Installation Manual - TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter

This document provides installation instructions for Tigo rapid shutdown products including the TS4-F, TS4-R-F, TS4-A-F, TS4-A-2F, and RSS Transmitter. It contains important safety instructions and warns that lethal voltage may be present. Installation must only be performed by trained professionals and in accordance with relevant electrical codes. The document provides overview diagrams of the system configurations and specifications for each product.

Uploaded by

Dominic Santiago
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
338 views

Installation Manual - TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter

This document provides installation instructions for Tigo rapid shutdown products including the TS4-F, TS4-R-F, TS4-A-F, TS4-A-2F, and RSS Transmitter. It contains important safety instructions and warns that lethal voltage may be present. Installation must only be performed by trained professionals and in accordance with relevant electrical codes. The document provides overview diagrams of the system configurations and specifications for each product.

Uploaded by

Dominic Santiago
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 34

Installation Manual

TS4-F, TS4-R-F, TS4-A-F, TS4-A-2F and


RSS Transmitter
IMPORTANT SAFETY INSTRUCTIONS

LETHAL VOLTAGE MAY BE PRESENT IN ANY PV INSTALLATION


SAVE THESE INSTRUCTIONS
• This manual contains important instructions for installation and maintenance of the Tigo
product models TS4-F, TS4-R-F, TS4-A-F, TS4-A-2F, and the RSS Transmitter.

• Risk of electric shock, do not remove cover, disassemble, or repair, no user serviceable
parts inside. Refer servicing to qualified service personnel.

• Before installing or using the Tigo System, please read all instructions and warning
markings on the Tigo products, appropriate sections of your inverter manual,
photovoltaic (PV) module installation manual, and other available safety guides.

• Failure to adhere to these instructions may result in injury or death, damage to the
system or voiding the factory warranty.

• To reduce risk of fire and shock hazard, install this device with strict adherence to
National Electric Code (NEC) ANSI/NFPA 70 and/or local electrical codes. When the
photovoltaic array is exposed to light, it supplies a DC voltage to the Tigo TS4 units. The
TS4 units start in the “ON” state and their output voltage may be as high as the PV
module open circuit voltage (VOC) when connected to the module. The installer
should use the same caution when handling electrical cables from a PV module with or
without the TS4 units attached.

• Installation must be performed by trained professionals only. Tigo does not assume
liability for loss or damage resulting from improper handling, installation, or misuse of
products.

• Remove all metallic jewelry prior to installing the Tigo TS4 units to reduce the risk of
contacting live circuitry. Do not attempt to install in inclement weather.

• Do not operate the Tigo TS4 units if they have been physically damaged. Check existing
cables and connectors, ensuring they are in good condition and appropriate in rating.
Do not operate Tigo TS4 units with damaged or substandard wiring or connectors. Tigo
TS4 units must be mounted on the high end of the PV module backsheet or racking
system, and in any case above ground.

• Do not connect or disconnect under load. Turning off the Inverter and/or the Tigo
products may not reduce this risk. Internal capacitors within the inverter can remain
charged for several minutes after disconnecting all power sources. Verify capacitors
have discharged by measuring voltage across inverter terminals prior to disconnecting
wiring if service is required. Wait 30 seconds after rapid shutdown activation before
disconnecting DC cables or turning off DC disconnect.

• Always assume TS4 units are in “ON” state, or may turn on when restarting.

The transmitter control power supply MUST be on the same AC branch circuit
as the inverter to meet rapid shutdown requirements.

