Parallel Operation of Synchronous Generator-1 PDF
Parallel Operation of Synchronous Generator-1 PDF
Parallel Operation
Parallel Operation of AC
of
Generators
AC Generators
Frequency-Power Characteristics
Effect Of Additional Real Power To Generator Speed
nnl n’nlnl
n’’
nfl
Power
Pfl (kW)
Frequency-Power Characteristics
Effect Of Additional Real Power To Generator Frequency
v Since prime mover speed is proportional to generator
frequency, the latter also decreases with increasing load.
f
P = sP ( f nl - f sys )
fnl
where:
Frequency(Hz)
fsys
P = power output of generator ffl
fnl = no load frequency
ffl = full load frequency
fsys = operating frequency of
system at power P.
sP = inverse of slope of curve,
P Pfl Power (kW)
kW/Hz or MW/Hz.
Frequency(Hz)
nnl = = = 900 rpm
P 8
b) Let fsys = operating frequency
of generator for any given
power output P. P Pfl Power
(kW)
Pfl P
=
f nl - f fl f nl - f sys
c) s P = 66.667 kW / Hz
100 kW
P= (60 - f )
sys
(60 - 58.5) Hz
Frequency(Hz)
Pfl
= s P = 66.667 kW / Hz
f 'nl - f ' fl
Frequency(Hz)
fol
125
P 100 Power
(kW)
Frequency(Hz)
125
P 100 Power
(kW)
EA
jXS IA
δ
Vφ
IA θ
EA
jXS IA
δ
Vφ
θ
IA
EA
jXS IA
δ
Vφ
θ
IA
EA
jXS IA
δ
IA Vφ
EA
jXS IA
δ
IA Vφ
Voltage(VT)
Terminal
VTnl
VTfl
ffl ffl
Frequency(Hz)
Voltage
Power Q,
consumed (kW) consumed (kVAR)
supplied supplied
Infinite bus curves
Operation of Generators in Parallel with
Large Power Systems
Load
Load
Generator
Infinite Bus
Operation of Generators in Parallel with
Large Power Systems
Load
G Generator
Infinite Bus
Operation of Generators in Parallel with
Large Power Systems
f
fnl
v Note that the power supplied by the bus to the load will
start to decrease as some of the load will be shouldered
by the generator (assuming the generator do not supply
power to the bus).
Operation of Generators in Parallel with
Large Power Systems
Generator at Higher Frequency:
f
fnl B
POUT
E A sin d = X S
3Vf
Operation of Generators in Parallel with
Large Power Systems
Generator Phasor Diagram:
The generator phasor
diagram as the frequency is
adjusted to higher value (by
EA governor set points) for
negligible resistance RA
θ EA sinδ
δ IAXS
(leading power factor)
IA
θ Vφ
increasing proportionately
increasing proportionately
with real power output
Equal to IA Cos θ
Increasing
Constant*
increasing
increasing
Constant
with IA
Behavior of variables as real power supplied by generator increases
* Provided field current is held constant as real power drawn is increased. Note
also that EA momentarily increases when rpm (and therefore frequency) of
the generator is increased but eventually settles to the same value as it
shares more real power to the load.
Operation of Generators in Parallel with
Large Power Systems
v Thus to totally transfer the power source of a load from the infinite
bus to the generator, we gradually increase the generator frequency
until all power requirement of the load equals the power supplied by
the generator.
v The generator frequency can be increased by adjusting the prime
mover governor set points.
v Further increase in generator power generation, will result in the
generator supplying power to the infinite bus.
v Note that while VT (and EA for that matter) change with change in
frequency, this change is only momentary as the generator will have to
adjust to the infinite bus frequency and terminal voltage.
v Hence, as VT and EA settles to a constant value, the current and
associated power factor supplied by the generator changes.
Illustrative Problem 2
§ A 200-kW, 0.8 lagging power factor load currently draws power from a
400-V, 60-Hz infinite bus. A 400-V, ∆-connected generator with
synchronous reactance of 1.0 Ω is to be connected in parallel with an
infinite bus to take over the load. Copper losses are negligible.
a) What is the current drawn from the infinite bus (IB) before the
generator is paralleled?
b) What is the current drawn from the IB immediately after the
generator is connected to the bus. What is the current drawn from
the generator?
c) The governor on the prime mover is gradually adjusted to transfer
real power to the generator. At the point where the generator is
delivering half of the real power requirements of the load, what is
the current drawn from both the IB and the generator? What is
the power factor of the generator?
d) If the governor set point is adjusted such that the generator is
now supplying 90% of the real power, find current supplied by the
generator and the infinite bus.
Illustrative Problem 2
IB IL
Load
200-kW, 0.8
lagging power
factor, 400-V,
60-Hz
Infinite bus G2
Generator
Illustrative Problem 2
IB IL
Load
200-kW, 0.8
lagging power
IG = 0 factor, 400-V,
60-Hz
Infinite bus G2
At the time the generator is
Generator paralleled
Illustrative Problem 2
Solution:
a) Before generator is put in parallel with infinite bus (put on line), the
power and current drawn by the load will be supplied by infinite bus.
