Three-Phase Rectifiers: Principles of Operation, Analysis and Performance Evaluation
Three-Phase Rectifiers: Principles of Operation, Analysis and Performance Evaluation
1 Introduction
Fig.1 shows the power circuit configuration of a half-wave rectifier circuit. The
supply is a 3-phase balanced voltage source, where:
𝑣1 = 𝑉𝑚 sin 𝜔𝑡,
2𝜋
𝑣2 = 𝑉𝑚 sin(𝜔𝑡 − ),
3
4𝜋
𝑣2 = 𝑉𝑚 sin (𝜔𝑡 − ) (1)
3
where vm is the peak value of the phase voltage, SCRs (1, 2, 3) forms the
positive half-wave rectifier switches. The rectifier of this form is referred to as
the positive rectifying group (PRG).
The load is assumed pure resistive. This will allow better understanding of the
principle of operation.
If a negative rectifying group (NRG), i.e., SCRs (1’, 2’ and 3’) is added as
shown in Fig.2, the rectifier becomes Three-Phase Full-Wave Rectifier.
Page | 1
Also, the numbering system of the SCRs shown is not the conventional standard
numbering system. The Shown numbering system is employed to better
understanding of the system operation.
In general, M-phase rectifier circuits can be used. However, since the available
power supply is three-phase, M-phase rectifiers are rarely used in recent days. It
was developed and used in the late 1980s and 1990s of the last century,
especially for battery charging by the communication systems. The design and
maintenance complexity of such systems results in the come back to three-phase
rectifier systems.
(a) With full-wave rectifiers, the input (supply) current waveform has zero
average value. This is very demanding and required by the Electric
Utilities, since no system transformer saturation is possible if the DC input
current is zero. This is not the case with half-wave rectifiers circuits.
Page | 2
(b) More average load voltage and current (and hence more power) from the
same supply is obtained by full-wave rectifiers, since the output average
voltage is doubled when compared to half-wave rectifiers, assuming same
SCRs current ratings.
(c) The harmonic contents of both the load and supply waveforms are much
lower compared to half-wave rectifiers. Less Ripple Factor in the voltage
side, and less Total Harmonic Distortion Factor in the supply side are
achieved.
Fig. 4 shows the phasor diagram of the balanced three-phase supply, where v1,
v2, and v3 are the phase voltages, and v12, v23, v31, v21, v32 and v13 are the
corresponding line voltages. Assuming y-connected supply, the line voltages are
given as:
𝜋
𝑣12 = ⎷3 𝑉𝑚 sin(𝜔𝑡 + ),
6
𝜋
𝑣23 = ⎷3 𝑉𝑚 sin(𝜔𝑡 − ),
2
5𝜋
𝑣31 = ⎷3 𝑉𝑚 sin(𝜔𝑡 + ),
6
5𝜋
𝑣21 = ⎷3 𝑉𝑚 sin(𝜔𝑡 − ),
6
𝜋
𝑣32 = ⎷3 𝑉𝑚 sin(𝜔𝑡 + ),
2
𝜋
𝑣13 = ⎷3 𝑉𝑚 sin (𝜔𝑡 − ) (2)
6
Page | 3
The six line voltages are involved in the load voltage waveform construction of
the rectifier. Fig. 5 shows the waveforms of the nine different voltages of the
system.
This means that if α = 0°, then SCR 1 should be triggered at ωt = 𝞹/3 or 30°.
Page | 4
4-2 Sequence of Triggering and Conventional Numbering of SCRs
Since there is a phase shift between 120° between each phase and the other,
there should be a 120° phase delay of triggering signal of the SCR 2 of phase 2,
compared to that of SCR 1 of phase 1. This implies that if SCR 1 is triggered at
ωt = 30° + α, SCR 2 should be triggered at ωt = (30° + α) + 120°, and similarly
SCR 3 should be triggered at ωt = (30° + α) + 240°.
Concerning the NRG, since SCR 1’ is responsible for the negative half-cycle of
phase 1, the triggering signal of SCR 1’ should be delayed by 180°when
compared to that of SCR 1.
The Table below show the time sequence of triggering SCRs 1, 2, 3, 1’, 2’, and 3’.
1 α + 30° 1
2 α + 150° 3
3 α + 270° 5
1’ αα + 210° 4
2’ α + 330° 6
3’ α + 450° (= α + 90°) 2
Page | 5
Fig. 6 shows the schematic diagram of the three-phase rectifier circuit with
standard numbering system.
By now, we are ready to start construction of the voltage and current waveforms
of three-phase rectifier circuits for different triggering angles.
*
390° implies that SCR 5 also conducts over the period between 0°and 30°.
**
450° implies that SCR 6 also conducts over the period between 0°and 90°.
Now, the above table can be translated in to two blocks (shown under the
waveforms of Fig.7). One block for the PRG, and the second block for the
NRG. From these two blocks, one can realize the SCRs to conduct at any period
of time. For instance, over the period from 0°and 30°, SCR 5, belongs to v3 and
SCR 6, belongs to v2. The output voltage will then be v3 – v2 = v32. This can be
Page | 6
repeated for the complete period of 360° in order to construct the waveform of
the load voltage.