01/24/2020 2
TABLE OF CONTENTS

TS4-F Rapid Shutdown System 4 Mechanical Specifications –


TS4-F / TS4-R-F 25
TS4 Fire Safety Products 5
Technical Specifications – TS4-A-F 26
System Overview: TS4-F 6
Technical Specifications – TS4-A-2F 27
System Overview: TS4-R-F 7
Technical Specifications –
System Overview: TS4-A-F 8 RSS Transmitter 28

System Overview: TS4-A-2F 9 Technical Specifications –


RSS Transmitter Commercial Kit 29
Installation Notes 10
Technical Specifications –
TS4-F Installation 11 RSS Transmitter Outdoor Kit 30

TS4-R-F Installation 12 Testing Rapid Shutdown 31

TS4-A-F Installation 13 Conduit Drilling Guide 32

TS4-A-2F Installation 14 Miscellaneous 33

RSS Transmitter Installation – Installation Complete 34


Single RSS Core 15

RSS Transmitter Wiring –


Single RSS Core 16

RSS Transmitter Grounding –


Single RSS Core 17

RSS Transmitter Installation –


Dual RSS Core 18

RSS Transmitter Wiring –


Dual RSS Core 19

RSS Transmitter Grounding –


Dual RSS Core 20

RSS Transmitter Commercial Installation 21

RSS Transmitter Commercial Wiring 22

Technical Specifications –
TS4-F / TS4-R-F 24

3
TS4-F RAPID SHUTDOWN SYSTEM

Module-Level Power Electronics:

TS4-F, TS4-R-F, TS4-A-F


• NEC 2017 690.12 Rapid shutdown
compliant
• Module-level deactivation
• PLC communication
• Plug & play, no configuration required

Transmitter:

RSS Transmitter
• Rapid Shutdown System Transmitter for
rapid shutdown activation of TS4-F, TS4-R-F,
or TS4-A-F units
• The external device that provides a keep-
alive signal to the TS4-F via Power Line
Communication

4
TS4 FIRE SAFETY PRODUCTS

Module-Integrated:

TS4-F
• Module electronics are contained in the
junction box, installed at the PV module
factory.
• Connected in series like regular modules
• No additional wiring connections to make

Add-on:

TS4-R-F, TS4-A-F
• Bracket clips to module frame without tools
• TS4-R-F or TS4-A-F outputs are connected in
series to form a string
• No additional grounding required

5
SYSTEM OVERVIEW: TS4-F

1 2 3
Rapid
Shutdown
System
Transmitter

1. Modules with integrated TS4-F


2. RSS Transmitter and RSS Core
3. Inverter

The TS4-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for
operation.
The Tigo RSS Transmitter is installed in line with a solar PV inverter, as shown, and
can be installed inside the inverter or external to it.

Method of Operation
All TS4-F units start in the OFF position and measure 0.6V at the output. When
power is supplied to the RSS Transmitter, the TS4-F units turn ON and allow full
PV module voltage.
The units constantly receive a “keep-alive” signal from the transmitter over
PLC. When power to the transmitter is cut, this keep-alive signal ceases,
sending every TS4-F into shutdown mode with output reduced to 0.6V.

6
SYSTEM OVERVIEW: TS4-R-F

1 2 3
TS4-R-F
4 - 123A

Rapid
Shutdown
System
Transmitter

1. Modules with TS4-R-F add-on


2. RSS Transmitter and RSS Core
3. Inverter

Note: connect modules to TS4-R inputs before connecting outputs


The TS4-R-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for
operation.

• TS4-R-F mounting is recommended on the upper right as shown, but can be


placed elsewhere on the frame or bolted to the racking if needed.
• TS4-R-F cable glands must not be facing up.
• Allow clearance between PV module and mounting surface for air
circulation around TS4-R-F.
• Do not drill additional mounting holes in the frame or metal bracket.

7
SYSTEM OVERVIEW: TS4-A-F

1 2 3
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218

TS4-A-F DO NOT DISCONNECT


UNDER LOAD
4 - 123A

Rapid
Shutdown
System
Transmitter

1. Modules with TS4-A-F add-on


2. RSS Transmitter and RSS Core
3. Inverter

Note: connect modules to TS4-A inputs before connecting outputs


The TS4-A-F requires a Tigo RSS Transmitter or inverter with built-in transmitter for
operation.