Thus,
b) At the instant the generator is paralleled to the infinite bus, its status
will be floating supplying very little real power and current. Thus,
I B = 360.84 A
IG = 0
The IB and generator curves and the phasor diagram of the generator
at this time will look like this,
Illustrative Problem 2
f VT
60 Hz
400 V
A A
Infinite bus and generator curves at the instant generator is put on line with bus
Phasor diagram of generator at the instant generator is put on line with bus
Illustrative Problem 2
c) When the prime mover governor set points is adjusted for the
generator to take on half of the load real power, the curves and phasor
diagram will look like this,
f VT
B
60 Hz 400 V
A
Pib, kW 100 100 PG, kW Qib, kVAR 160.5 -10.5 = QG QG, kVAR
Infinite bus and generator curves when generator is supplying 100 kW
EAG
jXSGIAG
100,000
I AG cos q G = = 83.33 A
3 ´ 400
ë 400 û
Since magnitude of EA does not change, |EAG| = |VφG|
d G + 2(90 - q G ) = 180
q G = 6.012o
Illustrative Problem 2
Solution: EAG
jXSGIAG
c) θG EAG sinδG = XSIAG cos θi
IAG δG
θG
VφG
E AG sin d G = X SG I AG cos q G
400 sin 12.02o
I AG = o
= 83.76 A
1.0 cos 6.012
I AG = 83.789 A
Illustrative Problem 2
Solution: EAG
jXSGIAG
c) θG EAG sinδG = XSIAG cos θi
IAG δG
θG
VφG
200,000
I fLOAD = = 208.33Ð - 36.87 V
3(400)(0.8)
S G = 3VfG I AG
*
= 3(400Ð0 o )(83.789Ð - 6.012) = 100,546.8Ð - 6.012 o VA
S G = +99,994.16 - j10,527.455 VA
The above result shows that the generator is supplying real power but
receiving reactive power (Q is negative).
Illustrative Problem 2
Solution:
c) By energy conservation,
S LOAD = S B + S G
S B = 250,000Ð36.87 o - 100,546.8Ð - 6.012 o
S B = 189,134Ð58.08 o
S B = 100,001 + j160,534.51 VA
S B = +100,001 + j160,534.51 VA
This means, that the infinite bus is supplying real and reactive power.
Note that the reactive power supplied by the infinite bus is the total of
the reactive power consumed by the generator and the load.
QB = QG + QLOAD
160,534.51 @ 10,531 + [200,000 / tan(36.87)]
160,534.51 @ 160,531.56
Illustrative Problem 2
Solution:
SB 189,134
I LB = = = 273 A
3VLB 3 (400)
Illustrative Problem 2
IB IL
Load
200-kW, 0.8
lagging power
IG factor, 400-V,
60-Hz
Infinite bus G2
When generator is delivering
Generator ½ of the total real power.
Operation of Generators in Parallel with
Large Power Systems
Behavior of Reactive Power Supplied by Generator:
v While real power supplied by generator increased (thru
small momentary increases in frequency thru the governor
set points*), the reactive power did not. In fact, at this
point, the generator is receiving reactive power from the
infinite bus.
EA
IA cosθ = constant
jIAXS
EA sinδ = IAXscosθ = constant
δ
IA
θ IA sinθ
Vφ
EA
IA cosθ = constant
jIAXS EA sinδ = IAXscosθ = constant
δ
θ IA sinθ Vφ
IA
EA
IA cosθ = constant
Vφ
θ IA sinθ
EA
IA cosθ = constant
Vφ
θ IA sinθ
Therefore;
X S I AG cos q G = 1.0 ´ 83.76 ´ 0.994 = 83.3 V
Illustrative Problem 3
Therefore:
QG = 12 QL = 12 (150) kVAR = 75 kVAR
From generator, the supplied reactive power is:
QG = 3VfG I AG sin q G = 75 kVAR
75 kVAR (varies while IF is adjusted (see
I AG sin q G = = 62.5 A phasor diagram))
3(400)
Illustrative Problem 3
I AG sin q G 62.5
= = 0.7503
X S I AG cos q G 83.3
q G = 36.88 o
I AG = 104.14 A
POUT = 3VfG I AG sin q G
POUT = 3(400)(104.14) sin 36.88 = 99,961 » 100 kW (constant)
Note: The generator is now operating at lagging power factor
Operation of Similar Generators in Parallel
Load
G1 (Pload, Qload) G2
f
Pload
Pload
Pload
Pload
Pload
VT
Qload
VT
Qload
VT
Qload
VT
Qload
f
fsys
Pload
f
fsys
Pload
VT
Qload
VT
Qload