This document provides a sizing summary for the air system PACK AC ZONE 1 serving 12 zones covering 3,158 square feet at a Ministry of Health facility in Hail, Saudi Arabia. Key findings include: - The central cooling coil has a peak load of 25.2 tons occurring in July, requiring a coil airflow of 7,760 CFM and supply air temperature of 50.8°F. - The central heating coil has a maximum load of 18.4 MBH occurring in January, requiring a coil airflow of 4,974 CFM and supply air temperature of 51.0°F. - The supply fan requires a maximum airflow of 8,502 CFM with no static pressure or

Uploaded by

umair186
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
79 views1 page

Air System Sizing Summary For PACK AC ZONE 1

This document provides a sizing summary for the air system PACK AC ZONE 1 serving 12 zones covering 3,158 square feet at a Ministry of Health facility in Hail, Saudi Arabia. Key findings include: - The central cooling coil has a peak load of 25.2 tons occurring in July, requiring a coil airflow of 7,760 CFM and supply air temperature of 50.8°F. - The central heating coil has a maximum load of 18.4 MBH occurring in January, requiring a coil airflow of 4,974 CFM and supply air temperature of 51.0°F. - The supply fan requires a maximum airflow of 8,502 CFM with no static pressure or

Uploaded by

umair186
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Air System Sizing Summary for PACK AC ZONE 1

Project Name: MINISTRY OF HEALTH 0805 05-08-2018


Prepared by: TEC 05:31PM

Air System Information


Air System Name ........................ PACK AC ZONE 1 Number of zones ......................................................... 12
Equipment Class ...................................... PKG ROOF Floor Area ............................................................ 3158.1 ft²
Air System Type .................................................. VAV Location .......................................... HAIL, Saudi Arabia

Sizing Calculation Information


Zone and Space Sizing Method:

Zone CFM .......................... Peak zone sensible load Calculation Months ....................................... Jan to Dec
Space CFM .................. Individual peak space loads Sizing Data ................................................... Calculated

Central Cooling Coil Sizing Data

Total coil load ....................................................... 25.2 Tons Load occurs at .................................................. Jul 1800
Total coil load ..................................................... 302.1 MBH OA DB / WB ................................................. 103.5 / 65.5 °F
Sensible coil load ................................................ 270.0 MBH Entering DB / WB ........................................... 84.2 / 63.3 °F
Coil CFM at Jul 1800 ........................................... 7760 CFM Leaving DB / WB ............................................ 50.8 / 49.0 °F
Max block CFM at Jul 1900 ................................. 8502 CFM Coil ADP .................................................................. 47.1 °F
Sum of peak zone CFM ....................................... 8730 CFM Bypass Factor ........................................................ 0.100
Sensible heat ratio .............................................. 0.894 Resulting RH ............................................................... 46 %
ft²/Ton ................................................................. 125.4 Design supply temp. ................................................. 56.0 °F
BTU/(hr-ft²) ........................................................... 95.7 Zone T-stat Check ............................................. 12 of 12 OK
Water flow @ 10.0 °F rise ..................................... N/A Max zone temperature deviation ................................ 0.0 °F

Central Heating Coil Sizing Data

Max coil load ........................................................ 18.4 MBH Load occurs at ................................................. Jan 0700
Coil CFM at Jan 0700 .......................................... 4974 CFM BTU/(hr-ft²) ................................................................. 5.8
Max coil CFM ...................................................... 8502 CFM Ent. DB / Lvg DB ............................................ 47.5 / 51.0 °F
Water flow @ 20.0 °F drop ................................... N/A

Supply Fan Sizing Data

Actual max CFM at Jul 1900 ................................ 8502 CFM Fan motor BHP ........................................................ 0.00 BHP
Standard CFM ..................................................... 8195 CFM Fan motor kW .......................................................... 0.00 kW
Actual max CFM/ft² ............................................... 2.69 CFM/ft² Fan static ................................................................. 0.00 in wg

Outdoor Ventilation Air Data


Design airflow CFM ............................................. 2494 CFM CFM/person ........................................................... 17.69 CFM/person
CFM/ft² ................................................................. 0.79 CFM/ft²

Hourly Analysis Program v4.50 Page 1 of 1