FIN STABILIZER - S800 - Part A-APLICATIE REALA
FIN STABILIZER - S800 - Part A-APLICATIE REALA
TECHNICAL MANUAL
Part A
Mechanical Part
Fin Stabilizer
4506E-00_S800-517-05 Part A.doc
Type S
Revision 00
- Fin Stabilizer
Page II
4506E-00_S800-517-05 Part A.doc
E-Mail: [email protected]
Internet: www.bv-industrie.de
Dok-ID: 4506E-00\S800-517-05\A
14.11.2006
Revision 00
- Fin Stabilizer
Document revision sheet Page III
Revision 00
- Fin Stabilizer
Overview Page IV
Overview
The Technical Manual is divided in two parts (books). Part A describes the mechanical part of
the equipment and Part B the electrical part. The following figure shows, which component is
described in which book.
Nose
up 30
°
ALARM ALARM
30
°
Nose
up
3
°
20
20
°
10°
10°
START START
0°
0°
10°
10°
°
20
20
Nose Nose
STOP STOP
° 30
°
down
30
down Fin angle Fin angle
3
2 4
B+V Indistrietechnik 1 5
ThyssenKrupp
4506E-00_S800-517-05 Part A.doc
2 4
Nose
up 30
°
ALARM ALARM
30
°
Nose
up
2
°
20
20
°
10°
10°
START START
0°
0°
10°
10°
°
20
20
Nose 30 Nose
STOP STOP
° °
down
30
down Fin angle Fin angle
3-4 m
B+V Indistrietechnik
ThyssenKrupp
5
ALARM ALARM
NOSE UP NOSE UP
START START START START
30 30
30 20
30 20
20 10 20 10
degree 0 STOP STOP degree 0 STOP STOP
10 10
10 10
20 20
0 30 0 30
EMERGENCY EMERG ENCY EMERGEN CY EMERG ENCY
3 0/1A NOSE DOWN OPERATION OPERATI ON 30/1A NOSE DO WN OPERATION OPERATI ON
ERGEN C ME
RGE NC
EM
E
Y
1 1
0206FVI-1.wmf
Revision 00
- Fin Stabilizer
Table of contents Page V
Chapter 0
0 General and safety ........................................................................................... 0-1
0.1 General............................................................................................................. 0-1
0.1.1 Explanation of symbols .................................................................................... 0-1
0.1.2 Information regarding the technical manual ..................................................... 0-2
0.1.3 Liability and warranty........................................................................................ 0-2
0.1.4 Equally applicable documents.......................................................................... 0-3
0.1.5 Copyright protection ......................................................................................... 0-3
0.1.6 Spare parts....................................................................................................... 0-3
0.1.7 Disposal............................................................................................................ 0-4
0.2 Safety ............................................................................................................... 0-4
0.2.1 Intended use..................................................................................................... 0-4
4506E-00_S800-517-05 Part A.doc
Chapter 1
1 Description ....................................................................................................... 1-1
1.1 General description .......................................................................................... 1-1
1.1.1 Principle of stabilization.................................................................................... 1-1
1.1.2 Fin stabilizing system type S ............................................................................ 1-3
1.1.3 Fin unit with fin box........................................................................................... 1-5
1.1.4 Principle of operation, electro hydraulic ........................................................... 1-7
1.2 Technical data .................................................................................................. 1-10
1.2.1 Ship data .......................................................................................................... 1-10
1.2.2 Operating data.................................................................................................. 1-10
1.2.3 Fin unit.............................................................................................................. 1-11
1.2.3.1 Housing and extending cylinder ....................................................................... 1-11
1.2.3.2 Locking cylinder................................................................................................ 1-11
1.2.3.3 Hydraulic fin control unit ................................................................................... 1-12
1.2.3.4 Valve groups .................................................................................................... 1-13
1.2.3.4.1 Valve group 1 ................................................................................................... 1-13
1.2.3.4.2 Valve group 2 ................................................................................................... 1-13
1.2.3.5 Lubricating unit ................................................................................................. 1-14
1.2.3.6 Header Tank..................................................................................................... 1-14
1.2.4 Hydraulic power unit......................................................................................... 1-15
Revision 00
- Fin Stabilizer
Table of contents Page VI
Chapter 2
2 Control and operation....................................................................................... 2-1
2.1 Measures to be taken before setting into operation for the first time ............... 2-1
2.1.1 Checks ............................................................................................................. 2-1
2.1.2 Venting ............................................................................................................. 2-2
2.1.3 Testing.............................................................................................................. 2-2
2.2 Normal operation.............................................................................................. 2-3
2.2.1 Setting into operation ....................................................................................... 2-3
2.2.2 Switching on the system................................................................................... 2-4
2.2.2.1 Switching on from the bridge............................................................................ 2-4
Revision 00
