Chapter 3.7 Cooling Tower
Chapter 3.7 Cooling Tower
COOLING TOWER
Syllabus
Cooling Tower: Types and performance evaluation, Efficient system operation, Flow control
strategies and energy saving opportunities, Assessment of cooling towers
7.1 Introduction
Cooling towers are a very important part of many chemical plants. The primary task of a cooling
tower is to reject heat into the atmosphere. They represent a relatively inexpensive and
dependable means of removing low-grade heat from cooling water. The make-up water source is
used to replenish water lost to evaporation. Hot water from heat exchangers is sent to the cooling
tower. The water exits the cooling tower and is sent back to the exchangers or to other units for
further cooling. Typical closed loop cooling tower system is shown in Figure 7.1.
Cooling towers fall into two main categories: Natural draft and Mechanical draft.
Natural draft towers use very large concrete chimneys to introduce air through the media. Due to
the large size of these towers, they are generally used for water flow rates above 45,000 m 3/hr.
These types of towers are used only by utility power stations.
Mechanical draft towers utilize large fans to force or suck air through circulated water. The water
falls downward over fill surfaces, which help increase the contact time between the water and the
air - this helps maximise heat transfer between the two. Cooling rates of Mechanical draft towers
depend upon their fan diameter and speed of operation. Since, the mechanical draft cooling
towers are much more widely used, the focus is on them in this chapter.
In the counter flow induced draft design, hot water enters at the top, while the air is introduced at
the bottom and exits at the top. Both forced and induced draft fans are used.
In cross flow induced draft towers, the water enters at the top and passes over the fill. The air,
however, is introduced at the side either on one side (single-flow tower) or opposite sides
(double-flow tower). An induced draft fan draws the air across the wetted fill and expels it
through the top of the structure.
The Figure 7.2 illustrates various cooling tower types. Mechanical draft towers are available in
a large range of capacities. Normal capacities range from approximately 10 tons, 2.5 m 3/hr flow
to several thousand tons and m3/hr. Towers can be either factory built or field erected – for
example concrete towers are only field erected.
Many towers are constructed so that they can be grouped together to achieve the desired
capacity. Thus, many cooling towers are assemblies of two or more individual cooling towers or
“cells.” The number of cells they have, e.g., a eight-cell tower, often refers to such towers.
Multiple-cell towers can be lineal, square, or round depending upon the shape of the individual
cells and whether the air inlets are located on the sides or bottoms of the cells.
The basic components of an evaporative tower are: Frame and casing, fill, cold water basin, drift
eliminators, air inlet, louvers, nozzles and fans.
Frame and casing: Most towers have structural frames that support the exterior enclosures
(casings), motors, fans, and other components. With some smaller designs, such as some glass
fiber units, the casing may essentially be the frame.
Fill: Most towers employ fills (made of plastic or wood) to facilitate heat transfer by maximising
water and air contact. Fill can either be splash or film type.
With splash fill, water falls over successive layers of horizontal splash bars, continuously
breaking into smaller droplets, while also wetting the fill surface. Plastic splash fill promotes
better heat transfer than the wood splash fill.
Film fill consists of thin, closely spaced plastic surfaces over which the water spreads, forming a
thin film in contact with the air. These surfaces may be flat, corrugated, honeycombed, or other
patterns. The film type of fill is the more efficient and provides same heat transfer in a smaller
volume than the splash fill.
Cold water basin: The cold water basin, located at or near the bottom of the tower, receives the
cooled water that flows down through the tower and fill. The basin usually has a sump or low
point for the cold water discharge connection. In many tower designs, the cold water basin is
beneath the entire fill.
In
channeled to a perimeter trough that functions as the cold water basin. Propeller fans are mounted
beneath the fill to blow the air up through the tower. With this design, the tower is mounted on
legs, providing easy access to the fans and their motors.
Air inlet: This is the point of entry for the air entering a tower. The inlet may take up an entire
side of a tower—cross flow design— or be located low on the side or the bottom of counter flow
designs.
Louvers: Generally, cross-flow towers have inlet louvers. The purpose of louvers is to equalize
air flow into the fill and retain the water within the tower. Many counter flow tower designs do
not require louvers.
Nozzles: These provide the water sprays to wet the fill. Uniform water distribution at the top of
the fill is essential to achieve proper wetting of the entire fill surface. Nozzles can either be fixed
in place and have either round or square spray patterns or can be part of a rotating assembly as
found in some circular cross-section towers.
