Power System Protection: Dr. Lionel R. Orama Exclusa, PE Week 3
Power System Protection: Dr. Lionel R. Orama Exclusa, PE Week 3
Operating coil
kS
iOP =
kI
FNET = 0 = k I I OP − K S
2
KS
I OP = = I PU k I I OP > K S
2
“a” contact forcing force
KI is produced
1
sin (ωt ) = (1 − cos(2ωt ))
2
2
• Variable force
FOP (t ) = kφ Φ M (1 − cos(2ωt ))
2
– causes Vibration
• Measures are taken to
avoid vibration
φ1
φ2
Copyright L.R. Orama 2006 11
Response to AC Currents
• Measures are taken
to avoid vibration
– Shading Ring
FOP (t ) = kφ (φ12 + φ22 )
φ1 = 2Φ M sin(ωt ) Lφ2 = 2Φ M sin(ωt + θ )
θ = 90°
φ2 = 2Φ M sin(ωt + 90) = φ2 = 2Φ M cos(ωt )
Constant (
FOP (t ) = 2kφ Φ M sin 2 (ωt ) + cos 2 (ωt )
2
)
=1
FOP (t ) = 2kφ Φ M = k I I OP
2 2
RMS
Copyright L.R. Orama 2006 12
Plunger Type Relay
Protected
Device
ISYS1 ISYS2
ISYS1=ISYS2 IFAULT
ISYS1-ISYS2=0
Protected
Device
ISYS1 ISYS2
IFAULT
ISYS1=IFAULT+ISYS2
ISYS1-ISYS2=IFAULT
Differential current, relays operate
I OP = I E 2 − I E1
Copyright L.R. Orama 2006 27
True CT Performance
As said before:
• IE causes CT error
– CT’s saturates differently or
– Reisdual B exists
I CT 1 ≠ I CT 2
• Therefore differential current
Copyright L.R. Orama 2006 28
CT Mismatch Occurs
• Overcurrent
operates for high
values of IF (ISYS)
external
• Apply relay with
alternate
characteristic
– “percentage
differential”
2
Ignoring KS & solving
2
N
K OP [N OP ( I1 − I 2 )] = K RES R ( I1 + I 2 )
2 for FNET=0
2
2
NR
[N OP ( I1 − I 2 )] =
2 K RES
( I +
2 1 2 I )
K OP
I1 + I 2 N K RES
I1 − I 2 = K ' LK'= R
2 N OP K OP
I1 + I 2
I OP = I1 − I 2 > K '
2
VLL = Vφ I L = Iφ
•Percentage
differential
protection in a Y-∆
Power transformer
5 •Primary is overrated
I RELAY − R = 5 A I CT − R = A
3 Notes: Define Transformer Rating:
FOA: Forced Oil & Air
I FLY 200 A
Ideal CTRATIO = = = 346 : 5 FA: Forced Air
I CT − R 5A OA: Nothing Forced
3
Copyright L.R. Orama 2006 44
Taps are Provided
CTR do not always match the
Power Transformer Ratio
•IRELAY-L=5A, IRELAY-R=8.66A
•Choose 5A on the 13.8kV side,
and 8.7 on the 138kV side
•Mismatch occurs from
•Taps
•Load tap changers (+_10%)
•Make % slope for TAP+LTC
Mismatch
Harmonic
Restraining Coil,
works whit
differential current