Installation Manual - TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter
Installation Manual - TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter
• Risk of electric shock, do not remove cover, disassemble, or repair, no user serviceable
parts inside. Refer servicing to qualified service personnel.
• Before installing or using the Tigo System, please read all instructions and warning
markings on the Tigo products, appropriate sections of your inverter manual,
photovoltaic (PV) module installation manual, and other available safety guides.
• Failure to adhere to these instructions may result in injury or death, damage to the
system or voiding the factory warranty.
• To reduce risk of fire and shock hazard, install this device with strict adherence to
National Electric Code (NEC) ANSI/NFPA 70 and/or local electrical codes. When the
photovoltaic array is exposed to light, it supplies a DC voltage to the Tigo TS4 units. The
TS4 units start in the “ON” state and their output voltage may be as high as the PV
module open circuit voltage (VOC) when connected to the module. The installer
should use the same caution when handling electrical cables from a PV module with or
without the TS4 units attached.
• Installation must be performed by trained professionals only. Tigo does not assume
liability for loss or damage resulting from improper handling, installation, or misuse of
products.
• Remove all metallic jewelry prior to installing the Tigo TS4 units to reduce the risk of
contacting live circuitry. Do not attempt to install in inclement weather.
• Do not operate the Tigo TS4 units if they have been physically damaged. Check existing
cables and connectors, ensuring they are in good condition and appropriate in rating.
Do not operate Tigo TS4 units with damaged or substandard wiring or connectors. Tigo
TS4 units must be mounted on the high end of the PV module backsheet or racking
system, and in any case above ground.
• Do not connect or disconnect under load. Turning off the Inverter and/or the Tigo
products may not reduce this risk. Internal capacitors within the inverter can remain
charged for several minutes after disconnecting all power sources. Verify capacitors
have discharged by measuring voltage across inverter terminals prior to disconnecting
wiring if service is required. Wait 30 seconds after rapid shutdown activation before
disconnecting DC cables or turning off DC disconnect.
• Always assume TS4 units are in “ON” state, or may turn on when restarting.
The transmitter control power supply MUST be on the same AC branch circuit
as the inverter to meet rapid shutdown requirements.
01/24/2020 2
TABLE OF CONTENTS
Technical Specifications –
TS4-F / TS4-R-F 24
3
TS4-F RAPID SHUTDOWN SYSTEM
Transmitter:
RSS Transmitter
• Rapid Shutdown System Transmitter for
rapid shutdown activation of TS4-F, TS4-R-F,
or TS4-A-F units
• The external device that provides a keep-
alive signal to the TS4-F via Power Line
Communication
4
TS4 FIRE SAFETY PRODUCTS
Module-Integrated:
TS4-F
• Module electronics are contained in the
junction box, installed at the PV module
factory.
• Connected in series like regular modules
• No additional wiring connections to make
Add-on:
TS4-R-F, TS4-A-F
• Bracket clips to module frame without tools
• TS4-R-F or TS4-A-F outputs are connected in
series to form a string
• No additional grounding required
5
SYSTEM OVERVIEW: TS4-F
1 2 3
Rapid
Shutdown
System
Transmitter
The TS4-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for
operation.
The Tigo RSS Transmitter is installed in line with a solar PV inverter, as shown, and
can be installed inside the inverter or external to it.
Method of Operation
All TS4-F units start in the OFF position and measure 0.6V at the output. When
power is supplied to the RSS Transmitter, the TS4-F units turn ON and allow full
PV module voltage.
The units constantly receive a “keep-alive” signal from the transmitter over
PLC. When power to the transmitter is cut, this keep-alive signal ceases,
sending every TS4-F into shutdown mode with output reduced to 0.6V.
6
SYSTEM OVERVIEW: TS4-R-F
1 2 3
TS4-R-F
4 - 123A
Rapid
Shutdown
System
Transmitter
7
SYSTEM OVERVIEW: TS4-A-F
1 2 3
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218
Rapid
Shutdown
System
Transmitter
1 2 3
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218
Rapid
Shutdown
System
Transmitter
• TS4-F, TS4-R-F, and TS4-A-F are shipped in the OFF position and will
measure 0.6V at the output when the keep-alive signal is not
present.
• Failing to follow the sequence of installation steps may result in TS4
damage not covered under warranty.
• Connect all TS4-R-F or TS4-A-F units to their respective modules
before connecting their outputs in series.
• Install all TS4-F, TS4-R-F, or TS4-A-F/TS4-A-2F units before powering
on the RSS Transmitter.
• Never apply an external voltage source to a module or string
equipped with TS4-F, TS4-R-F, or TS4-A-F/TS4-A-2F units.
