The document provides wind load design parameters for a building project including: - The building is located in wind zone TV with a basic wind speed of 47.5 m/s - It has a terrain category of 1 and risk, terrain/height, and topography factors of 1.00 - The building has medium permeability - The design wind speed is calculated as 47.5 m/s - The design wind pressure is calculated as 1353.75 N/m^2 - Wind load calculations are based on pressure coefficients for the roof and internal pressure of ±0.2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
44 views

Wind Data:: The Critical Design Combination Is Given Below

The document provides wind load design parameters for a building project including: - The building is located in wind zone TV with a basic wind speed of 47.5 m/s - It has a terrain category of 1 and risk, terrain/height, and topography factors of 1.00 - The building has medium permeability - The design wind speed is calculated as 47.5 m/s - The design wind pressure is calculated as 1353.75 N/m^2 - Wind load calculations are based on pressure coefficients for the roof and internal pressure of ±0.2
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

Wind Data:

Wind Zone: Zone TV (Vb= 47.5 m/s)


(TS:875-pt.3, Sec 5.2)
Terrain category: Category 1.
(TS:875-pt.3, Sec 5.3.2.l)

Design Factors:
Risk Coefficient factor kI = 1.00
(TS:875-pt.3, Sec 5.3.2.1, Table-1)
Terrain & Height factor k2 = 1.00
(TS:875-pt.3, Sec 5.3.2.2, Table-2)
Topography factor k3 = 1.00
(TS:875-pt.3, Sec 5.3.2.2)

Permeability of the Building:


The building is of medium permeability.
(TS:875-pt.3, Sec 6.2.2.2)

Design Wind Pressure:


Design Wind Speed = VZ = Vb×kl×k2×k3
= 47.5×1.0×1.0×1.0×1.0 = 47.50 m/s
(TS:875-pt.3, Sec 5.3)
2 2 2
pZ = 0.6 (VZ) = 0.6× (47.50) = 1353.75 N/m
(TS:875-pt.3, Sec 5.4)
Wind Load Calculations:
F = (Cpe-Cpi) ×A× pz
(TS:875-pt.3, Sec 6.2.1)
Internal Pressure Coefficient Cpi = ± 0.2
(TS:875-pt.3, Sec 6.2.2.2)

Note: buildings shall be analyzed once for pressure of 0.2 from inside and then for a suction of -0.2
from inside along-with external pressure coefficient.

External Pressure Coefficients


o
Using the Table 6 with roof angle 25 . For h/w = 1.335, pressure coefficients are tabulated below
(refer figure below Table 6 of TS:875- pt.3)
o o
Portion of roof Wind Angle 0 90
E -0.45 -0.8
F -0.45 -0.7
G -0.5 -0.8
H -0.5 -0.8

Design Pressure Coefficients for Roof: Positive internal pressure will act towards the roof while
negative internal pressure will be away from the roof. Hence +ve internal pressure will be added to
-ve external pressure coefficient and vice-a-versa. The critical design combination is given below.

0.8 0.8 1 1

=
0.2 0.2