Ecbc Building Envelope PDF
Ecbc Building Envelope PDF
4. Building Envelope
4.1 General
Overview
T he building envelope refers to the exterior façade, and is comprised of opaque components and
fenestration systems. Opaque components include walls, roofs, slabs on grade (in touch with ground),
basement walls, and opaque doors. Fenestration systems include windows, skylights, ventilators, and
doors that are more than one-half glazed. The envelope protects the building’s interior and occupants
from the weather conditions and shields them from other external factors e.g. noise, air pollution, etc.
Example 4.1: R -Value and U-factor Calculations for Cavity Wall Construction
The design of the building envelope is generally the responsibility of an architect. The building designer is
responsible for making sure that the building envelope is energy-efficient and complies with the mandatory and
prescriptive requirements of the Code. ECBC also provides ‘trade-off option’ which allows flexibility to the
designer to ‘trade-off ’ prescriptive requirements of building components, while meeting the minimum energy
performance requirements of the envelope.
Figure 4.6: Heat Transfer (Conduction, Convection, & Radiation) and Infiltration Across a Window
4.2.1.1 U-factors
Clear glass, which is the most common type of glass used today, has no significant thermal resistance (R-value)
from the pane itself. It has a value of R-0.9 to R-1.0 due to the thin films of air on the interior and exterior
surfaces of the glass. The U-factor (thermal conductance), must account for the entire fenestration system
including the effects of the frame, the spacers in double glazed assemblies, and the glazing. There are a wide
variety of materials, systems, and techniques used to manufacture fenestration products, and accurately
accounting for these factors is of utmost importance when meeting the fenestration requirements. The Code
also specifies U-factor for sloped glazing and skylights, and minimum U-factors for unrated products.
ECBC has used W/m2·C as the unit for U-factor. Since differences in temperature are always denoted in K in
physics literature, ECBC User Guide has used W/m2·K as the unit of U-factor. Wherever, °C was being used
for differences in temperature, it has been replaced with K in the Guide.
U-factors for fenestration systems (including the sash and frame) are required to be determined in accordance
with ISO-15099 (as specified in ECBC §11: Appendix C) by an accredited independently laboratory and labeled
and certified by the manufacturer or other responsible party. Box 4-D briefly explains how these issues are
addressed in US.
Box 4-D: How Fenestration Products are Tested, Certified, and Labeled in the U.S.
In the U.S, the fenestration U-factors are determined in accordance with the National Fenestration Rating
Council (NFRC) Standard 100. NFRC is a membership organization of window manufacturers, researchers,
and others that develops, supports, and maintains fenestration rating and labeling procedures. Most fenestration
manufacturers have their products rated and labeled through the NFRC program. Certified products receive
an 8 ½ by 11 inch NFRC label that lists the U-factor, SHGC, and the visible transmittance.
ECBC identifies several areas in the building envelope where attention should be paid to infiltration control.
These include:
a. Joints around fenestration and doorframes.
b. Openings at penetrations of utility services through roofs, walls, and floors.
c. Site-built fenestration and doors.
d. Building assemblies used as ducts or plenums.
e. Joints, seams, and penetrations of vapor retarders.
f. All other openings in the building envelope.
It is also recommended that junctions between walls and foundations, between walls at building corners, between
walls and structural floors or roofs, and between walls and roof or wall panels.
Fenestration products, including doors, can also significantly contribute to infiltration. Although not included in
the Code, it is recommended that fenestration products should have infiltration less than 0.4 cfm/ft² (2.0 l/s·m²).
For glazed entrance doors that open with a swinging mechanism and for revolving doors, it is recommended
that infiltration be limited to 1.0 cfm/ft² (5.0 l/s·m²).
If designing a cool roof, requirements for minimum solar reflectance and initial emittance levels are specified
[ECBC 4.3.1.1].
Roofs with slopes less than 20° shall have an initial solar reflectance of no less than 0.70 and an initial emittance
no less than 0.75. Solar reflectance shall be determined in accordance with ASTM E903-96 and emittance shall
be determined in accordance with ASTM E408-71 (RA 1996).
Climate Zone Hospitals, Hotels, Call Centers Other Building Types (Daytime)
(24-Hour)
Maximum U-factor of Minimum R-value Maximum U-factor Minimum R-value
the overall assembly of insulation alone of the overall of insulation alone
(W/m2·K) (m2·K/W) assembly (W/m2·K) (m2·K/W)
Composite U-0.440 R-2.10 U-0.440 R-2.10
Hot and Dry U-0.440 R-2.10 U-0.440 R-2.10
Warm and Humid U-0.440 R-2.10 U-0.440 R-2.10
Moderate U-0.440 R-2.10 U-0.440 R-2.10
Cold U-0.369 R-2.20 U-0.352 R-2.35
For unrated windows, follow the values given in Table 4.7 (Table 11.1 of Appendix C of ECBC).
Table 4.7: Defaults for Unrated Vertical Fenestration (Overall Assembly including Sash and
Frame) - Table 11.1 of ECBC
Frame Type Glazing Type Clear Glass Tinted Glass
U-factor SHGC VLT U-Factor SHGC VLT
(W/m2· K) (W/m2· K)
All frame types Single Glazing 7.1 0.82 0.76 7.1 0.70 0.58
Wood, vinyl, or fiberglass frame Double Glazing 3.3 0.59 0.64 3.4 0.42 0.39
Metal and other frame type Double Glazing 5.1 0.68 0.66 5.1 0.50 0.40
Exception to ECBC §4.3.3: The SHGC requirement of a fenestration can be affected by overhangs on a
building, which reduce solar gains. ECBC uses a term called a projection factor to determine how well an
overhang shades the building’s glazing. The projection factor is calculated by measuring the distance from the
window to the farthest edge of the overhang and dividing that by the distance from the bottom of the window
to the lowest point of the overhang demonstrates how to calculate a projection factor.
Projection Factor = H (horizontal)/V (vertical)
ECBC provides a modified SHGC requirement where there are overhangs and/or side fins, which are a
permanent part of the building. This may be applied in determining the SHGC for the Proposed Design. An
adjusted SHGC, accounting for overhangs and/or sidefins, is calculated by multiplying the SHGC of the
unshaded fenestration product by a multiplication (M) factor. If this exception is applied, a separate M Factor
shall be determined for each orientation and unique shading condition.
• PF= Ratio of overhang projection divided by height from window sill to bottom
of overhang (must be permanent)
4.3.4 Skylights
A skylight is a fenestration surface having a slope of less than 60 degrees from the horizontal plane. Other
fenestration, even if mounted on the roof of a building, is considered vertical fenestration.
Skylights can be installed into a roof system either flush-mounted or curb-mounted (including site built). In
order to create a positive water flow around them, skylights are often mounted on “curbs” set above the roof
plane. However, these curbs, rising 6 to 12 inches (15 to 30 centimeters) above the roof, create additional heat
loss surfaces right where the warmest air of the building tends to collect. Portions of roof that serve as curbs
that mount the skylight above the level of the roof (See below) are part of the opaque building envelope.
SRR: Skylight roof ratio which is the ratio of the total skylight area of the roof, measured to the outside of
the frame, to the gross exterior roof. See §11.2.2 for typical complying skylight constructions.