415V Side Relay Setting Data
415V Side Relay Setting Data
b) Fault current - Own terminal : 37039 A Fault wrt to 4.5% Imp value on trafo
2.0 CT DETAILS
b) Secondary current : 5 A
Please ensure the CT Ratio is 1600/5A
CT Ratio 1600/5 1600 A
3.0 RELAY DETAILS
a) Type : Schneider
b) Make :
c) Phase overcurrent Characteristics : IEC Normal inverse (As per IEC 60255-4/IS 3231)
Earth overcurrent characteristics a 0.02
b 0.1414
d) Setting Range
Range Set Value
IDMT Over Current (51)
i) Phase overcurrent low Pickup :(i>) 0.2 ….. 2.5 in steps of 0.05 1.10
ii) Phase overcurrent inverse time :(ti>) 0.01 to 1.5 in steps of 0.001 0.1
ii) Phase overcurrent Definite Time :(T>>) 0.03 to 20 in steps of 0.001 0.030
IDMT Earth Fault (51N)
i) Earth over Current Setting (E>) : 0.05 …..2.5 in steps of 0.001 0.10
ii) Earth Overcurrent Inverse time (Ei>) : 0.01 to 1.5 in steps of 0.001 0.050
HIGH Set Earth Fault (50N)
DEFINITE MINIMUM TIME
i) Earth overcurrent High Setting : 0.5 …..15 in steps of 0.005 0.30
PSM : 6.3
CT Limitation
d) Relay Operating time at TMS=1.0 : 0.1414 (for PSM>10,PSM=10)
6^0.02-1
: 3.68 at 1 Sec
: 0.2 / 3.68
: 0.05
TMS for 51 N 0.05
: 37039.2100040239*5%/1600
: 0.1*1666.76445018108/1600
: 0.104
: 0.3 *37039.2100040239/1600x0.1
PSM : 6.3
: 3.68
: 0.2 / 3.68
: 0.05
: 0.050
4.4 EARTH FAULT INSTANTANEOUS ELEMENT 50N
0.30 * Maximum
a) Earth fault setting : demand current /
CT Ratio
0.15*1666.76445
:
018108/1600
: 0.31
b) Fault current - Own terminal : 37039 A Fault wrt to 4.5% Imp value on trafo
2.0 CT DETAILS
b) Secondary current : 5 A
Please ensure the CT Ratio is 1600/5A
CT Ratio 1600/5 1600 A
3.0 RELAY DETAILS
a) Type : Schneider
b) Make :
c) Phase overcurrent Characteristics : IEC Normal inverse (As per IEC 60255-4/IS 3231)
Earth overcurrent characteristics a 0.02
b 0.1414
d) Setting Range
Range Set Value
IDMT Over Current (51)
i) Phase overcurrent low Pickup :(i>) 0.2 ….. 2.5 in steps of 0.05 1.00
ii) Phase overcurrent inverse time :(ti>) 0.01 to 1.5 in steps of 0.001 0.1
ii) Phase overcurrent Definite Time :(T>>) 0.03 to 20 in steps of 0.001 0.030
IDMT Earth Fault (51N)
i) Earth over Current Setting (E>) : 0.05 …..2.5 in steps of 0.001 0.09
ii) Earth Overcurrent Inverse time (Ei>) : 0.01 to 1.5 in steps of 0.001 0.050
HIGH Set Earth Fault (50N)
DEFINITE MINIMUM TIME
i) Earth overcurrent High Setting : 0.5 …..15 in steps of 0.005 0.25
PSM : 6.9
CT Limitation
d) Relay Operating time at TMS=1.0 : 0.1414 (for PSM>10,PSM=10)
6^0.02-1
: 3.68 at 1 Sec
: 0.15 / 3.68
: 0.04
TMS for 51 N 0.05
: 37039.2100040239*5%/1600
: 0.1*1666.76445018108/1600
: 0.104
: 0.3 *37039.2100040239/1600x0.09
PSM : 6.9
: 3.68
: 0.15 / 3.68
: 0.04
: 0.050
4.4 EARTH FAULT INSTANTANEOUS ELEMENT 50N
0.30 * Maximum
a) Earth fault setting : demand current /