- Fin Stabilizer
Table of contents Page VII
Chapter 3
3 Maintenance..................................................................................................... 3-1
3.1 Maintenance periods ........................................................................................ 3-1
3.2 Maintenance activities ...................................................................................... 3-2
3.2.1 Fin extension and retraction ............................................................................. 3-2
3.2.2 Emergency pump unit operation ...................................................................... 3-3
4506E-00_S800-517-05 Part A.doc
Chapter 4
4 Troubleshooting................................................................................................ 4-1
Revision 00
- Fin Stabilizer
Table of contents Page VIII
Chapter 5
5 Spare parts and special tools ........................................................................... 5-2
5.1 Spare parts....................................................................................................... 5-2
5.2 Special tools ..................................................................................................... 5-4
5.3 Illustration ......................................................................................................... 5-5
Chapter 6
6 Service information........................................................................................... 6-1
6.1 Hydraulic system .............................................................................................. 6-1
6.2 Lubrication oil system....................................................................................... 6-2
6.3 Permissible filter elements ............................................................................... 6-3
6.3.1 Return line filter hydraulic power unit ............................................................... 6-3
6.3.2 Return line filter lubricating unit ........................................................................ 6-3
6.3.3 For return line filter, header tank ...................................................................... 6-3
6.3.4 For leak oil line filter, hydraulic power unit ....................................................... 6-3
6.3.5 For pressure filter, hydraulic power unit ........................................................... 6-3
Chapter 7
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Table of contents Page IX
List of Illustrations
Fig. IV-1 Components of the fin stabilizer ....................................................................... IV
Fig. 1-1 Ship in rough sea ............................................................................................. 1-2
Fig. 1-2 Flow encountering fin ....................................................................................... 1-2
Fig. 1-3 Fin stabilizing system type S ............................................................................ 1-3
Fig. 1-4 Fin unit.............................................................................................................. 1-6
Fig. 1-6 Housing and extending cylinder ....................................................................... 1-24
Fig. 1-7 Rotary vane motor............................................................................................ 1-26
Fig. 1-8 Fin drive principle ............................................................................................. 1-28
Fig. 1-9 Lubricating unit ................................................................................................. 1-31
Fig. 1-10 Lubricating pump.............................................................................................. 1-32
Fig. 1-11 Header tank...................................................................................................... 1-34
Fig. 1-12 Main pump........................................................................................................ 1-40
Fig. 1-13 Gear-type pump (emergency pump) ................................................................ 1-42
Fig. 1-14 Bladder accumulator ........................................................................................ 1-44
Fig. 1-14.1 Gear-type pump (circulating pump).................................................................. 1-46
Fig. 1-15 Return and leak oil line filter ............................................................................. 1-48
Fig. 1-16 Hydraulic fin control unit ................................................................................... 1-50
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Part A
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Chapter 0
General and safety
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
General and safety Page 0-1
Note!
This symbol labels tips and information that must be observed to ensure efficient and trouble-
free handling of the stabilizer.
Revision 00
- Fin Stabilizer
General and safety Page 0-2
Note!
For reasons of clearness includes this manual not all detail-information of the plant and can also
not describe every possible application of it.
If any further information are requested or any unexpected problems with the plant occurs, which
are not detailed enough described in this manual, please contact the service-department of the
manufacturer B+V Industrietechnik GmbH (for contact information see page II).
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
General and safety Page 0-3
as defined by copyright protection law and are subject to other industrial property rights. Any
improper utilization is liable to prosecution.
It is not permitted to pass on the technical manual to third parties, to copy it in whatever type or
form - even extracts - or to recycle and/or communicate the contents without written permission
by B+V Industrietechnik GmbH (manufacturer). Violations incur the obligation to pay
compensation, all other rights reserved.
We reserve also to the right to exercise industrial property rights.
ATTENTION!
Wrong or faulty spare parts can lead to damage, malfunctions or complete breakdown of
the equipment!
If not released spare parts are used, all guarantee, service, compensation and liability claims
against the manufacturer, his agents or representatives forfeit.
