0% found this document useful (0 votes)
248 views

Fan Coil Room Thermostat RDF510, RDF530 : en ZH

The document provides mounting and operating instructions for a fan coil room thermostat. It includes diagrams of the thermostat dimensions and wiring. The summaries are: 1) It provides diagrams showing the dimensions and wiring of the thermostat, including connections for power supply, fan speeds, valves, and relays. 2) The operating instructions overview includes settings for timer delay off, manual heating/cooling changeover, and accessing control parameters. 3) A parameter list details settings for functions like timer duration, control sequence, and parameters that can be adjusted.

Uploaded by

محمد علي
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
248 views

Fan Coil Room Thermostat RDF510, RDF530 : en ZH

The document provides mounting and operating instructions for a fan coil room thermostat. It includes diagrams of the thermostat dimensions and wiring. The summaries are: 1) It provides diagrams showing the dimensions and wiring of the thermostat, including connections for power supply, fan speeds, valves, and relays. 2) The operating instructions overview includes settings for timer delay off, manual heating/cooling changeover, and accessing control parameters. 3) A parameter list details settings for functions like timer duration, control sequence, and parameters that can be adjusted.

Uploaded by

محمد علي
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

s A6V10889954 Mounting and dismounting /

en Mounting instructions zh

Fan coil room thermostat

RDF510…, RDF530…

Installation live demo Datasheet

Mounting location of thermostat / Wiring diagrams /


RDF510… en ) zh ( )
AC 230 V power supply, mains and
L, N AC 230 V
neutral
Q1, SPST relay outputs for fan speed (Q1)
Q2, Q3 low (Q1), medium (Q2), high (Q3) (Q2) (Q3)
N1 RDF510… RDF510…
N2 RDF530… RDF530…
M 3-speed fan motor
V1, V2 Valves
Y1, Y2 SPST relay output, normally open
Y12 SPDT relay output, normally closed
Y14 SPDT relay output, normally open
T 6.3 A Internal fuse (6.3 A), replaceable (6.3 A)
Dimensions (mm) / ( )
Connect only one fan at a time to Q
View A / A View B / B RDF530… output Q on the thermostat

Do not connect Y12 to either L or N, Y12


or use Y12 as AC 230 V power
supply Y12 AC 230 V

Internal fuse (replaceable) /


Fuse type / SLOW-BLOW /
Size / 5.2 x 20 mm
Voltage rating / 250 V
Current rating / 6.3 A

The fuse supports a total maximum loading (fan and valve) of 5 A.


Above are the dimensions for the thermostat and its mounting plate. 5A

Siemens Building Technologies RDF510…, RDF530… A6V10889954_c 2018-03-27 1/2


en Operating instructions zh RDF510…, RDF530…
Overview /
1) Timer with delay Off /
If P28=0 (factory setting), press for more than 3 seconds to
set the on-time duration each time. If P28=1, 2, 3 up to 23 hours,
preset with a fixed on-time, countdown begins once the
thermostat is ON (refer to Parameter list below).
P28=0 3
P28 1 23

2) Manual heating/cooling changeover /


With manual changeover (P01=2), symbols / indicate the
current control sequence selected. i.e. heating or cooling mode.
/ P01=2 , /

Changing control parameters /


Press + and – simultaneously for 3 seconds. / + –3
Within 2 seconds, press + for 3 seconds to go to the parameter access mode.
2 +3
Press < or > to select the desired parameter. / < >
Press ü to edit the parameter, then use + and – to change its value.
ü + –
Press ü to confirm the change, then continue to select/edit other parameters/values.
ü / /
Press to exit parameter access mode. /

Parameter list /
Parameter Description Factory setting Setting range Adj.
!
P01 Control sequence / RDF510… = 2 0:= Heating only / 4:= Heating and cooling /
RDF530… = 4 1:= Cooling only /
2:= H/C changeover manual / / RDF510…: 0, 1, 2; RDF530…: 2, 4
P05 Sensor calibration / 0K -5 … +5 K
P06 Standard temperature display / 0 0:= Room temperature / 1:= Setpoint /
P09 Minimum setpoint in Comfort mode / 5 °C 5 …40 °C
P10 Maximum setpoint in Comfort mode / 35 °C 5 …40 °C
P14 Keylock function / 0 0:= No lock / 1:= Full lock / 2:= Partial lock /
P15 Fan control deadzone in Comfort mode / / 1 0:= Fan off /
1:= Fan speed 1 in heating or cooling mode /
P27 Operating mode settings upon power down 0 0:= Return to previous operating mode or user settings /
1:= Protection mode /
P28 Timer with delay Off / 0 0:= Users to set on-time duration /
1 to 23:= Preset with a fixed on-time in hours /
P30 Switching differential in heating mode / 1K 0.5…6 K
P31 Switching differential in cooling mode / 1K 0.5...6 K
P33 Deadzone in Comfort mode / / 2K 0.5...5 K (RDF530)
P59 Fan minimum on-time (dwelling time) / ( ) 2 minutes / 2 1...6 minutes / 1 ... 6
P65 Protection heating setpoint / 8°C OFF, 5°C…Wcoolpro; Wcoolpro=40°C max.
P66 Protection cooling setpoint / OFF / OFF, Wheatpro…40°C; Wheatpro=5°C min.
P71 Reload factory setting / OFF / OFF:= Disable / ; ON:= Reload start /
“---” is displayed for 3 seconds during reload process / “---” 3
! Please record all changes you make. /
To download the latest documentations and applications, go to: / https://www.downloads.siemens.com/download-center/
Subject to change.
2/2 2018-03-27 A6V10889954_c RDF510..., RDF530... Siemens Building Technologies