CT Ratio
0.15*1666.76445
:
018108/1600
: 0.31
b) Fault current - Own terminal : 37039 A Fault wrt to 4.5% Imp value on trafo
2.0 CT DETAILS
b) Secondary current : 5 A
Please ensure the CT Ratio is 1600/5A
CT Ratio 1600/5 1600 A
3.0 RELAY DETAILS
a) Type : Schneider
b) Make :
c) Phase overcurrent Characteristics : IEC Normal inverse (As per IEC 60255-4/IS 3231)
Earth overcurrent characteristics a 0.02
b 0.1414
d) Setting Range
Range Set Value
IDMT Over Current (51)
i) Phase overcurrent low Pickup :(i>) 0.2 ….. 2.5 in steps of 0.05 0.95
ii) Phase overcurrent inverse time :(ti>) 0.01 to 1.5 in steps of 0.001 0.1
ii) Phase overcurrent Definite Time :(T>>) 0.03 to 20 in steps of 0.001 0.030
IDMT Earth Fault (51N)
i) Earth over Current Setting (E>) : 0.05 …..2.5 in steps of 0.001 0.08
ii) Earth Overcurrent Inverse time (Ei>) : 0.01 to 1.5 in steps of 0.001 0.050
HIGH Set Earth Fault (50N)
DEFINITE MINIMUM TIME
i) Earth overcurrent High Setting : 0.5 …..15 in steps of 0.005 0.20
PSM : 7.3
CT Limitation
d) Relay Operating time at TMS=1.0 : 0.1414 (for PSM>10,PSM=10)
6^0.02-1
: 3.68 at 1 Sec
: 0.1 / 3.68
: 0.03
TMS for 51 N 0.05
: 37039.2100040239*5%/1600
: 0.1*1666.76445018108/1600
: 0.104
: 0.3 *37039.2100040239/1600x0.08
PSM : 7.3
: 3.68
: 0.1 / 3.68
: 0.03
: 0.050
4.4 EARTH FAULT INSTANTANEOUS ELEMENT 50N
0.30 * Maximum
a) Earth fault setting : demand current /
CT Ratio
0.15*1666.76445
:
018108/1600
: 0.31
2.0 CT DETAILS
b) Secondary current : 5 A
Please ensure the CT Ratio is 1600/5A
CT Ratio 1600/5 1200 A
3.0 RELAY DETAILS
a) Type : Schneider
b) Make :
c) Phase overcurrent Characteristics : IEC Normal inverse (As per IEC 60255-4/IS 3231)
Earth overcurrent characteristics a 0.02
b 0.1414
d) Setting Range
Range Set Value
IDMT Over Current (51)
i) Phase overcurrent low Pickup :(i>) 0.2 ….. 2.5 in steps of 0.05 0.70
ii) Phase overcurrent inverse time :(ti>) 0.01 to 1.5 in steps of 0.001 0.1
ii) Phase overcurrent Definite Time :(T>>) 0.03 to 20 in steps of 0.001 0.030
IDMT Earth Fault (51N)
i) Earth over Current Setting (E>) : 0.05 …..2.5 in steps of 0.001 0.08
ii) Earth Overcurrent Inverse time (Ei>) : 0.01 to 1.5 in steps of 0.001 0.050
HIGH Set Earth Fault (50N)
DEFINITE MINIMUM TIME
i) Earth overcurrent High Setting : 0.5 …..15 in steps of 0.005 0.20
PS for 51 0.704
PSM : 7.5
CT Limitation
d) Relay Operating time at TMS=1.0 : 0.1414 (for PSM>10,PSM=10)
6^0.02-1
: 3.68 at 1 Sec
: 0.1 / 3.68
: 0.03
TMS for 51 N 0.05
: 20868.6941762431*5%/1200
: 0.1*939.091237930939/1200
: 0.078
: 0.3 *20868.6941762431/1200x0.08
PSM : 7.5
: 3.68
: 0.1 / 3.68
: 0.03
: 0.050
4.4 EARTH FAULT INSTANTANEOUS ELEMENT 50N
0.30 * Maximum
a) Earth fault setting : demand current /
CT Ratio
0.15*939.091237
:
930939/1200
: 0.23