Fans: Both axial (propeller type) and centrifugal fans are used in towers. Generally, propeller
fans are used in induced draft towers and both propeller and centrifugal fans are found in forced
draft towers. Depending upon their size, propeller fans can either be fixed or variable pitch.
A fan having non-automatic adjustable pitch blades permits the same fan to be used over a wide
range of kW with the fan adjusted to deliver the desired air flow at the lowest power
consumption.
Automatic variable pitch blades can vary air flow in response to changing load conditions.
Tower Materials
In the early days of cooling tower manufacture, towers were constructed primarily of wood.
Wooden components included the frame, casing, louvers, fill, and often the cold water basin. If
the basin was not of wood, it likely was of concrete.
Today, tower manufacturers fabricate towers and tower components from a variety of
materials. Often several materials are used to enhance corrosion resistance, reduce maintenance,
and promote reliability and long service life. Galvanized steel, various grades of stainless steel,
glass fiber, and concrete are widely used in tower construction as well as aluminum and various
types of plastics for some components.
Wood towers are still available, but they have glass fiber rather than wood panels (casing) over
the wood framework. The inlet air louvers may be glass fiber, the fill may be plastic, and the cold
water basin may be steel.
Larger towers sometimes are made of concrete. Many towers—casings and basins—are
constructed of galvanized steel or, where a corrosive atmosphere is a problem, stainless steel.
Sometimes a galvanized tower has a stainless steel basin. Glass fiber is also widely used for
cooling tower casings and basins, giving long life and protection from the harmful effects of
many chemicals.
Plastics are widely used for fill, including PVC, polypropylene, and other polymers. Treated
wood splash fill is still specified for wood towers, but plastic splash fill is also widely used when
water conditions mandate the use of splash fill. Film fill, because it offers greater heat transfer
efficiency, is the fill of choice for applications where the circulating water is generally free of
debris that could plug the fill passageways.
Plastics also find wide use as nozzle materials. Many nozzles are being made of PVC, ABS,
polypropylene, and glass-filled nylon. Aluminum, glass fiber, and hot-dipped galvanized steel are
commonly used fan materials. Centrifugal fans are often fabricated from galvanized steel.
Propeller fans are fabricated from galvanized, aluminum, or molded glass fiber reinforced plastic.
i) “Range” is the difference between the cooling tower water inlet and outlet temperature. (See
Figure 7.3).
ii) “Approach” is the difference between the cooling tower outlet cold water temperature and
ambient wet bulb temperature. Although, both range and approach should be monitored,
the `Approach’ is a better indicator of cooling tower performance. (see Figure 7.3).
iii) Cooling tower effectiveness (in percentage) is the ratio of range, to the ideal range, i.e.,
difference between cooling water inlet temperature and ambient wet bulb temperature, or
in other words it is = Range / (Range + Approach).
iv) Cooling capacity is the heat rejected in kCal/hr or TR, given as product of mass flow rate of
water, specific heat and temperature difference.
v) Evaporation loss is the water quantity evaporated for cooling duty and, theoretically, for every
10,00,000 kCal heat rejected, evaporation quantity works out to 1.8 m 3. An empirical
relation used often is:
vii) Blow down losses depend upon cycles of concentration and the evaporation losses and is
given by relation:
viii) Liquid/Gas (L/G) ratio, of a cooling tower is the ratio between the water and the air mass
flow rates. Against design values, seasonal variations require adjustment and tuning of
water and air flow rates to get the best cooling tower effectiveness through measures like
water box loading changes, blade angle adjustments.
Thermodynamics also dictate that the heat removed from the water must be equal to the
heat absorbed by the surrounding air:
where: L/G = liquid to gas mass flow ratio (kg/kg) T 1 = hot water temperature
Capacity
Heat dissipation (in kCal/hour) and circulated flow rate (m 3/hr) are not sufficient to understand
cooling tower performance. Other factors, which we will see, must be stated along with flow rate
m3/hr. For example, a cooling tower sized to cool 4540 m 3/hr through a 13.9oC range might be
larger than a cooling tower to cool 4540 m3/hr through 19.5oC range.
Range
Range is determined not by the cooling tower, but by the process it is serving. The range at the
exchanger is determined entirely by the heat load and the water circulation rate through the
exchanger and on to the cooling water.
Thus, Range is a function of the heat load and the flow circulated through the system.
