Design of Septic Tank

The document provides calculations to determine the required capacity of a septic tank. It estimates the number of users, waste water inflow, sludge accumulation, and retention period. Based on these factors, it calculates the total waste volume to be 11.8 cubic meters. The recommended septic tank size is 8 meters long by 2 meters wide by 1.5 meters deep, with a capacity of 19.2 cubic meters. This meets the volume needs calculated and passes other design checks for soil bearing capacity and uplift forces.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
100% found this document useful (1 vote)
615 views1 page

Design of Septic Tank

The document provides calculations to determine the required capacity of a septic tank. It estimates the number of users, waste water inflow, sludge accumulation, and retention period. Based on these factors, it calculates the total waste volume to be 11.8 cubic meters. The recommended septic tank size is 8 meters long by 2 meters wide by 1.5 meters deep, with a capacity of 19.2 cubic meters. This meets the volume needs calculated and passes other design checks for soil bearing capacity and uplift forces.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 1

A.

Design of Septic Tank Capacity

1.0 Design Consideration per Philippine Sanitary Code 2.0 No. of User
Retention period 1.00 day/s Operation Manager & Staff 2 MTH 2
Sludge and Scum Storage 2/3 tank Volume Shift Supervisor 1 REL 2
Waste Water Inflow 75.00 gal/person/day CRO 4 ALSEC 1
Sludge Accumulation Rate 40.00 lit/person/year BOP 6 LGN 2
Maximum Filled Volume 50% tank vol. DCS 2 Others 5
Desludging Interval 4.00 year/s Estimated No. of User 27

3.0 Volume of Waste Water 5.0 Summary


Total waste water inflow in a day 7,492.50 lit/day
Total waste water in Retention period 7,492.50 lit
Say: 7,493.00 lit.
Total Sludge and Scum 4,320.00 lit.

1.80
Total Waste inflow 11,813.0 lit.
Or 11.8 cu.m 17.7 cu.m

4.0 Septic Tank Sizing


Free Board 0.30 m 5.33 2.67
Depth of Septic Tank 1.50 m 8.00
Width of Septic Tank 2.00 m
6.0 Volume Capacity Check
Length of digestion chamber 5.00 m Volume Inflow 17.72 cu.m
Total Tank Length 7.50 m Volume of Tank 19.20 cu.m
Say: 8.00 m Therefore, Septic Tank Capcity: OK

B. Soil Bearing Check

Allowable SBC 140.00 KN/Sq.m Total wt. 493.44 KN


Concrete unit wt. 24.00 KN/cu.m Bearing pressure @ the bot. 30.84 KN/Sq.m
Water unit wt. 10.00 KN/cu.m Therefore, SBC OK
Ground Water level - 3.00 m

Sturctural Wt.
Element Length Width Thickness Unit Wt. Total Wt.
Top slab 8.00 2.00 0.20 24.00 76.80
Wall 1.80 2.00 0.20 24.00 51.84
Bot Slab 8.00 2.00 0.20 24.00 76.80
Water Full 8.00 2.00 1.80 10.00 288.00

B. Check for Uplift Force ( Clause 10.2 and 2.4.7.4 of EC7: en 1997-1-1)

Note: Neglecting side friction and other possible stablizing forces

Stabilizing Force
Ultimate limit state, Gstb, d 444.10 KN
Destabilizing Force
Ultimate limit state, Vdst,d - KN