GROUP SETTING
Normal Setting Group
Setting Group Change Depending on Power Flow
Alternative Setting Group
Setting Group Change on VT Automation Open
Setting Group Restoration Time from Live-Live
LOOP AUTOMATION SCHEME
Function
Switch Location
No-Voltage Detect
No-Voltage Counts to Lockout
No-Voltage Counts before Open
Open Delay Time
NC Closing at Live-Live
NC Closing Time
Lockout Time (only for SS)
Reset Time
NO Source Select
NO Closing Time
NO Auto Open at Restoration
Directional Load Decrease to RST for NO Open
Directional Load Decrease to ABC for NO Open
GROUP 1 ~ 4
OVER CURRENT
DIRECTION
UNDER VOLTAGE
OVER VOLTAGE
UNDER FREQUENCY
OVER FREQUENCY
SYNCHRONISM CHECK
ANALOG ALARM
1
OFF
2
2
10
OFF
SS
3
2
1
2
NO
2
60
30
OFF
180
NO
50
50
GROUP 4 Unit
NON-DIRECTIONAL
YES
TRIP
400 A
2
0 Min
2
0.2 Sec
01-A
1
0 Sec
0 Sec
RDMT
0 Sec
02-B
1
0 Sec
0 Sec
RDMT
0 Sec
OFF
1000 A
0 Sec
OFF
2000 A
0 Sec
OFF
2000 A
0 Sec
GROUP 4 Unit
NON-DIRECTIONAL
YES
TRIP
60 A
2
0 Min
2
0.2 Sec
20-1
1
0 Sec
0 Sec
RDMT
0 Sec
21-2
1
0 Sec
0 Sec
RDMT
0 Sec
OFF
1000 A
0 Sec
OFF
2000 A
0 Sec
OFF
2000 A
0 Sec
GROUP 4 Unit
NON-DIRECTIONAL
YES
OFF
400 A
2
0.2 Sec
01-A
1
0 Sec
0 Sec
RDMT
0 Sec
02-B
1
0 Sec
0 Sec
RDMT
0 Sec
OFF
1000 A
0 Sec
OFF
2000 A
0 Sec
OFF
2000 A
0 Sec
GROUP 4 Unit
OFF
5 A
0 %
90 DEG
1 Sec
0 Sec
NO
88 DEG
YES
GROUP 4 Unit
OFF
80 %
10 Sec
10 A
YES
GROUP 4 Unit
OFF
10 A
0.2 Sec
OFF
10 A
0.2 Sec
GROUP 4 Unit
ON
20 %
0.01 Sec
GROUP 4 Unit
20 %
20 A
300 DEG
20 %
20 A
330 DEG
20 %
20 A
300 DEG
GROUP 4 Unit
ON
80 %
50 %
0.4 Sec
GROUP 4 Unit
OFF
80 %
1 Sec
GROUP 4 Unit
OFF
120 %
1 Sec
GROUP 4 Unit
OFF
49.8 Hz
0.1 Sec
OFF
49.8 Hz
0.1 Sec
OFF
49.8 Hz
0.1 Sec
OFF
49.8 Hz
0.1 Sec
GROUP 4 Unit
OFF
60.2 Hz
0.1 Sec
OFF
60.2 Hz
0.1 Sec
OFF
60.2 Hz
0.1 Sec
OFF
60.2 Hz
0.1 Sec
GROUP 4 Unit
OFF
5 A
50 %
20 %
500 ms
50 ms
NON-DIRECTIONAL
GROUP 4 Unit
ON
30 DEG
0 Hz
0 %
0.1 Sec
0.05 Sec
GROUP 4 Unit
OFF
16000 A
16000 A
16000 A
38000 V
54000 K
OFF
0 A
0 A
0 A
0 V
0 K
GROUP 4 Unit
0.6 Sec
2 Sec
15 Sec
15 Sec
30 Sec
4
2
1
1
4
2
1
1
4
2
1
1
4
0.6 Sec
2 Sec
15 Sec
15 Sec
30 Sec
10 Sec
OFF
OFF
0.3 Sec
0.2 Sec
I/O
Title Setting Unit
AC RATING
Line Configuration Y-G
System Frequency 50 Hz
Rated Voltage ( L - L ) 20000 V
Reference Voltage ( L - N ) 11500 V
Reference Phase A
CT ratio 1000
CT Direction FORWARD
NCT ratio 1000
NCT Direction FORWARD
Phase Rotation A-B-C
Sample Frequency 128 S/C
VT Type INT_6CVT
VT Secondary Voltage NOT USED
WAVEFORM TRIGGER
Pre-1st Cycle 4
Post-2nd Cycle 4
Pre-2nd Trigger Cycle 20
DEMAND SETTING
Block Interval 15 Min Min
Roll Interval 30 Min Min
ENERGY PROFILE
Profile Type MONTHLY
Demand Reset Day MON Day
Demand Reset Date 1 Date
CAN DO PULSE TIME
Battery Test Pulse Width 1000 ms
FI RESET METHOD
FI Reset Select MANUAL
FI Time Out 0 Hour
CLOSE INTERLOCK
Live Bus Live Line NO
Live Bus Dead Line NO
Dead Bus Live Line NO
Dead Bus Dead Line NO
Sync.Fail YES
VOLTAGE DISPLAY
Voltage Display L-L
AUTOMATIC BATTERY
Checking Cycle 0 Day
Checking Time (Hour) 0 Hour
Checking Time (Min) 0 Min
FI TYPE SELECT
FI Type Select TRIP
ENERGY COUNTER
Holding at Midnight ENABLE
DELAY
Close Delay 0 Sec
SWITCH OPERATION COUNT
Open Count 0
PQM
Title Setting Unit
VOLTAGE UNBALANCE
Voltage Unbalance Detection Level 30 %
Voltage Unbalance Detection Time 1 Sec
CURRENT UNBALANCE
Current Unbalance Detection Level 30 %
Current Unbalance Detection Time 1 Sec
SAG
Sag Detection Level 0.9 PU
Sag Detection Cycle 2 Cycle
SWELL
Swell Detection Level 1.2 PU
Swell Detection Cycle 2 Cycle
INTERRUPTION
Interruption Detection Level 0.1 PU
Interruption Detection Cycle 2 Cycle
VOLTAGE THD ALARM
Alarm Level 0 %
Detection Time 0.4 Sec
CURRENT THD ALARM
Alarm Level 0 %
Detection Time 0.4 Sec
* ATTENTION -1.#IND00
Detection level or alarm level settings for all PQM functions -1.#IND00
can be set with the value “0” for disabling the function. -1.#IND00
COMMUNICATION
PORT
IEC 60870