VRF Additonal Refrigerant Charge Calculation

The document contains specifications for refrigerant pipe diameters and required additional refrigerant amounts for different pipe lengths. Table 1 lists additional refrigerant needs in kg per 1m of pipe for various pipe diameters. Table 2 shows outdoor unit combinations and required compensation in HP for different system horsepowers. An equation is provided to calculate total additional refrigerant needed based on pipe lengths and diameters.

Uploaded by

towiwa
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
1K views

VRF Additonal Refrigerant Charge Calculation

The document contains specifications for refrigerant pipe diameters and required additional refrigerant amounts for different pipe lengths. Table 1 lists additional refrigerant needs in kg per 1m of pipe for various pipe diameters. Table 2 shows outdoor unit combinations and required compensation in HP for different system horsepowers. An equation is provided to calculate total additional refrigerant needed based on pipe lengths and diameters.

Uploaded by

towiwa
Copyright
© © All Rights Reserved
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 5

Table 1

Pipe dia. at liquid side in (mm) ø6.4 ø9.5 ø12.7

Additional refrigerant 0.025 0.055 0.105


amount/1m in Kg

Table 2 (Standard model) Table 2


Combined horse Outdoor Compensation by Combined
power (HP) combination(HP) System HP (kg) horse power
(HP)
5 5 0.0 -
6 6 0.0 -
8 8 1.5 -
10 10 2.5 -
12 12 3.5 -
14 14 8.5 -
16 16 10.5 16
18 10 8 0.0 -
20 10 10 3.0 -
22 12 10 5.0 -
24 12 12 7.5 24
26 14 12 8.5 26
28 16 12 9.5 28
30 16 14 11.5 30
32 16 16 12.5 32
34 12 12 10 3.0 34
36 12 12 12 4.0 36
38 16 12 10 6.0 38
40 16 12 12 7.0 40
42 16 14 12 8.0
44 16 16 12 10.0
46 16 16 14 12.0
48 16 16 16 14.0
42 12 10 10 10 -4.0
44 12 12 10 10 -2.0
46 12 12 12 10 0.0
48 12 12 12 12 2.0
ø15.9 ø19.0 ø22.2 Additional refrigerant needed

0.16 0.25 0.35 Additional refrigerant needed

Table 2 (High efficiency model)


Outdoor combination(HP) Compensation by
System HP (kg)

- L1 32
- L2 19.9
- L3 13.5
- L4 8.9
- L5 6
- L6 0
8 8 0.0
- Where
- L1 Real total length o
- L2 Real total length o
8 8 8 -4.0 L3 Real total length o
10 8 8 -4.0 L4 Real total length o
10 10 8 -2.0 L5 Real total length o
10 10 10 0.0 L6 Real total length o
8 8 8 8 -6.0
10 8 8 8 -6.0
10 10 8 8 -6.0
10 10 10 8 -6.0
10 10 10 10 -5.0
((L1x0.025)+(L2x0.055)+(L3x0.105)+(L4x0.160)+(L5x0.25)+(L6x0.35)+(compensation by system

14.736 Kg

m
m
m
m
m
m

Real total length of liquid pipe ø6.4


Real total length of liquid pipe ø9.5
Real total length of liquid pipe ø12.7
Real total length of liquid pipe ø15.9
Real total length of liquid pipe ø19.0
Real total length of liquid pipe ø22.2
compensation by system HP))