• If parallel string connections are needed, first connect the TS4-F, TS4-R-F,
or TS4-A-F to the PV modules, then connect all TS4-F, TS4-R-F, or TS4-A-F
outputs in series, and finally pass one side (+ or -) of the homeruns
through the PLC transmitter to turn the system ON.
Smart modules with an integrated TS4 Junction box are installed and
connected in series just like standard PV modules.
1 TS4-F TS4-F
4 - 123A 4 - 123A
2
TS4-F TS4-F
4 - 123A 4 - 123A
1 2
TS4-R-F TS4-R-F
4 - 123A 4 - 123A
3 TS4-R-F
4 - 123A
TS4-R-F
4 - 123A
1 2
Tigo Rapid Shutdown Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218 NEC 690.12-2017 and C22.1-2015 Rule 64.218
3 TS4-A-F
4 - 123A
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218
DO NOT DISCONNECT
UNDER LOAD
TS4-A-F
4 - 123A
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218
DO NOT DISCONNECT
UNDER LOAD
1 TS4-A-2F
4 - 123A
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218
DO NOT DISCONNECT
UNDER LOAD
- + - +
PV Module 1 PV Module 2
1. Connect PV modules to TS4-A-2F inputs
2
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218
- + - +
PV Module 1 PV Module 2
2. Connect TS4-A-2F outputs in series
LOCK OUT 1 2
+ -
LED (Signal)
* for conduit
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
LOCK OUT + -
AC Wires for
Power Supply
Homerun
Only (+) or (-)
through RSS Core
LOCK OUT + -
Conduit Ground
LOCK OUT 1 2
+ -
*
LED (Signal)
RSS Core inputs
4
* 3 *
1 DIN Rail PSU
2 RSS Transmitter
* for conduit
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
LOCK OUT + -
AC Wires for
Power Supply
Homerun
Only (+) or (-)
through RSS Core
Homerun
LOCK OUT + -
Conduit Ground
-V +V
+ V ADJ
1 2
+ -
Rapid
Shutdown
System
L N
Transmitter
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.
Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter
or AC disconnect if not at same location.
RSS TRANSMITTER COMMERCIAL WIRING
-V +V
+ V ADJ
+ -
Rapid
Shutdown
System
L N
Transmitter
G L2 L1
Homerun
Only (+) or (-)
through RSS Core
Homerun
Only (+) or (-)
through RSS Core
Output
Specify system voltage when ordering (1000V / 1500V) for appropriate cables
& connectors.
Cabling
Type H1Z2Z2-K
25
TECHNICAL SPECIFICATIONS – TS4-A-F
Mechanical
Weight 490g
Electrical
139.7
120±10
1200±10
Specify system voltage when ordering (1000V / 1500V) for appropriate cables
& connectors.
Mechanical
Weight 590g
Electrical
15.6
139.7
120±10
200±10
1800±10
Specify system voltage when ordering (1000V / 1500V) for appropriate cables
& connectors.
Input Current 1A
RSS Core
Environmental
38 41.3
610
18 AWG
38.5
90.9
Rapid
Shutdown
System
Transmitter
73 max
25.0 min
RSS Transmitter - Front View RSS Transmitter - Side View RSS Core - Side View
Input Current 1A
RSS Core
Environmental
38 41.3
610
18 AWG
38.5
90.9
Rapid
Shutdown
System
Transmitter
73 max
25.0 min
RSS Transmitter - Front View RSS Transmitter - Side View RSS Core - Side View
Input Current 1A
RSS Core
Environmental
110 17
0
38 41.3 610
18 AWG
+ -
Rapid
38.5
Shutdown
System
L N Transmitter
90.9
270
Rapid
Shutdown
System
Transmitter
max
73
25.0 min
TS4-F (or TS4-R-F, TS4-A-F, TS4-A-2F) and an RSS Transmitter are a solution
to meet NEC 2014 & 2017 690.12 Rapid Shutdown requirements.
Test your rapid shutdown system by switching off the AC power to the
RSS Transmitter or inverter with built-in transmitter.
TS4-F, TS4-R-F, and TS4-A-F units will reduce their output to 0.6V when
the Transmitter is powered off.
The RSS Transmitter control power supply MUST be on the same AC branch
circuit as the inverter to meet rapid shutdown requirements.
41.6 41.6
68 41.6
108
41.6
40 40
2X Ø 28 Ø 28 3X Ø 28 2X Ø 28
41.6
41.6
41.6
52.3
104.5
41.6
52.3 52.3
2X Ø 35 Ø 35 3X Ø 35 2X Ø 35
*all dimensions in mm
MISCELLANEOUS
33
INSTALLATION COMPLETE
Problems?
TS4-F Troubleshooting Guide