Concerning the load current waveforms, and since the load is assumed pure DC,
the load current will have the same shape as that of the load voltage. However,
the scale of the load current is decided by the load resistance.
For the supply currents, each phase has its own current waveform. These
waveforms have identical shapes, but shifted by 120°. Let us investigate how to
construct the supply current of phase (1), i.e., is1. When SCR 1 conducts over
the period (30° + α) ≤ ωt ≤ (150° + α), or (30°) ≤ ωt ≤ (150°), the supply current
is the same as that of the load current (i.e., is1 = io). Similarly, when SCR 4
conducts over the period (210°) ≤ ωt ≤ (330°), the supply current is the same as
that of the load current, but with a negative sign (i.e., is1 = - io). Fig. 7 shows the
supply current of phase (1).
Figures (8) to (9) show the waveforms of interest for triggering angles 0f 30°
and 60° respectively.
In all three cases shown, the load current is seen to be continuous. Only for α =
60°, the load current has a zero-crossing point. However, no zero-current gap is
realized. This implies that the load current is continuous over the range of (0°) ≤
α < (60°). For α 60°, the system is said to run in the critical mode of operation.
When α ˃ 60°, the system is expected to operate in the discontinuous current
mode of operation (i.e., the load current is discontinuous with zero current
gaps). Details will follow in the example below.
To investigate this mode of operation, a firing angle of 90° (i.e., α ˃ 60°) will be
investigated. Fig.10 shows the construction of the load voltage waveform for α
= 90°.
Page | 7
Table (3): Wavefrm Construction for α = 90°
The same procedure will be followed for the construction of the load voltage
waveform. However, there is a certain restriction to be considered carefully.
Since the load current will never be negative in rectifier circuits, the load
voltage will never be negative. Table (3) shows the conduction pattern of the
rectifier switches for the firing angle of 90°.
This implies that SCR 1 conducts twice over two distinct periods, implying that
the load current is discontinuous. One period sharing conduction with SCR 6,
Page | 8
and the second sharing conduction with SCR 2. For this to occur successfully,
SCR 1 (and hence all other SCRs) should be triggered twice; at ωt = 120° and
60° later (i.e., at ωt = 180°)
This mode of operation is valid until the maximum value of the triggering angle,
which should be identified later.
If the triggering circuit is nor well designed to match the discontinuous current
mode of operation, the rectifier behaves like a half-controlled rectifier when αis
greater than 60°. That is something to be avoided.
rectifier switches should be drawn to define its peak value. Let us draw the
voltage across SCR1 which is defined as vAK1. Construction of this waveform is
directly related to the equation below:
When SCR 1 is conducting ON, negligible voltage appears across its terminal.
When SCR 1 is OFF, the voltage across its terminals depends upon which of the
SCRs of its group is conducting (i.e., PRG). If SCR 3 is conducting, then the
voltage across SCR 1 terminals will be vAK1 = v1 – v2 = v12. In the contrary, if
SCR 5 is conducting, this voltage will be vAK1 = v1 – v3 = v13.
The voltage ratings of the SCRs of a three-phase rectifier is then given by:
Page | 9
7 System Performance Parameters and SCR Voltage Rating
To calculate these parameters, RMS values of the load voltage, load current, and
supply current should be evaluated. Also, the fundamental component of the
supply current should also be evaluated.
One important relationship that we should realize, is that the RMS value of the
input current is directly related to the RMS value of the load current by the
formula:
This fact can be realized when considering the line current, which has a 120°
duration positive, and 120° duration negative, covering 240° of the 360°
covered by the load current (the 2/3 ratio is taken from the ratio 240/360).
In the following section, the Average and RMS expressions of the load voltage
for both modes of operations are derived.
𝐼𝑂 (𝑅𝑀𝑆)2 𝑅
𝑃𝐹𝑖𝑛 =
3 𝐼𝑆 (𝑅𝑀𝑆) 𝑉𝑆 (𝑅𝑀𝑆)
𝑉𝑂 (𝑅𝑀𝑆)
𝑃𝐹𝑖𝑛 =
√6 𝑉(𝑆) (𝑅𝑀𝑆)
Page | 10
Page | 11
Page | 12
Fig.1: Half-wave Rectifier (PRG).
Page | 13
Fig.2: Full-wave Rectifier: (PRG+NRG).
Page | 14
Fig.3: 3-PH Rectifier Circuit: Bridge Circuit.
Page | 15
Fig.4: Vector Diagram Of 3-PH System.
Page | 16
Fig.5: Waveforms of 3-PH Balanced Supply.
Page | 17
Fig.6: 3-PH Rectifier: Standard Numbering.
Page | 18
Fig.7: Voltage & Current Waveforms.
α = 0° .
Page | 19
Fig.8: Voltage & Current Waveforms.
α = 30°.
Page | 20
Fig.9: Voltage & Current Waveforms.
α = 60° .
Page | 21
Fig.10: Voltage & Current Waveforms.
α = 90° (DCM).
Page | 22
Fig.11: VAKI Venations (PIV).
α = 0°.
Page | 23
Fig.12: VAKI Venations (PIV).
α = 30°.
Page | 24