Write Up On LPBP System
Write Up On LPBP System
DRG.NO. 4-18000-90-440
VR_C15.FR
------------------------------------------------------------------------------------------------4-18000-90-440, Rev.01---------
1.0 GENERAL
For this purpose, the bypass valve combinations (i.e. LPBP SV & CV) open
in relationship to the pressure in the reheat line, by a pressure controller.
The pressure regulator feeds the positioner, such that,
Each LP-bypass Stop Valve (SV) and Control Valve (CV) is provided with
its own Electro-Hydraulic Actuator (EHA) which operates with high
pressure control fluid supplied by a centralized Hydraulic Power Supply
Unit (HPSU).
The EHA of each LPBP-SV is provided with a pilot valve (solenoid valve)
and 2 Trip Solenoid Valves (TSV) for redundancy. On receiving a trip
signal, one of the coils of TSV must de-energise to cause trip. The
opening of bypass SV is done over the pilot valve, which is controlled in
relationship to the pressure controller output signal.
The pressure set point is formed over a MAX selection of the Fixed
setpoint & Variable setpoint.
For startup and coast-down, a fixed setpoint value is fed to the pressure
controller. This can be manually set to the desired value from the control
room. It can also be set from the `Automatic Setpoint Matching’ (ASM)
to have a proper balance between the reheater flow and buildup of
reheater pressure during a cold start. The ASM can be switched ON/OFF
from the control room.
For the reduction of steam temperature, water is injected into the bypass
steam before steam enters into the condenser.
In case of partial bypass, the designed steam flow is exceeded for the
shedding of loads of turbine emergency trip with high super heater
pressure. This may lead to the condition of insufficient injection water and
overloading of condensate pumps. To avoid this , a flow limit controller is
provided which restricts the opening of the LPBP-CV depending on
pressure after the bypass valves. For this, the output of the pressure
controller or manual control is coupled with the output of the flow limit
controller in a MIN selection.
This is the pressure after the LPBP CV. A pressure transmitter measures
the pressure in the pipeline downstream each bypass valve combination
and the maximum pressure is derived from a MAX selection of the two
transmitters. This pressure gives the actual value of pressure after the
LPBP CV.
2.3.1 Bypass SV
The opening of each BPSV is done over a pilot valve (solenoid valve)
which is controlled by the effective position setpoint (hs) .
Pilot valve ON (energised) = SV open.
The pilot valve is switched ON when the position setpoint is > -20% and
LPBP trip has not responded.
2.3.2 Bypass CV
Water is injected into the bypassed steam before it passes into the
condenser. This is done by a controlled-type Water Injection Valve (WIV).
There is one Water Injection Valve for both LP-bypass valve combinations,
which is controlled over a controller.
Malfunctions of the turbine bypass, i.e. failure to open the bypass valves,
have to be counteracted by opening of the reheater safety valves to
ensure flow through the reheater. This prevents heat accumulation in the
reheater tubes. For this purpose, the measure of flow through reheater is
the magnitude of the control deviation between actual and set pressure.
The following limit signals are generated from the pressure controller, for
control of the reheater safety valves :
• Control deviation of the pressure controller (xd) > 30%
• Position setpoint >25%
The reheater control valves are opened under the following conditions :
¾ The control deviation rises above the value given above AND
neither the bypass stop valves are open (<100%) nor all bypass
control valves are at least about 60% open, the command for
opening the reheater safety valves is given after a delay of 5 sec.
¾ The position setpoint exceeds 25% AND the LPBP stop valves are
not open (<100%), the command for opening the reheater safety
valves is given after a time delay of 30s.
The valve positioner performs the function of positioning the EHA of the
LPBP-CV according to the position setpoint. An individual positioner is
allotted to each EHA. Each positioner gets its setpoint as described above
in pt. 2.3.2.The positioner is mounted in control cabinet located near
Actuator. The positioner controls the. Proportional-valve The proportional-
valve in turn, positions the EHA to operate the corresponding LPBP-CV.
The position of the piston in the operating cylinder of the EHA is recorded
by means of an analog position transmitter, thereby giving the position
actual value.
Switching over to manual control can be done from the control room
by the control display ‘LPBP Controller ON/OFF’. The switching ON is
stored (OFF has preference to ON). In addition, in case of disturbances in
the electrical part of the controller, switching over to manual control is
done.
2.6.1 Tracking
As long as the pressure actual value and the pressure setpoint conform,
switching over is bump less. If the set-value and the actual value do not
conform, the position of the LPBP-CV varies according to the existing
control deviation.
4.1 The following status indications are provided in the control room:
- Fixed Setpoint
- Variable Setpoint
- Effective pressure setpoint
- Control Deviation
- Reheater Pressure (HRH steam press before LPBP Valves)
4.3 Alarms :