• TS4-A-F mounting is recommended on the upper right as shown, but can be


placed elsewhere on the frame or bolted to the racking if needed.
• TS4-A-F cable glands must not be facing up.
• Allow clearance between PV module and mounting surface for air
circulation around TS4-A-F.
• For installation on frameless modules, remove metal clips and bolt TS4-A to
rail. Do not drill additional mounting holes in the frame or metal bracket.
8
SYSTEM OVERVIEW: TS4-A-2F

1 2 3
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218

TS4-A-2F DO NOT DISCONNECT


UNDER LOAD
4 - 123A

Rapid
Shutdown
System
Transmitter

1. Modules with TS4-A-2F add-on


2. RSS Transmitter and RSS Core
3. Inverter

Note: connect modules to TS4-A inputs before connecting outputs


The TS4-A-2F requires a Tigo RSS Transmitter or inverter with built-in transmitter
for operation.

• TS4-A-F mounting is recommended on the upper right as shown, but can be


placed elsewhere on the frame or bolted to the racking if needed.
• TS4-A-F cable glands must not be facing up.
• Allow clearance between PV module and mounting surface for air
circulation around TS4-A-F.
• For installation on frameless modules, remove metal clips and bolt TS4-A to
rail. Do not drill additional mounting holes in the frame or metal bracket.
9
INSTALLATION NOTES

• TS4-F, TS4-R-F, and TS4-A-F are shipped in the OFF position and will
measure 0.6V at the output when the keep-alive signal is not
present.
• Failing to follow the sequence of installation steps may result in TS4
damage not covered under warranty.
• Connect all TS4-R-F or TS4-A-F units to their respective modules
before connecting their outputs in series.
• Install all TS4-F, TS4-R-F, or TS4-A-F/TS4-A-2F units before powering
on the RSS Transmitter.
• Never apply an external voltage source to a module or string
equipped with TS4-F, TS4-R-F, or TS4-A-F/TS4-A-2F units.
• If parallel string connections are needed, first connect the TS4-F, TS4-R-F,
or TS4-A-F to the PV modules, then connect all TS4-F, TS4-R-F, or TS4-A-F
outputs in series, and finally pass one side (+ or -) of the homeruns
through the PLC transmitter to turn the system ON.

• If connecting TS4-A-2F to a single PV module:


• Connect PV module to Input 1, connect Input 2 cables together

• Place rapid shutdown system label no more than 1m (3ft) from


initiator (AC disconnect) or service panel containing means of
disconnection if not at same location.

Place safety labels in proper location


10
TS4-F INSTALLATION

Smart modules with an integrated TS4 Junction box are installed and
connected in series just like standard PV modules.

Connect modules with TS4-F in series before powering on the


RSS Transmitter.

1 TS4-F TS4-F
4 - 123A 4 - 123A

2
TS4-F TS4-F
4 - 123A 4 - 123A

RSS Transmitter must be powered OFF during TS4-F installation. 11


TS4-R-F INSTALLATION

Standard modules can be equipped with TS4-R-F add-on units as


shown below.

Always connect modules to TS4-R inputs before connecting outputs.

Each TS4-R-F must have a PV module connected to its input before


connecting the outputs of TS4-R-F units in series.

To disconnect TS4-R-F from a module, disconnect the TS4-R-F outputs


from the string before disconnecting the TS4-R-F inputs from the
module junction box.

1 2
TS4-R-F TS4-R-F
4 - 123A 4 - 123A

3 TS4-R-F
4 - 123A
TS4-R-F
4 - 123A

RSS Transmitter must be powered OFF during TS4-R-F installation. 12


TS4-A-F INSTALLATION

Standard modules can be equipped with TS4-A-F add-on units as


shown below.

Always connect modules to TS4-A inputs before connecting outputs.

Each TS4-A-F must have a PV module connected to its input before


connecting the outputs of TS4-A-F units in series.

To disconnect TS4-A-F from a module, disconnect the TS4-A-F outputs


from the string before disconnecting the TS4-A-F inputs from the
module junction box.

