FDC PDF
FDC PDF
RESPONSE
Saving life and property through effective licensing, plan review,
and inspection of fire protection systems.
August 2006
The required number of inlet connections varies depending on the type and demand of the system being
served. For fire sprinkler systems, NFPA 13(99) 5-15.2.2 requires a 4" pipe size for fire engine connections. Exception #2
allows a single-outlet FDC where piped to a 3" or smaller riser. These criteria indicate that unless the riser of the sprinkler
system is 3" or smaller, the FDC must have a minimum of two connections. There is no other criterion in NFPA 13 requiring
more than two connections. For standpipe systems, NFPA 14(00) 2-8.2 requires each FDC to have at least two 2-1/2" internal
threaded swivel fittings. Further 14(00) 5-7 requires standpipe systems to be designed so that the system demand can be
supplied by both the attached water supply, where required, and fire department connections. There is no explicit requirement
for an FDC to have a 4-way connection. However, if the standpipe demand is such that it cannot be adequately supplied through
a 2-way FDC, 14(00) 5-7 provides a basis for requiring additional connections.
Siamese connections are most commonly located on the side of buildings, but may also be located remote from
the building. These are know as “freestanding” or “sidewalk” FDCs. NFPA 13 requires the fire department
connection to be located on the street side of buildings and the Minnesota State Fire Marshal policy FP-03 further
clarifies the location as the address side of buildings. There are situations where locating the FDC in these
locations is impractical (i.e. large shopping malls). It is important that the fire department connection be provided
at a location approved by the local fire official.
A less common type of FDC that is utilized is known as a “Storz” type fire department connection. These are
typically used for large diameter hose connections. This connection features two to three lugs for "quick"
connection of the fitting, depending on hose diameter. Storz connections are currently not listed for use in fire
protection systems. It is important that the hose lines between the pumper truck and the Storz connection are
properly rated for the higher pressures produced by the pumper truck.
Siamese connections are to be equipped with plugs or caps. This is to prevent dirt and other foreign objects
from entering the piping, which would inhibit water flow or prevent the connection from being used during an
emergency. It is important to replace broken or missing caps to maintain the connections in working order.
To prevent water from collecting in the piping between the check valve and the inlet body, an automatic drip
is to be installed at the lowest point of the FDC piping. Without the automatic drip any collected water could
freeze and prevent use of the fire department connection under fire conditions.