WAY Race Ittings: Fig. 010 Sway Brace Pipe Attachment

Sway brace fittings are designed to brace pipes against sway and seismic disturbances. They attach to pipes between 1-6 inches in diameter and are braced with 1 or 1 1/4 inch pipes. The fittings are electro-galvanized steel and install by placing over the pipe to brace, adjusting the angle, and inserting the bracing pipe through the opening. They are UL and FM approved for use with NFPA and PHD sway brace components.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
114 views1 page

WAY Race Ittings: Fig. 010 Sway Brace Pipe Attachment

Sway brace fittings are designed to brace pipes against sway and seismic disturbances. They attach to pipes between 1-6 inches in diameter and are braced with 1 or 1 1/4 inch pipes. The fittings are electro-galvanized steel and install by placing over the pipe to brace, adjusting the angle, and inserting the bracing pipe through the opening. They are UL and FM approved for use with NFPA and PHD sway brace components.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

SWAY BRACE FITTINGS

FIRE PROTECTION
SWAY BRACE FITTINGS & SEISMIC CATALOG

FUNCTION: Designed for bracing pipe against sway and seismic disturbance. The pipe
attachment component of a sway brace system used in conjunction with a PHD Fig. 010
Manufacturing structural attachment fitting, and joined together with a bracing SWAY BRACE
pipe element forms a complete sway brace assembly. Sway brace assemblies
are intended to be installed in accordance with NFPA 13 and the manufacturer’s PIPE ATTACHMENT
installation instructions.
SIZE: Pipe size 1" thru 6". Pipe size used for bracing 1" or 1 1⁄4" Schedule 40 IP.
FINISH: Electro-galvanized
MATERIAL: Low Carbon Steel
INSTALL: Place over the pipe to be braced, adjust brace angle, and insert bracing pipe
through opening leaving a minimum of 1" extending from attachment. Brace
pipe can be installed on top or bottom of pipe to be braced but must be a
minimum of 6" away from a pipe joint. Tighten nuts down evenly until hex
heads break off.
APPROVALS: Underwriters Laboratories listed for US and Canada. Factory Mutual approved.
Listed for use with NFPA and PHD sway brace components only
ORDERING: Specify figure number, brace pipe size, and sprinkler pipe size

UL Maximum Design Load FM Maximum Design Load


Weight Ea. Brace Pipes 1” or 1 1/4”
1” (25mm) 1 1/4” (32mm) (GB/T3091, EN10255H, or JISG3454)
Brace Pipe Brace Pipe Pipe Size Brace Angle
Pipe Size SCH 10, 40 From Vertical
SCH 40 lbs. kN lbs. kg lbs. kg & Flow Pipe (Degrees) lbs. kN
*1 (25) 1000 (4.45) 0.71 (0.32) 0.75 (0.34) 30°-44° 340 (1.51)
1 1/4 (32) 1000 (4.45) 0.76 (0.34) 0.79 (0.36) 45°-59° 480 (2.13)
1 (25)
60°-74° 590 (2.62)
1 1/2 (40) 1000 (4.45) 0.79 (0.36) 0.82 (0.37) 75°-90° 660 (2.93)
2 (50) 1000 (4.45) 0.84 (0.38) 0.88 (0.40) 30°-44° 350 (1.55)
2 1/2 (65) 1000 (4.45) 0.90 (0.41) 0.94 (0.43) 45°-59° 500 (2.22)
1 1/4 (32)
60°-74° 610 (2.71)
3 (80) 1000 (4.45) 0.98 (0.44) 1.02 (0.46)
75°-90° 680 (3.02)
4 (100) 1000 (4.45) 1.10 (0.50) 1.14 (0.52) 30°-44° 290 (1.28)
6 (150) 1600 (7.12) N/A N/A 1.40 (0.63) 45°-59° 420 (1.86)
1 1/2 (40)
60°-74° 510 (2.26)
* Restraint only 75°-90° 570 (2.53)
30°-44° 390 (1.73)
45°-59° 550 (2.44)
2 (50)
60°-74° 670 (2.98)
75°-90° 750 (3.33)
30°-44° 440 (1.95)
45°-59° 620 (2.75)
2 1/2 (65)
60°-74° 760 (3.38)
75°-90° 850 (3.78)
30°-44° 470 (2.09)
45°-59° 660 (2.93)
3 (80)
60°-74° 810 (3.33)
75°-90° 910 (4.04)
30°-44° 430 (1.91)
45°-59° 610 (2.71)
4 (100)
60°-74° 750 (3.33)
75°-90° 840 (3.73)
30°-44° 250 (1.11)
45°-59° 350 (1.55)
*6 (150)
60°-74° 430 (1.91)
75°-90° 480 (2.13)
* 1 1/4 brace size only
imensions shown in parentheses are in millimeters.
Unless otherwise specified, all dimensions on drawings and in charts are in inches and dimensions shown in parentheses are in millimeters.

Refer to PHD Manufacturing, Inc.’s full-line catalogs for additional items & technical information
Visit: www.phd-mfg.com • Call: (800) 321-2736 • E-Mail: [email protected] 11