The PCS-902S line distance relay provides comprehensive protection and control functions for transmission lines, including six zones of phase and ground distance protection, pilot protection, overcurrent protection, undercurrent protection, voltage protection, negative sequence protection, and monitoring functions like fault location and event recording. It supports applications for overhead lines and cables, with flexible settings, half-wave algorithm for distance protection, and communication via fiber channels.

Uploaded by

Kelly chat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
46 views2 pages

1557275886464lh4el Nari Dis Prot 2

The PCS-902S line distance relay provides comprehensive protection and control functions for transmission lines, including six zones of phase and ground distance protection, pilot protection, overcurrent protection, undercurrent protection, voltage protection, negative sequence protection, and monitoring functions like fault location and event recording. It supports applications for overhead lines and cables, with flexible settings, half-wave algorithm for distance protection, and communication via fiber channels.

Uploaded by

Kelly chat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

www.nrec.

com/en

PCS-902S Line Distance Relay operation element. The phase selection is automatically
resulted according to the reliability of phase selector, so
that to avoid probable mistaken multi-phase selection
by adopting overreaching phase selector.

• Special overcurrent element of breaker failure protection, its


dropoff time is no more than 15ms.

• The overcurrent protection is combined with harmonic blocking


and cold load starting logic, which can prevent from
m a l - o p e r a t i o n a ff e c t e d b y i m p u l s e c u r r e n t w h i l e t h e
transformer is initiated on no-load.

PCS-902S line distance relay integrates main and back-up • Selectable IEC, ANSI inverse-time characteristic curves, also
protection functions, which is designed for overhead line, the curve can be defined by users and the inverse-time dropoff
cables and hybrid transmission lines of various voltage curve selection is supported.
levels and provides comprehensive protection and control
• Support single-ended impedance-based fault location, mutual
solutions. With its flexibility and the powerful PCS-Studio
compensation for parallel lines arrangement is also available.
configuration tool, PCS-902S offers future-oriented system
solutions with high investment security and low operating • Both dedicated fiber channel and multiplexing fiber channel
costs. are supported, and single mode and multi-mode channel
combination operation mode is enable. Communication rate
supports 64kbit/s and 2Mbit/s, and communication protocol
supports C37.94 and G.703.

Functions
Protection and Control

• Six zone phase-to-phase distance protection (21Q/21M)

Mho or quadrilateral characteristic, directional, load


encroachment, power swing blocking releasing and unique
low-voltage elements are provided for phase-to-phase
distance protection.

• Six zone phase-to-ground distance protection (21Q/21M)

Mho or quadrilateral characteristic, reactance characteristic,


Features directional, load encroachment, power swing blocking
releasing and unique low-voltage elements are provided for
• Two-terminal transmission line application, including overhead
phase-to-ground distance protection.
line and cable
• Pilot distance protection (85)
• Distance Protection
one of selectable six zone for pilot scheme, such as PUTT,
° Distance protection adopted the half-wave algorithm is
POTT, Blocking, Unblocking, DTT & Zone Extension. The
also supported, and its typical operation time is 12-15ms.
scheme integrates current reversal logic, weak-infeed echo
° zones distance protection, independent zero-sequence and open breaker echo.
compensation factor for each zone, the phase-to-ground and
• Pilot directional earth-fault protection (85)
phase-to-phase characteristic of distance protection can be
set independently. Directional zero-sequence comparison element for pilot
scheme, such as PTT, Blocking and Unblocking. The scheme
° The unique power swing blocking releasing logic and integrates current reversal logic, weak-infeed echo and open
can properly supervise distance protection during power
breaker echo.
swing, which ensures distance protection to operate
correctly for internal faults during power swing, and • Six stages phase overcurrent protection (67P, 50/51P)
prevents distance protection from mal-operation during
Selectable time characteristics (definite-time or inverse-time)
power swing.
and directional elements (forward, reverse or non-directional)
• Unique phase selector has the same protection zone as are provided. A harmonic blocking function is integrated to

10
PCS S Series
restrain each stage independently. • Synchrocheck (25)

• Six stages earth-fault protection (67G, 50/51G) Synchrocheck can be used for auto-reclosing and manual
c l o s i n g f o r s i n g l e - b r e a k e r a n d d u a l - b r e a k e r. T h e
Selectable time characteristics (definite-time or synchronism check function compensates for breaker
inverse-time) and directional elements (forward, reverse or close time, frequency, magnitude, and angle differences
non-directional) are provided. A harmonic blocking function between the two voltage sources used for synchronism.
is integrated to restrain each stage independently.
• Voltage and current drift auto adjustment
• Four stages negative-sequence overcurrent protection (67Q,
50/51Q) The relay continually and automatically traces the voltage and
current drifts and adjusts the zero point to acquire accurate
Selectable time characteristics (definite-time or measurements.
inverse-time) and directional elements (forward, reverse or
non-directional) are provided. Stage 3 can be selected as • Single-ended impedance-based fault location
alarm purpose.

• One stage undercurrent protection (37) Monitoring and Measurement


• Four stages undervoltage protection (27P) • Energy measurement (active and reactive energies for import
and export)
Time characteristics is selectable between definite-time
and inverse-time. Phase voltage or phase-to-phase • CT circuit failure supervision
voltage can be selected for protection calculation.
• VT circuit failure supervision
“1-out-of-3” or “3-out-of-3” logic can be selected for
protection criterion. • Fault phase selection

• Four stages overvoltage protection (59P) • Fault Locator with parallel-line compensation

Time characteristics is selectable between definite-time and • Self diagnostic


inverse-time. Phase voltage or phase-to-phase voltage can be
• Event recorder including 1024 change-of-binary-input events,
selected for protection calculation. “1-out-of-3” or “3-out-of-3”
1024 supervision events, 256 control logs and 1024 device logs
logic can be selected for protection criterion.
• Disturbance recorder including 32 disturbance records with
• Four stages negative-sequence overvoltage protection (59Q)
waveforms (The format is compatible with COMTRADE.)
• Four stages zero-sequence overvoltage protection (59G)
• Pilot communication channel supervision
• Switch-onto-fault (SOTF) logic
• System frequency supervision
Switch-onto-fault logic is used to acceleratedly clear the faults
• Clock synchronization using IRIG-B, SNTP, PPS (Pulse-Per-
during manual closing and auto-reclosing based on distance
Second) and PPM (Pulse-Per-Minute) , IEEE1588
element or overcurrent element (phase current and residual
current).

• Unique power swing blocking releasing logic (PSBR) Communication

The power swing blocking releasing logic prevents • Optional single- or dual- pilot channels (fiber optic)
mal-operations during external faults in power swing
• Support G.703 and C37.94
situations. It quickly clears the internal faults in power swing
scenarios. • Up to four 10Base-T/100Base-TX copper Ethernet ports
using IEC 61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
• Auto-reclosing (79)
• Up to four 100Base-FX optical Ethernet ports using IEC
Single-/Three-pole reclosing mode is provided. Up to four-shot
61850, DNP3.0 or IEC 60870-5-103 over TCP/IP
breaker auto-reclosing with synchronism and voltage check
logic. • Two RS-485 serial ports using IEC 60870-5-103

• Remote/local control • One RS-485 serial port for clock synchronization

The control of circuit breaker, disconnector and earth switch • Support GOOSE communication module using IEC 61850-8-1
can be implemented via communication, LCD menu and binary GOOSE
inputs. User programmable interlocking logics are available by • Full compatibility between IEC 61850 Editions 1 and 2
PCS-Studio.
• Redundancy protocols PRP and HSR

• One front RJ-45 port for debugging