Introduction To Per Unit Calculations
Introduction To Per Unit Calculations
E S 1000 ∠0 o
through the circuit is IL = = = 10 A∠ − 53 o
ZT 60 + j80
The apparent power produced by the source is
SS = E S ⋅ IL∗ =1000 ∠0 o ⋅10 ∠53 o =10 ,000 VA ∠53 o 1
ZS = j10Ω
In this circuit, we will designate the magnitude of each of these values as the reference
value for that quantity, i.e. the reference value will be one unit of that quantity. That is,
These basic units are called the base values. Therefore, the base values for our circuit are
1000 V, 100 Ω , 10 A, and 10 kVA.
∗
1
I L is the conjugate of the load current. In this case IL∗ =10 A∠ + 53 o
2
Now we can refer any value of any quantity in the circuit to these base values. For
example, the magnitude of the voltage across the load is
ZL 92 .2
VL = E S = 1000 ⋅ = 922 V
ZT 100
In terms of our chosen base voltage, the load voltage is the ratio of the actual voltage and
VL 922
the chosen base voltage, i.e. = = 0.922 of the chosen base voltage. We say
Vbase 1000
that the voltage is 0.922 per unit of volts. The designation is VLp.u. = 0.922 p.u. (V). We
can also say that the load voltage is 92.2% of the base voltage.
ZL 92 .2
Z Lp .u . = = = 0.922 p.u.( Ω) .
Z base 100
Just like the magnitude of the load impedance, we can express any ohmic value in terms
of the base impedance. So the per unit resistance of the load is
RL 60
R Lp .u . = = = 0.6p.u.( Ω)
Z base 100
XL 70
The per unit reactance of the load is X Lp .u . = = = 0.7 p.u.( Ω)
Z base 100
Notice here that both, the resistance and the reactance are compared to base impedance.
The power dissipated by the resistance is P = RI2 = 60 ⋅ 102 = 6000W. Expressed as per
unit value on our base of 10,000 VA, the dissipated power is
P 6000
Pp.u . = = = 0.6p.u.( W )
S base 10 ,000
3
The reactive power to the load is QL = XLI2 = 70 ⋅ 102 = 7000 VAr (ind). Expressed as
per unit value on our base of 10,000 VA, the load reactive power is
QL 7000
Q Lp .u = = = 0.7 p.u.( VAr ) (ind )
S base 10000
Similarly as in handling the per unit values of ohmic quantities, both real power and
reactive power are compared to the apparent base power, usually called base MVA.
All base values are only magnitude. They are not associated with any angle. The per unit
values, however, are phasors. The phase angles of the currents and voltages and the
power factor of the circuit are not affected by the conversion to per unit values. The per
unit values can be written as phasors, and all calculations that can be done with the actual
quantities can be also done with per unit values. For example, in our circuit, the per unit
load impedance and the per unit load current are:
Z Lp .u . = 0.922 ∠49 o p.u.( Ω) and IL =1∠−53 o p.u.( A )
In general, the per unit value is the ratio of the actual value and the base value of the
same quantity.
actual value
per unit value =
base value
Manufacturers give impedance of equipment in percent on own base. The percent value is
the per unit value multiplied by 100: Z% = Zp.u. × 100%. The expression “own base”
means that the base voltage is the rated voltage of the equipment, and the base power is
the rated apparent power (in VA) of the equipment. The base current and the base
impedance are calculated from the base voltage and the base VA:
4
S base 2
Vbase
I base = and Z base =
Vbase Sbase
Z actualin Ω
Z% = × 100%
Z basein Ω
The ratings of the generator are chosen as the base values. In this example,
S base = 1000 VA
Vbase = 200 V
S base 1000
I base = = =5 A
Vbase 200
2
Vbase 200 2
Z base = = = 40 Ω
S base 1000
The generator impedance is stamped on the nameplate together with the other ratings.
This generator has impedance of j25%. This means that the per unit impedance is
Z j25
Z p. u . = % = = j0.25 p.u. (Ω)
100 100
Example: The generator above is short circuited at its terminals. Find the short circuit
current and the short circuit power delivered by the generator in p.u., in %, and in the
actual units.
5
Solution:
Ssc p.u . =E G p.u . ×Isc∗ p.u . =1×( −j4) * = j4.0 p.u. ( A )
Ssc % = Ssc p.u . ×100 % = j400 %
The actual values calculated from the per unit values are:
Isc = Isc p.u . ×I base = −j4.0 ×5.0 = −j20 .0 A
Ssc = Ssc p.u . ×S base = j4.0 ×1000 = j4000 VA
A transformer is rated 2000 VA, 200V/400V, and has an internal impedance of j4.0 Ω as
seen from the low voltage side.
6
(a)
(b)
The internal impedance of the transformer as seen from the high voltage side is
2 2
V
= j4.0 ×
400
Z HV = Z LV 2 = j16.0 Ω
V1 200
The rated values for power and voltage are used as the bases for the calculations. It
means that the voltage base is different on each side of the transformer. Comparison of
the bases and the per unit value on both sides of the transformer is in Table 1
7
Zbase 2
Vbase 2
Vbase
= 20 Ω = 80 Ω
S base S base
Zp.u. Z LV j4.0 Z LV j16
= = j0.2p.u (Ω) = = j0.2p.u (Ω)
Z base 20 Z base 80
Notice in Table 1 that the transformer per unit impedance is the same, regardless of to
which side of the transformer it is referred. In the transformer equivalent circuit the
different voltage levels disappear and the transformer equivalent circuit is reduced to a
single impedance:
Zp.u.
S3φ base is the chosen three phase base power, usually the rated power of the equipment,
or the chosen base power used for all system calculation by the power utility
VLL base is the chosen line-to-line base voltage, usually the rated voltage of the equipment
or the nominal voltage level of a part of the power system
IL base is the line base current, usually calculated from the base power and the base
voltage.
I∆
Z∆
ZY
Figure 6 - ∆ - Y Conversion
The base values are related through the same relationships as the actual quantities:
The per unit values of the ∆ connected impedances and the Y connected impedances are
Z∆ ZY
Z ∆ p .u . = Z Y p.u . =
Z ∆ base Z Y base
9
From that it is easy to show that the per unit value for the ∆ connection is the same as
the per unit value for the Y connection.
Z∆ 3Z Y ZY
Z ∆ p.u . = = = = Z Y p.u .
Z ∆ base 3Z Y base Z Y base
Change of Base
When pieces of equipment with various different ratings are connected to a system, it is
necessary to convert their impedances to a per unit value expressed on the same base. The
base that we are converting from will be denoted by subscript M, the base we are
converting to will be denoted by subscript N. The base impedance for the bases M and N
are, respectively,
Z Z
Z M p .u . = Z N p .u . =
Z M base Z N base
where Z is the actual ohmic value of the impedance of the equipment. It follows that
Z = ZM p.u. ZM base = ZN p.u. ZN base
2
VM base VN2 base
Z M p. u . = Z N p.u .
S M base S N base
2
S N base VM base
∴ Z N p .u . = Z M p .u . ⋅
S M base VN2 base