The live loads that shall be used for different building areas are specified. Offices shall use 4 kN/m2 accounting for general office loads of 2.5 kN/m2 and additional 1.5 kN/m2 for removable partitions. Canteens, halls, and other common areas shall use 5 kN/m2. Toilet rooms and locker rooms shall use 3 kN/m2. Kitchens shall use 7.5 kN/m2. The design wind load is 40 m/s. Notional horizontal loads of 0.015 of the dead load will be applied according to BS8110-1:1997.

Uploaded by

khlee.mitra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
110 views

Live Load PDF

The live loads that shall be used for different building areas are specified. Offices shall use 4 kN/m2 accounting for general office loads of 2.5 kN/m2 and additional 1.5 kN/m2 for removable partitions. Canteens, halls, and other common areas shall use 5 kN/m2. Toilet rooms and locker rooms shall use 3 kN/m2. Kitchens shall use 7.5 kN/m2. The design wind load is 40 m/s. Notional horizontal loads of 0.015 of the dead load will be applied according to BS8110-1:1997.

Uploaded by

khlee.mitra
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Live Load (Q)

The following live loads shall be used:

Type of Live loads (kN/m 2) remark


Building/room
Offices (including 2.5 + 1.5 = 4 BS6399 1997: General Office
removable lightweight =2.5 kN/m2
partitions) Estimated removable lightweight
partitions = 1.5kN/m2
Canteens, halls, event 5 Follow BS6399 1997
corridors,

\
center,
stairs, concourse, store
Toilets, wash and 3 Follow BS6399 1997
locker rooms,
computer room,
electrical equipment
room
Kitchen 7.5 Follow BS6399 1997
Car park & driveways 5 Follow BS6399 1984
(If follow BS6399 1997 = 2.5kN/m2
(used for LHDN car park), surface crack
lines may occur)

M&E /motor room 7.5 Follow BS6399 1997

Roof + ceiling + 1.5 Follow BS6399 1997


services

Wind Load

Design Wind Load = 40 mis.

According to Malaysia Standards MS1553 :2002,


100 years return period @ Kuching =34.9m/s

Notional Load (horizontal)

Notional load (Fx & Fy) with lateral load factor = 0.015 (1.5%) of Dead Load would be
applied to every storey level according to BS8110-l :1997 - clause 3.1.4.