Cooling towers are usually specified to cool a certain flow rate from one temperature to another
temperature at a certain wet bulb temperature. For example, the cooling tower might be specified
to cool 4540 m3/hr from 48.9oC to 32.2oC at 26.7oC wet bulb temperature.
Cold Water Temperature 32.2oC – Wet Bulb Temperature (26.7oC) = Approach (5.5oC)
As a generalization, the closer the approach to the wet bulb, the more expensive the cooling tower
due to increased size. Usually a 2.8 oC approach to the design wet bulb is the coldest water
temperature that cooling tower manufacturers will guarantee. If flow rate, range, approach and
wet bulb had to be ranked in the order of their importance in sizing a tower, approach would be
first with flow rate closely following the range and wet bulb would be of lesser importance.
Heat Load
The heat load imposed on a cooling tower is determined by the process being served. The degree
of cooling required is controlled by the desired operating temperature level of the process. In
most cases, a low operating temperature is desirable to increase process efficiency or to improve
the quality or quantity of the product. In some applications (e.g. internal combustion engines),
however, high operating temperatures are desirable. The size and cost of the cooling tower is
proportional to the heat load. If heat load calculations are low undersized equipment will be
purchased. If the calculated load is high, oversize and more costly, equipment will result.
Process heat loads may vary considerably depending upon the process involved. Determination
of accurate process heat loads can become very complex but proper consideration can produce
satisfactory results. On the other hand, air conditioning and refrigeration heat loads can be
determined with greater accuracy.
Information is available for the heat rejection requirements of various types of power
equipment. A sample list is as follows:
* Air Compressor
- Single-stage - 129 kCal/kW/hr
- Single-stage with after cooler - 862 kCal/kW/hr
- Two-stage with intercooler - 518 kCal/kW/hr
- Two-stage with intercooler and after cooler - 862 kCal/kW/hr
* Refrigeration, Compression - 63 kCal/min/TR
* Refrigeration, Absorption - 127 kCal/min/TR
* Steam Turbine Condenser - 555 kCal/kg of
steam
* Diesel Engine, Four-Cycle, Supercharged - 880 kCal/kW/hr
* Natural Gas Engine, Four-cycle - 1523 kCal/kW/hr
(18 kg/cm2 compression)
Wet Bulb Temperature
Initial selection of towers with respect to design wet bulb temperature must be made on the basis
of conditions existing at the tower site. The temperature selected is generally close to the average
maximum wet bulb for the summer months. An important aspect of wet bulb selection is, whether
it is specified as ambient or inlet. The ambient wet bulb is the temperature, which exists generally
in the cooling tower area, whereas inlet wet bulb is the wet bulb temperature of the air entering
the tower. The later can be, and often is, affected by discharge vapours being recirculated into the
tower. Recirculation raises the effective wet bulb temperature of the air entering the tower with
corresponding increase in the cold water temperature. Since there is no initial knowledge or
control over the recirculation factor, the ambient wet bulb should be specified. The cooling tower
supplier is required to furnish a tower of sufficient capability to absorb the effects of the increased
wet bulb temperature peculiar to his own equipment.
It is very important to have the cold water temperature low enough to exchange heat or to
condense vapours at the optimum temperature level. By evaluating the cost and size of heat
exchangers versus the cost and size of the cooling tower, the quantity and temperature of the
cooling tower water can be selected to get the maximum economy for the particular process.
The Table 7.1 illustrates the effect of approach on the size and cost of a cooling tower. The towers
included were sized to cool 4540 m 3/hr through a 16.67oC range at a 26.7oC design wet bulb.
The overall width of all towers is 21.65 meters; the overall height, 15.25 meters, and the pump
head, 10.6 m approximately.
Table 7.1 APPROACH Vs. COOLING TOWER SIZE (4540 m3/hr; 16.67oC Range 26.7oC Wet Bulb;
10.7 m Pump Head)
Approach oC 2.77 3.33 3.88 4.44 5.0 5.55
Suppose a cooling tower is installed that is 21.65 m wide × 36.9 m long × 15.24m high, has three
7.32 m diameter fans and each powered by 25 kW motors. The cooling tower cools from 3632
m3/hr water from 46.1oC to 29.4oC at 26.7oC WBT dissipating 60.69 million kCal/hr. The Table
7.2 shows what would happen with additional flow but with the range remaining constant at
16.67oC. The heat dissipated varies from 60.69 million kCal/hr to 271.3 million kCal/hr.
