0% found this document useful (0 votes)
683 views1 page

Fire Sprinkler Heat Collector

The document discusses heat collectors, which are sometimes used above sprinklers when the sprinklers are too far below the ceiling. However, the document provides three key reasons why heat collectors are not appropriate and can actually delay sprinkler activation: 1) There is no scientific data that supports their use or performance. Testing has shown heat collectors can delay response by creating dead air space above the sprinkler. 2) Convective heat, which supplies over 80% of the heat needed for activation, requires air flow past the sprinkler, which heat collectors can disrupt. 3) Sprinklers are designed to be within 12 inches of the roof or ceiling to cool structural members, which
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
683 views1 page

Fire Sprinkler Heat Collector

The document discusses heat collectors, which are sometimes used above sprinklers when the sprinklers are too far below the ceiling. However, the document provides three key reasons why heat collectors are not appropriate and can actually delay sprinkler activation: 1) There is no scientific data that supports their use or performance. Testing has shown heat collectors can delay response by creating dead air space above the sprinkler. 2) Convective heat, which supplies over 80% of the heat needed for activation, requires air flow past the sprinkler, which heat collectors can disrupt. 3) Sprinklers are designed to be within 12 inches of the roof or ceiling to cool structural members, which
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

QUICK

RESPONSE
Saving life and property through effective licensing, plan review,
and inspection of fire protection systems.
April 2011

Heat Collector

The concept of placing a small “heat collector” above a sprinkler to assist in activation is not
appropriate nor has it been contemplated in the NFPA standards. This is not new to the standards
although the practice of using such devices at times has been misused. New language in the 2010
edition of NFPA 13 (Section 8.5.4.1.4) reinforces the position that the use of heat collectors does not
comply with the requirements in NFPA 13.

Heat collectors, which usually take the form of round or square metal baffles, or "pie plates," are
occasionally prescribed where sprinklers are suspended too far below a ceiling or where there are other
concerns about timely response. Ironically, they can do more harm than good. While these devices may
seem like a logical solution to an immediate problem, there is no engineering or scientific data that
supports their use or performance. In fact, there is evidence that objects like this above a sprinkler will
delay its activation. A ceiling jet moving above this deflector could not reach the sprinkler.

Work done at Factory Mutual showed that convective heat


typically supplies more than 80 percent of the heat sprinklers
need for activation. However, convective heat requires a flow
of air past the sprinkler, and testing has shown that heat
collectors with edges, such as inverted boxes, can actually
delay sprinkler response, presumably because they create
dead air space. Even flat heat collectors are only effective
where the edge of the heat collector picks up the fire plume
and acts like a small ceiling. To work effectively, the
combined areas of heat collectors need to make up a large
percentage of the floor area.

Sprinklers are to be located within 12" of the roof deck (with a


few exceptions). The rules describing the maximum distance
permitted for sprinklers below ceilings must be followed. One
of the objectives of the standard is to cool the ceiling near the Exhibit 1: “Heat collector”
structural members with spray from a nearby sprinkler, which improperly utilized in lieu of proper
is not accomplished by a sprinkler far down from the ceiling sprinkler placement.
and a heat collector will not help this situation.

Water shields used on in-rack sprinklers should not be confused with heat collectors. They are sized to
prevent water discharge from higher sprinklers from wetting and cooling the lower sprinkler operating
mechanisms, thus inhibiting proper activation.