1 2
Tigo Rapid Shutdown Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218 NEC 690.12-2017 and C22.1-2015 Rule 64.218

TS4-A-F DO NOT DISCONNECT


UNDER LOAD
TS4-A-F DO NOT DISCONNECT
UNDER LOAD
4 - 123A 4 - 123A

3 TS4-A-F
4 - 123A
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218

DO NOT DISCONNECT
UNDER LOAD
TS4-A-F
4 - 123A
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218

DO NOT DISCONNECT
UNDER LOAD

RSS Transmitter must be powered OFF during TS4-A-F installation. 13


TS4-A-2F INSTALLATION

Standard modules can be equipped with TS4-A-2F add-on units as


shown below.

Always connect modules to TS4-A inputs before connecting outputs.

Each TS4-A-2F must have a PV module connected to its inputs


before connecting the outputs of TS4-A-2F units in series.

To disconnect TS4-A-2F from a module, disconnect the TS4-A-2F


outputs from the string before disconnecting the TS4-A-2F inputs from
the module junction box.
If connecting 2F to a single PV module:
• Connect PV module to Input 1
• Connect Input 2 cables together

1 TS4-A-2F
4 - 123A
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218

DO NOT DISCONNECT
UNDER LOAD

- + - +

PV Module 1 PV Module 2
1. Connect PV modules to TS4-A-2F inputs

2
Tigo Rapid Shutdown
NEC 690.12-2017 and C22.1-2015 Rule 64.218

TS4-A-2F DO NOT DISCONNECT


UNDER LOAD
4 - 123A

- + - +

PV Module 1 PV Module 2
2. Connect TS4-A-2F outputs in series

RSS Transmitter must be powered OFF during TS4-A-2F installation. 14


RSS TRANSMITTER INSTALLATION –
SINGLE RSS CORE
AC LED (Power)
85-264V PSU +VIN
GND

LOCK OUT 1 2
+ -

TAG OUT Rapid


Shutdown
System
L N Transmitter

LED (Signal)

* RSS Core inputs

1 DIN Rail PSU * *


2 RSS Transmitter

3 RSS Core (CT) Suggested locations

* for conduit
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.

Note: Install TS4-F before powering on RSS Transmitter


· Drill holes in enclosure for conduit (see drilling guide for placement)
· Mount RSS Transmitter and power supply on DIN rail
· Connect DC leads from power supply (1) 1 to transmitter (2) 2
· Connect RSS Core (3) 3 to transmitter
Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter
or AC disconnect if not at same location.
RSS TRANSMITTER WIRING –
SINGLE RSS CORE

LOCK OUT + -

TAG OUT Rapid


Shutdown
System
L N Transmitter

AC Wires for
Power Supply

Homerun
Only (+) or (-)
through RSS Core

Note: Install TS4-F before powering on RSS Transmitter


· Pass either positive or negative homerun through RSS Core
· Connect wires to AC side of power supply

Max number of strings per RSS Core: 10


Max string length: 30 modules
Max current per RSS Core: 100A
Max cable length from inverter (+) to inverter (-): 1000ft (300m)
RSS TRANSMITTER GROUNDING –
SINGLE RSS CORE
DC Ground

LOCK OUT + -

TAG OUT Rapid


Shutdown
System
AC Ground L N Transmitter

Conduit Ground

Note: Install TS4-F before powering on RSS Transmitter


· Connect AC and DC ground wires to DIN rail
· Ground all conduit connections
· Turn on AC power to Transmitter power supply to activate
keep-alive signal and energize PV array
Warning: nonmetallic enclosure does not provide bonding between
conduit connections. Use grounding type bushings and jumper wires.
RSS TRANSMITTER INSTALLATION –
DUAL RSS CORE
LED (Power)
+VIN
GND

LOCK OUT 1 2
+ -

TAG OUT Rapid


Shutdown
System
L N Transmitter

RSS Core inputs

*
LED (Signal)
RSS Core inputs
4

* 3 *
1 DIN Rail PSU

2 RSS Transmitter

3 RSS Core (CT)


* *
4 RSS Core (CT) Suggested locations

* for conduit
Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.

