 (1999)
REPLACING OR WIRING MODULES. source and protected by overcurrent protective devices installed EN 61000-4-3 (1996) 10 V/m
in the field sized per the following: EN 61000-4-6 (1996) 10 V/m (all ports)
• WARNING - EXPLOSION HAZARD - DO NOT EN 61000-4-2 (1995) ±8 kV Air Discharge
Control-circuit Wire Size Maximum Protective Device ±4 kV Contact discharge
DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
Rating EN 61000-4-4 (1995) ±2 kV Power port
SWITCHED OFF OR THE AREA IS KNOWN TO BE
NONHAZARDOUS. AWG (mm2) Amperes ±1 kV Other ports
22 (0.32) 3 EN 61000-4-5 (1995) ±0.5 kV Power ports (DM/CM)
20 (0.52) 5 ±1 kV Signal ports
18 (0.82) 7
16 (1.3) 10
14 (2.1) 20
Attention! 12 (3.3) 25

• ATTENTION – RISQUE D’EXPLOSION – LE REM-


PLACEMENT DE TOUT COMPOSANTS INVALIDE LA
CERTIFICATION CLASS I, DIVISION 2.

• ATTENTION – RISQUE D’EXPLOSION – EN ZONE


EXPLOSIVE, VEUILLEZ COUPER L’ALIMENTATION
ÉLECTRIQUE AVANT LE REMPLACEMENT OU LE
RACCORDEMENT DES MODULES.

• ATTENTION – RISQUE D’EXPLOSION – NE PAS


DÉCONNECTER L’ÉQUIPEMENT TANT QUE
L’ALIMENTATION EST TOUJOURS PRÉSENTE OU
QUE LE PRODUIT EST TOUJOURS EN ZONE EXPLO-
SIVE ACTIVE.
Further information and documents about this product can be
found at the product pages on www.anybus.com.

www.anybus.com