Table 7.2 Flow vs. Approach for a Given Tower (Tower is 21.65 m × 36.9 M; Three
7.32 M Fans; Three 25 kW Motors; 16.7 C Range with 26.7oC Wet Bulb)
o
Approach
For meeting the increased 3heat load, few modifications Cold
wouldWater
be neededHot Water the water
to increase Million
FlowHowever,
flow through the tower. m /hr at higher capacities,
oC oC would increase.
the approach oC kCal/hr
In a cooling tower, hot water is distributed above fill media which flows down and is cooled due
to evaporation with the intermixing air. Air draft is achieved with use of fans. Thus some power is
consumed in pumping the water to a height above the fill and also by fans creating the draft.
An energy efficient or low power consuming cooling tower is to have efficient designs of fill
media with appropriate water distribution, drift eliminator, fan, gearbox and motor. Power savings
in a cooling tower, with use of efficient fill design, is directly reflected as savings in fan power
consumption and pumping head requirement.
Heat exchange between air and water is influenced by surface area of heat exchange, time of heat
exchange (interaction) and turbulence in water effecting thoroughness of intermixing. Fill media
in a cooling tower is responsible to achieve all of above.
Splash and Film Fill Media: As the name indicates, splash fill media generates the required heat
exchange area by splashing action of water over fill media and hence breaking into smaller water
droplets. Thus, surface of heat exchange is the surface area of the water droplets, which is in
contact with air.
Film Fill and its Advantages
In a film fill, water forms a thin film on either side of fill sheets. Thus area of heat exchange is
the surface area of the fill sheets, which is in contact with air.
Typical comparison between various fill media is shown in Table 7.3.
Tablerequirements
Due to fewer 7.3 Typical Comparisons Between Various
of air and pumping Fill Media
head, there is a tremendous saving in power with
the invention of film fill.
Splash Fill Film Fill Low Clog Film Fill
Recently, low-clog film fills with higher flute sizes have been developed to handle high turbid
waters. For sea water,
Possible low clog film fills
L/G Ratio 1.1 –are
1.5 considered as1.5the best choice in terms
– 2.0 of power
1.4 – 1.8
saving and performance compared to conventional splash type fills.
Effective Heat 30 – 45 m2/m3 150 m2/m3 85 – 100 m2/m3
ChoosingExchange
a Cooling Tower
Area
The counter-flow
Fill Height and cross flows 5are
Required – 10two mbasic designs
1.2 –of1.5cooling
m towers
1.5based
– 1.8 mon the
fundamentals of heat exchange. It is well known that counter flow heat exchange is more
effective as compared
Pumping Headto cross flow or parallel
9 – 12 mflow heat exchange.
5–8m 6–9m
Cross-flow cooling towers are provided with splash fill of concrete, wood or perforated PVC.
Requirement
Counter-flow cooling towers are provided with both film fill and splash fill.
TypicalQuantity of Air of Cross flow Spash
comparison HighFill, Counter Flow
MuchTower
low with Film FillLowand Splash
Required
fill is shown in Table 7.4. The power consumption is least in Counter Flow Film Fill followed by
Counter Flow Splash Fill and Cross-Flow Splash Fill.
Table 7.4 Typical Comparison of Cross flow splash fill, Counter Flow Tower
with Film Fill and Splash Fill
Number of Towers : 2
C
7.3 Efficient System Operation o
o
Cooling Water Treatment l
i
Cooling water treatment is mandatory for any cooling tower whether with splash fill or with n
film type fill for controlling suspended solids, algae growth, etc. g
With increasing costs of water, efforts to increase Cycles of Concentration (COC), by
Cooling Water Treatment would help to reduce make up water requirements significantly. In T
large industries, power plants, COC improvement
Counter Flow Filmis oftenCounter
considered
Flowas a key area for water
Cross-Flow Splash o
conservation. Fill Splash Fill Fill w
Fill Height, Meter 1.5 5.2 11.0 e
Drift Loss in the Cooling Towers r
Plant Area per Cell 14.4 × 14.4 14.4 × 14.4 12.64 × 5.49
It is very Number
difficult ofto Cells
ignoreper
drift problem6 in cooling towers. 6Now-a-days most of 5the end F
Tower
user specification calls for 0.02% drift loss. a
With technological
Power at development
Motor and processing
253 of PVC, manufacturers
310 have brought
330 large n
change inTerminal/Tower,
the drift eliminator
kW shapes and the possibility of making efficient designs of drift s
eliminators that Pumping
Static enable end user to specify
Head, 7.2 the drift loss requirement
10.9 to as low as 0.003 –
12.05
0.001%.
