Iecex Certificate of Conformity

1. This certificate verifies that synchronous generator models DG185ZL-04 meet IEC standards for explosive gas atmospheres. 2. The generators were tested and found to comply with IEC 60079-0 and IEC 60079-15 for type of protection "nA". 3. The certificate lists specific serial numbers, provides details on the generator design and electrical ratings, and notes specific conditions of use regarding current transformers and opening enclosures in explosive atmospheres.

Uploaded by

sithulibra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
148 views3 pages

Iecex Certificate of Conformity

1. This certificate verifies that synchronous generator models DG185ZL-04 meet IEC standards for explosive gas atmospheres. 2. The generators were tested and found to comply with IEC 60079-0 and IEC 60079-15 for type of protection "nA". 3. The certificate lists specific serial numbers, provides details on the generator design and electrical ratings, and notes specific conditions of use regarding current transformers and opening enclosures in explosive atmospheres.

Uploaded by

sithulibra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

IECEx Certificate

of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
for rules and details of the IECEx Scheme visit www.iecex.com
UNIT VERIFICATION

Certificate No.: IECEx DEK 11.0102X Issue No: 0 Certificate history:


Issue No. 0 (2012-07-10)
Status: Current Page 1 of 3

Date of Issue: 2012-07-10

Applicant: Brush HMA B.V.


Ringdijk 390 B
2983 GS Ridderkerk
The Netherlands

Equipment: Synchronous Generator Type DG185ZL-04


Serial number(s) or 410253.01, 410253.02, 410254, 410255.01, 410255.02, 410255.03, 410255.04
Unique Identification:

Type of Protection: nA

Marking: Ex nA d e mb (nL) op is II(n-pentane) T3


Ex nA d e mb (nL) nC op is II(n-pentane) T3 (with flux probe / partial discharge monitor)

Approved for issue on behalf of the IECEx T. Pijpker


Certification Body:

Position: Certification Manager

Signature:
(for printed version)

Date:

1. This certificate and schedule may only be reproduced in full.


2. This certificate is not transferable and remains the property of the issuing body.
3. The Status and authenticity of this certificate may be verified by visiting the Official IECEx Website.

Certificate issued by:


DEKRA Certification B.V.
Utrechtseweg 310
6812 AR Arnhem
The Netherlands
IECEx Certificate
of Conformity
Certificate No: IECEx DEK 11.0102X Issue No: 0

Date of Issue: 2012-07-10


Page 2 of 3

Manufacturer: Brush HMA B.V.


Ringdijk 390 B
2983 GS Ridderkerk
The Netherlands

Additional Manufacturing location(s):


Brush HMA B.V.
Ringdijk 390 B
2983 GS Ridderkerk
The Netherlands

This Unit verification certificate is issued as verification that the Apparatus identified on page 1, was assessed and tested and found to comply
with the IEC Standard list below. This certificate is granted subject to the conditions as set out in IECEx Scheme Rules, IECEx 02 and
Operational Documents as amended.

STANDARDS:
The electrical apparatus and any acceptable variations to it specified in the schedule of this certificate and the identified documents, was found
to comply with the following standards:

IEC 60079-0 : 2004 Electrical apparatus for explosive gas atmospheres - Part 0: General requirements
Edition:4.0
IEC 60079-15 : 2005-03 Electrical apparatus for explosive gas atmospheres Part 15: Construction, test and Marking of Type of
Edition:3 Protection "n" electrical apparatus

This Certificate does not indicate compliance with electrical safety and performance requirements other than those expressly included in the

Standards listed above.

TEST & ASSESSMENT REPORTS:


The Apparatus listed has successfully met the examination and test requirements as recorded in

Test Report:

NL/DEK/ExTR11.0118/00 NL/DEK/ExTR12.0031/00

Quality Assessment Report:


As this is a Unit Verification Certificate, no QAR is applicable as this certificate is specific to the items listed by serial number or other unique
identification.

NL/DEK/QAR11.0042/00
IECEx Certificate
of Conformity
Certificate No: IECEx DEK 11.0102X Issue No: 0

Date of Issue: 2012-07-10


Page 3 of 3

Schedule

EQUIPMENT:
Equipment and systems covered by this certificate are as follows:

Description

The generator of Type DG185ZL-04 of the design nos. 2082150ZL9 and 2082250ZL1 are non-sparking 3 phase, 4 pole, synchronous
generator with brushless exciter and closed, water cooled, air ventilation circuit.

The synchronous generator is in type of protection nA, the auxiliary equipment in types of protection Ex d, e, mb, (nL), op is and
additionally nC when equipped with partial discharge monitor and air gap flux probe.

Ambient temperature range: -5 °C to +40 °C


Method of cooling: IC 8A1W7
Rated cooling water temperature: +25 °C

Electrical data

Rated voltage:    11 kV
Rated Output:    30 MVA at power factor 0.80
Frequency:    50 Hz
Speed:     1 500 rpm

SPECIFIC CONDITIONS OF USE: YES as shown below:

The secondary circuit of the current transformers must be closed at all time.

Enclosures shall not be opened when an explosive atmosphere may be present.