Power System Protection: Lab Session 6
Power System Protection: Lab Session 6
Lab Session 6
6.0 Introduction
Frequency variations in the system occur due to the variation in the prime mover speed.
In a large inter-connected stable system frequency variations are rare. Because a generator unit
connected to a large stable system cannot operate at higher or lower frequency than the system
frequency. But a smaller system or a generator working alone is prone to frequency variations
due to the variations in load.
This abnormal condition is not very dangerous for the system. So frequency relay sense
the abnormal condition and activate alarm and if this condition persist for a long time then relay
operates the circuit breaker.
6.1 Over-Frequency
This condition is due to the increase in speed of prime mover. On the generation site this
is protected by the over-speed device. An over-frequency relay can be used as backup to
mechanical devices. Again, if the unit is connected to a stable system, the generator cannot
operate above the system frequency. However, if the system is dynamically unstable over-
frequency relays can alert the operator. In general, the governing devices will protect the unit
from over-speed. But for reliable system all system conditions must be addressed.
6.4 Procedure
Step 1:
Draw a power system having a three phase programmable source, three phase circuit
breaker, three-phase VI measurement unit and three phase RLC series load. Connect the blocks
as shown below.
Set the properties of each block as mentioned below. Keep all other parameters as it is.
System Frequency: 50 Hz
Total Simulation Time: 0.5 s
Solver: Ode23tb (stiff/TR-BDF2)
Solver reset Method: Robust
Three-Phase Breakers:
Initial status of breakers: closed
Step 2:
Set the parameters of all the blocks given in above diagram as specified below.
Integrator:
Initial condition: 0
This block is used to find the area under the curve. The area under the sinusoidal wave
depends upon the frequency. Because with the increase in frequency wave shrinks on time axis
and its area decreases and vice versa. It means the frequency of system can be judged from the
area under the curve. Observe the output of integrator on ‘scope’ along with the sinusoidal
waveform.
Gain:
This block is used to increase the difference between the areas at two different
frequencies. To set the value of gain, follow the instructions given below.
For all the students, from Reg. No. 1 to 5 gain is 50 times of their roll number, from Reg.
No. 6 to 25 gain is 10 times of their roll number, from Reg. No. 26 to 50 gain is 5 times of their
roll number and for the rest of the students gain is equal to their roll number.
Gain = 100
Sample time: 50e-6
Counter2:
Count Direction: Up
Count Event: Rising edge
Count Size: User defined
Max. Count: 1e6
Initial Count: 0
Output: Count
Reset input: Check this option
Pulse Generator:
Pulse type: Time based
Time: Use simulation time
Amplitude: 1
Period: 0.1
Pulse width (%): 1
Time delay (sec) 0.099
Set the proper initial condition of ‘S-R Flip-Flop’
Step 3:Simulate the system in following conditions by setting the parameters of ‘Three-Phase
Programmable Voltage Source’.