0172ea66506f59c Ek PDF
0172ea66506f59c Ek PDF
Sydney Olympic Site, Australia was also an interesting Harmonic order (n) % (In / I1)
site to study the effect of a large number of grid
1 100
connected PV systems on the quality of supply of the
utility systems [4]. The solar village consisted of up to 3 1,5
665 homes. Each of the 665 homes had 1 kWp of 5 0,6
photovoltaics on the roof connected to the local 7 0,3
underground low voltage grid via an inverter. The results 9 0,4
of the measurements from the Sydney Olympic Village 11 0,21
showed that harmonic voltages (1.9%) at the Olympic
13 0,2
Village were far below IEEE 519-1992 limits even after
the operation of all PV inverter systems in the solar THD 1,7
village.
It is presumed that some houses have the PV systems of
Another study has been done in two small Greek islands 2 kWp and so that the effective current of the inverter
(Arki and Antikythera) where Photovoltaic Stations (25 can be calculated as 9 Ampere. This value is adjusted to
kWp) were installed [6]. Inverters of Photovoltaic Table 1 and the result is shown in Table 2. Using the
Stations were used to measure the harmonic voltages and values in Table 2, each harmonic of the inverter is
currents. It was shown that the harmonics injected by the modelled as a current source. Thus, an inverter consists
Photovoltaic Stations to the electric grid were not very of seven current sources in the simulation circuit.
high (1.25% - 1.99% for Antikythera and 1.85% - 5.30%
for Arki) and at most cases they could not cause The wire used in the modelled circuit is a Rose
significant problems to the appliances of the customers. aluminium conductor, which is used in overhead power
lines in low voltage grid in Turkey. The wire is used to
II. SIMULATION feed the group of houses in Figure 2. Each group consists
In the simulation of circuit, it is assumed that only house of four houses and there are five groups of houses with
loads are present in the network. The number of the distances among them as 40 meters. According to the
houses is chosen as twenty and they are fed with mono distances, the resistance and inductance of the wire are
phase low voltage grid of a 50 kVA transformer. The found as 54 mΩ and 0.043 mH, respectively.
houses are designed as a circuit of resistive and inductive
Table 2 Inverter current harmonics.
5. node
Inverter 3
Harmonic House loads
(2kW)
PV 3
order (n) In (A) (4 * 336 VA)
<
1 9
3 0,135
5 0,054
40 meters
7 0,027
9 0,036
11 0,019
4. node
13 0,018
House loads
Using values mentioned above, and changing location of (4 * 336 VA)
< <
inverters in the modelled system, fifteen different circuits
are simulated and analyzed. The limit of total harmonic
distortion is taken as 5 % in all circuits. The single line
40 meters
scheme of the modelled system is shown Figure 2.
3. node
Inverter 2
III. SIMULATION RESULTS
When the circuit is examined from the point of view of
harmonics, the total harmonic distortion of voltage is House loads
(2kW)
PV 2
increased specifically when the inverter is close to the end (4 * 336 VA)
< <
of the line. However, these voltage harmonic distortions
(0.075%) are far below the IEEE 519-1992 limits (5%)
because the system chosen is close to the ideal electrical
40 meters
system in terms of the quality of energy. Increase in the
number of PV systems causes voltage rise in the
distribution line, particularly at the ends. In addition, 2. node
current harmonic distortions increase when the number of
inverters increases but do not exceed the limit of 5%
(1.96%). House loads
(4 * 336 VA)
< <
IV. CONCLUSION
According to the results of the simulation, the harmonic
distortion generated by PV generators is below the
standards in a distribution network which has only house
40 meters
(4 * 336 VA)
< <
transformer