Note: Install TS4-F before powering on RSS Transmitter


· Drill holes in enclosure for conduit (see drilling guide for placement)
· Mount RSS Transmitter and power supply on DIN rail
· Connect DC leads from power supply (1) 1 to transmitter (2) 2
· Connect RSS Core (3) 3 and (4)4 to transmitter
Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter
or AC disconnect if not at same location.
RSS TRANSMITTER WIRING –
DUAL RSS CORE

LOCK OUT + -

TAG OUT Rapid


Shutdown
System
L N Transmitter

AC Wires for
Power Supply

Homerun
Only (+) or (-)
through RSS Core

Homerun

Note: Install TS4-F before powering on RSS Transmitter


· Pass either positive or negative homerun through RSS Cores
· Connect wires to AC side of power supply

Max number of strings per RSS Core: 10


Max string length: 30 modules
Max current per RSS Core: 100A
Max cable length from inverter (+) to inverter (-): 1000ft (300m)
RSS TRANSMITTER GROUNDING –
DUAL RSS CORE
DC Ground

LOCK OUT + -

TAG OUT Rapid


Shutdown
System
AC Ground L N Transmitter

Conduit Ground

Note: Install TS4-F before powering on RSS Transmitter


· Connect AC and DC ground wires to DIN rail
· Ground all conduit connections
· Turn on AC power to Transmitter power supply to activate
keep-alive signal
Warning: nonmetallic enclosure does not provide bonding between
conduit connections. Use grounding type bushings and jumper wires.
RSS TRANSMITTER COMMERCIAL INSTALLATION

200-500VAC Power Supply LED (Power)


+VIN
+12VDC
GND
-12VDC

-V +V

+ V ADJ
1 2
+ -

Rapid
Shutdown
System
L N
Transmitter

RSS Core inputs


G L2 L1 LED (Signal)
RSS Core inputs
Ground
Neutral 4
Line

1 DIN Rail PSU


3
2 RSS Transmitter

3 RSS Core (CT)


4 RSS Core (CT)

Transmitter power supply must be on same AC branch circuit as inverter to meet rapid shutdown requirements.

Note: Install TS4-F before powering on RSS Transmitter


· Mount RSS Transmitter and power supply on DIN rail
· Connect DC leads from power supply (1)
1 to transmitter (2)
2
· Connect RSS Core (3)
3 and (4)
4 to transmitter

Place rapid shutdown system label no more than 1m (3ft) from RSS Transmitter
or AC disconnect if not at same location.
RSS TRANSMITTER COMMERCIAL WIRING

-V +V

+ V ADJ
+ -

Rapid
Shutdown
System
L N
Transmitter

G L2 L1
Homerun
Only (+) or (-)
through RSS Core

Homerun
Only (+) or (-)
through RSS Core

Note: Install TS4-F before powering on RSS Transmitter


· Pass either positive or negative homerun through RSS Cores
· Connect wires to AC side of power supply
· Turn on AC power to Transmitter power supply to activate
keep-alive signal
Max number of strings per RSS Core: 10
Max string length: 30 modules
Max current per RSS Core: 150A
Max cable length from inverter (+) to inverter (-): 1000ft (300m)
Appendix
TS4-F, TS4-R-F, TS4-A-F, RSS Transmitter
TECHNICAL SPECIFICATIONS –
TS4-F / TS4-R-F
Electrical Ratings TS4-F / TS4-R-F Fire Safety
Input

Rated DC Input Power 475W

Input Voltage 16 - 90V

Max Continuous Input Current (IMAX) 12.5A

Output

Output Power Range 0 - 475W

Output Voltage Range 0 – VOC

Communication Type Power Line Communication (PLC)

Rapid Shutdown UL Listed (NEC 2014 & 2017 690.12) Yes

Impedance Matching Capability No

Output Voltage Limit No

Maximum System Voltage 1500V

Specify system voltage when ordering (1000V / 1500V) for appropriate cables
& connectors.