The purpose of a cooling tower fan is to move a specified quantity of air through the system,
overcoming the system resistance which is defined as the pressure loss. The product of air
flow and the pressure loss is air power developed/work done by the fan; this may be also
termed as fan output and input kW depends on fan efficiency.
The fan efficiency in turn is greatly dependent on the profile of the blade. An aerodynamic
profile with optimum twist, taper and higher coefficient of lift to coefficient of drop ratio can
provide the fan total efficiency as high as 85-92 %. However, this efficiency is drastically
affected by the factors such as tip clearance, obstacles to airflow and inlet shape, etc.
As the metallic fans are manufactured by adopting either extrusion or casting process it is
always difficult to generate the ideal aerodynamic profiles. The FRP blades are normally
hand moulded which facilitates the generation of optimum aerodynamic profile to meet
specific duty condition more efficiently. Cases reported where replacement of metallic or
Glass fibre reinforced plastic fan blades have been replaced by efficient hollow FRP blades,
with resultant fan energy savings of the order of 20-30% and with simple pay back period of
6 to 7 months.
Also, due to lightweight, FRP fans need low starting torque resulting in use of lower HP
motors. The lightweight of the fans also increases the life of the gear box, motor and bearing
is and allows for easy handling and maintenance.
Performance Assessment of Cooling Towers
In operational performance assessment, the typical measurements and observations involved
are:
• Cooling tower design data and curves to be referred to as the basis.
• Intake air WBT and DBT at each cell at ground level using a whirling pyschrometer.
• Exhaust air WBT and DBT at each cell using a whirling psychrometer.
• CW inlet temperature at risers or top of tower, using accurate mercury in glass or a digital
thermometer.
• Process data on heat exchangers, loads on line or power plant control room readings, as
relevant.
• CW flow measurements, either direct or inferred from pump motor kW and pump head and
flow characteristics.
= 0.00085 x 1.8 x
1565 x (44-37.6)
= 15.32 m3/hr per
cell
* Percentage = [15.32/1565]*100
Evaporation Loss
= 0.97%
* Blow down = Evaporation losses
requirement for / (COC–1)
site COC of 2.7
= 15.32/(2.7–1) per
cell i.e., 9.01
m3/hr
* Make up water = Evaporation Loss
requirement/cell in + Blow down Loss
7.5 Energy Saving Opportunities in Cooling Towers
− Follow manufacturer’s recommended clearances around cooling towers and
relocate or modify structures that interfere with the air intake or exhaust.
− Optimise cooling tower fan blade angle on a seasonal and/or load basis.
− Correct excessive and/or uneven fan blade tip clearance and poor fan balance.
− On old counter-flow cooling towers, replace old spray type nozzles with new
square spray ABS practically non-clogging nozzles.
− Cover hot water basins to minimise algae growth that contributes to fouling.
− Replace slat type drift eliminators with low pressure drop, self extinguishing, PVC
cellular units.
− Segregate high heat loads like furnaces, air compressors, DG sets, and isolate
cooling towers for sensitive applications like A/C plants, condensers of captive
power plant etc. A 1oC cooling water temperature increase may increase A/C
compressor kW by 2.7%. A 1oC drop in cooling water temperature can give a
heat rate saving of 5 kCal/kWh in a thermal power plant.
− Monitor L/G ratio, CW flow rates w.r.t. design as well as seasonal variations. It
would help to increase water load during summer and times when approach is
high and increase air flow during monsoon times and when approach is narrow.
− Consider energy efficient FRP blade adoption for fan energy savings.
Table 7.5 Typical Problems and Trouble Shooting for Cooling Towers
Problem / Difficulty
Possible Causes
Remedies/Rectifying Action
1.Excessive absorbed current / electrical load
Voltage Reduction
3. Overloading owing to excessive air flow-fill has minimum water loading per m2 of tower section
Regulate the water flow by means of the valve
4. Excessive circulating water flow (possibly owing to too high pumping head)
Adjust the water flow-rate by means of the regulating valves. Check for absence of damage to the fill
Loss of water from basins/pans
1. Float-valve not at correct level
Adjust the make-up valve