7 Chapter 6 - Air Requirements of A Pressurization System
7 Chapter 6 - Air Requirements of A Pressurization System
Pressure levels
Stewart and Hobson studied the factors which can cause smoke to spread around a
building. As a result they were able to suggest guidelines for a pressurization system
designed for smoke control.
Table 6-1 details these guidelines.
Wind/Stack
Design pressure Fire pressure Building height
effect
(Pa) (Pa) (m)
(Pa)
25 8.0 8.5 5
25 10.5 8.5 25
50 13.0 8.5 50
50 19.5 8.5 100
50 29.5 8.5 150
Table (6-1) Design pressures.
This established the design pressure levels of 50 Pa for operating MODE 1 – All doors
closed – of a system although reduced pressures would be acceptable on buildings of lower
height.
49
Chapter (6) Air Requirements of a Pressurization System
Leakage Crack
area length Size Type of door
2
(m ) (m)
Single leaf in frame opening into
0.01 5.6 2 m x 800 mm
pressurized space.
Single leaf in frame opening
0.02 5.6 2 m x 800 mm
outwards.
Double leaf with or without central
0.03 9.2 2 m x 1.6 m
rebate.
2 m High x
0.06 8.0 Lift door.
2 m wide
Table (6-2) Typical leakage areas around doors.
For single openings, one door, AE = net free area of the opening.
For several openings, or doors situated in PARALLEL around a pressurized space figure
(6-1).
AE = A1 + A2 + A3 + …………
For several opening, or doors situated in SERIES along an escape route figure (6-2).
n
1 −1 /2
A E=⌊ ∑ ⌋
i=1 A 2i
For two doors in series more typical of a pressurization system this simplifies to
( A ¿ ¿ 1+ A 2)
A E= ¿
¿¿¿
50
Chapter (6) Air Requirements of a Pressurization System
Although we can estimate the effective area for an escape route in this way, there are
always, in any building, other leaks we are not aware of.
To accommodate these, the air supply volume calculated should be increased by at least
25%, stipulated by the code of practice. Many smoke control experts believe 25% to be
insufficient and propose it should be increased to 50%. This higher value is used
throughout this paper.
During the fire fighting the brigade need to open doors on the fire floor to gain entry
without themselves being engulfed in smoke. BS5588 Part 5 specifies that a velocity of 2.0
m/sec is needed to achieve this.
51
Chapter (6) Air Requirements of a Pressurization System
The air supply for both these cases is unusually greater than that required to develop the 50
Pa pressure requirement of mode 1. Therefore, to prevent the pressure in the escape way
rising above the maximum allowed, (60 Pa. in the U.K.), when all the doors are closed, the
air supply system must be capable of air volume variation. This maximum allowable
pressure is to ensure that escape doors can be opened by all types of persons at all times.
52