Rapid shutdown activation requires RSS Transmitter. 24


MECHANICAL SPECIFICATIONS –
TS4-F / TS4-R-F
Specifications TS4-F / TS4-R-F Fire Safety
Mechanical

Operating Temperature Range: -40°C to +70°C (-40°F to +158°F), RH < 85%

Storage Temperature Range: -40°C to +70°C (-40°F to +158°F), RH < 60%

Cooling Method Natural Convection

Dimensions (with cover) 178.5mm x 134mm x 25.5mm

Weight (base and cover) 670g

Outdoor Rating IP68, NEMA 3R

Cabling

Type H1Z2Z2-K

Output Length 1.2m standard, other lengths available

Cable Options 1000V rated, 1500V rated

Cable Cross-Section 6.3 ± 0.3mm

Connectors MC4, MC4 comparable

UV Resistance 500hr with UV light between 300-400nm @65C

Maximum System Voltage 1500V

25
TECHNICAL SPECIFICATIONS – TS4-A-F

Specifications TS4-A-F Fire Safety


Environmental

Operating Temperature Range -40°C to +85°C (-40°F to +185°F)

Outdoor Rating IP68, NEMA 3R

Mechanical

Dimensions 138.4mm x 139.7mm x 22.9mm

Weight 490g

Electrical

Input Voltage 16 - 90V

Maximum Continuous Input Current (IMAX) 12.5A

Maximum Power 500W

Output Cable Length 1.2m (standard), other lengths available

Connectors MC4 comparable (standard)

Communication Type PLC

Maximum System Voltage 1500V

Rapid Shutdown UL Listed (NEC 2014 & 2017 690.12) Yes


138.4 22.9
30

139.7

120±10

1200±10

Specify system voltage when ordering (1000V / 1500V) for appropriate cables
& connectors.

Rapid shutdown activation requires RSS Transmitter. 26


TECHNICAL SPECIFICATIONS – TS4-A-2F

Specifications TS4-A-2F Fire Safety


Environmental

Operating Temperature Range -40°C to +70°C (-40°F to +158°F)

Outdoor Rating IP68, NEMA 3R

Mechanical

Dimensions 138.4mm x 139.7mm x 22.9mm

Weight 590g

Electrical

Voltage Range (per input)1 16 - 90V

Maximum Current (per input) 15A

Maximum Power (total) 1000W

Output Cable Length 1.2m (portrait) or 2.2m (landscape)

Connectors MC4 (standard)

Communication Type PLC

Maximum System Voltage 1500V

Rapid Shutdown UL Listed (NEC 2014 & 2017 690.12) Yes


138.4
2X 9 77.8 21
MOUNT HOLE 30

15.6

139.7
120±10

200±10
1800±10

Specify system voltage when ordering (1000V / 1500V) for appropriate cables
& connectors.

Rapid shutdown activation requires RSS Transmitter. 27


TECHNICAL SPECIFICATIONS –
RSS TRANSMITTER
Electrical Ratings RSS Transmitter
Input

Input Voltage 12VDC

Input Current 1A

Average Supply Power 0.85W

Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.7mm

RSS Core

150A per Core


Maximum Current (Single Core: 150A, Dual Core: 300A)

Maximum MPPT String Voltage 1500VDC

Internal Opening for Wires ~25mm

Outside Dimensions 59mm

Maximum Number of Strings per Core 10

Maximum String Length 30 modules

Environmental

Temperature -40°C to 85°C

Recommended max. torque 0.79 N/m for wiring

38 41.3
610
18 AWG
38.5

90.9

Rapid
Shutdown
System
Transmitter
73 max

25.0 min

RSS Transmitter - Front View RSS Transmitter - Side View RSS Core - Side View

All dimensions in mm. 28


TECHNICAL SPECIFICATIONS –
RSS TRANSMITTER COMMERCIAL KIT
Electrical Ratings RSS Transmitter
Input

Input Voltage 12VDC

Input Current 1A

Average Supply Power 0.85W

Included Power Supply Rating 480/277VAC input, 12VDC output

Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.7mm

RSS Core

Maximum Current 150A per Core (includes 2 Cores for 300A)

Maximum MPPT String Voltage 1500VDC

Internal Opening for Wires ~25mm

Outside Dimensions 59mm

Maximum Number of Strings per Core 10

Maximum String Length 30 modules

Environmental

Temperature -40°C to 85°C

Recommended max. torque 0.79 N/m for wiring

38 41.3
610
18 AWG
38.5

90.9

Rapid
Shutdown
System
Transmitter
73 max

25.0 min

RSS Transmitter - Front View RSS Transmitter - Side View RSS Core - Side View

All dimensions in mm. 29


TECHNICAL SPECIFICATIONS –
RSS TRANSMITTER OUTDOOR KIT
Electrical Ratings RSS Transmitter
Input

Input Voltage 12VDC

Input Current 1A

Average Supply Power 0.85W

Dimensions(Transmitter only) 90.2mm x 36.3mm x 57.7mm

RSS Core

100A per Core


Maximum Current (Single Core: 100A, Dual Core: 200A)

Maximum MPPT String Voltage 1500VDC

Internal Opening for Wires ~25mm

Outside Dimensions 59mm

Maximum Number of Strings per Core 10

Maximum String Length 30 modules

Environmental

Temperature -40°C to 85°C

Recommended max. torque 0.79 N/m for wiring

110 17
0
38 41.3 610
18 AWG

+ -

Rapid
38.5

Shutdown
System
L N Transmitter
90.9

270

Rapid
Shutdown
System
Transmitter
max
73

25.0 min

RSS Transmitter Outdoor Enclosure RSS Core Installation Example

All dimensions in mm. 30


TESTING RAPID SHUTDOWN

TS4-F (or TS4-R-F, TS4-A-F, TS4-A-2F) and an RSS Transmitter are a solution
to meet NEC 2014 & 2017 690.12 Rapid Shutdown requirements.

TS4-F, TS4-R-F, TS4-A-F, and TS4-A-2F units automatically enter rapid


shutdown mode when the RSS Transmitter is switched off and resume
energy production when power is restored to the RSS Transmitter.

Wait 30 seconds after rapid shutdown activation before disconnecting


DC cables or turning off DC disconnect.

Test your rapid shutdown system by switching off the AC power to the
RSS Transmitter or inverter with built-in transmitter.

TS4-F, TS4-R-F, and TS4-A-F units will reduce their output to 0.6V when
the Transmitter is powered off.

Place safety labels in proper location

The RSS Transmitter control power supply MUST be on the same AC branch
circuit as the inverter to meet rapid shutdown requirements.

Click here for more info about Rapid Shutdown 31


CONDUIT DRILLING GUIDE

Enclosure Drilling Guide for .75" Conduit


Single Core Dual Core

41.6 41.6

68 41.6
108

41.6
40 40

47.1 47.1 47.1 47.1

2X Ø 28 Ø 28 3X Ø 28 2X Ø 28

Enclosure Drilling Guide for 1" Conduit


Single Core Dual Core

41.6
41.6

41.6
52.3

104.5
41.6

52.3 52.3

50.6 50.6 50.6 50.6

2X Ø 35 Ø 35 3X Ø 35 2X Ø 35

*all dimensions in mm
MISCELLANEOUS

Este equipamento não tem direito à proteção contra interferência prejudicial e


não pode causar interferência em sistemas devidamente autorizados.

33
INSTALLATION COMPLETE

Problems?
TS4-F Troubleshooting Guide

For more details on designing and


installing solutions powered by Tigo,
please visit:
Tigo Academy
Resource Center

Or contact us at:
[email protected]

Tigo Energy, Inc. 655 Campbell Technology Pkwy Suite 150, Campbell, California 95008 USA
www.tigoenergy.com P: +1.408.402.0802 F:+1.408.358.6279 | [email protected]