Revision 00
- Fin Stabilizer
General and safety Page 0-4
0.1.7 Disposal
If no agreement has been made regarding return or disposal, dismantled components of the
plant are to be recycled according the following appropriately dismantling:
• Scrap metal materials remains
• Take plastic elements to plastic recycling
• Dispose of remaining components that are sorted according to their material
compositions
ATTENTION!
Electrical scrap, electronic components, lubricants and other auxiliary substances are
subject to hazardous waste treatment and may only be disposed by permitted specialized
companies!
0.2 Safety
4506E-00_S800-517-05 Part A.doc
At the time of development and manufacture, the plant was built according to the applicable,
recognized state-of-the-art and is considered to be safe to operate.
However, risks can arise from the plant if it is not used by appropriately trained personnel or if it
is operated incorrectly or not according to the intend use.
The chapter "Safety" gives an overview of all important safety aspects to have an optimum
protection of persons and the safe, trouble-free operation of the equipment.
Additional to this, the other chapters in this technical manual contain concrete safety notes
identified by symbols to avert danger.
Furthermore the pictograms, signs and labels located at the plant must be observed, they may
not be removed and must be kept in a good and legible condition.
ATTENTION!
Any use that goes beyond the intended use and/or any other use of the plant is prohibited
and is not considered intended use.
Claims of any kind against the manufacturer and/or his representatives that arise from
damage due to non-intend use of the plant are excluded.
The customer is solely liable for any damage arising from non-intended use.
Revision 00
- Fin Stabilizer
General and safety Page 0-5
Intended use also includes the correct adherence to the operating conditions as well as the
information and instructions of this technical manual.
The Fin Stabilizer plant (see first page: Serial Number and Order Number), which is described in
this technical manual, is especially designed for the ship mentioned also on the first page (see
Ship Name / New building Number and Yard) and is only to be used on this ship.
The plant may only to be operated in the here described way.
Revision 00
- Fin Stabilizer
General and safety Page 0-6
Responsibilities for work on and with the plant (operation, maintenance, and repair) must be
clearly determined and adhered to, so that there are no obscurities in allocation of rights and
duties with regard to safety.
Only those persons are allowed to work with the plant, from who can be expected that they work
reliably on and with the plant. Avoid any mode of operation that impairs the safety of persons,
the environment or the plant.
Persons who are under the influence of drugs, alcohol or reaction-impairing medication must
never work on or with the plant.
For the selection of personnel, the applicable age- and profession-related regulations must be
observed for the place where the plant is being used.
The customer must also make sure that non-authorized persons are kept a sufficiently safe
distance to the plant.
The personnel is obliged to report the customer immediately about any changes at the plant that
impairs the safety of the function of it.
Revision 00
- Fin Stabilizer
General and safety Page 0-7
Safety shoes
To protect against heavy, falling parts and slipping on slippery floors.
Protective gloves
To protect the skin against friction, abrasions, piercing and deeper
injuries to the hands and to protect against contact with health-harming
4506E-00_S800-517-05 Part A.doc
substances.
Safety helmet
To protect against falling and flying parts and material.
Protective goggles
To protect eyes against flying parts and fluids.
Ear defenders
To protect against damage to hearing.
Respiratory protection
To protect against harmful gases, vapors, dusts and similar materials and
media.
Revision 00
- Fin Stabilizer
General and safety Page 0-8
0.2.8 Danger
A risk valuation for the plant was carried out. The construction and design of the plant based on
this estimation and corresponds to state-of-the-art.
The plant is operational reliable and safe when operated in accordance with the intended use.
However, there is still a residual risk!
• Never put any safety or monitoring devices, like pressure switches, out of operation or
stud them electrically.
• Depressurized the plant before any maintenance, cleaning or repair work to be carried
out.
• Before any maintenance, cleaning or repair work will be carried out, turn off the main
switch and secure the switch against being switched on again.
• De-energize the plant for all work on the electrical system.
• Do not remove any safety devices or deactivate them through changes.
• Exchange any damaged parts immediately.
Revision 00
- Fin Stabilizer
General and safety Page 0-9
WARNING! Outboard!
During working outboard in the area of the fin stabilizer there is a considerable danger of
getting crushed or otherwise injured by the moving fin.
4506E-00_S800-517-05 Part A.doc
Only qualified personnel who have been instructed about what is involved may carry out
the work and only in presence of a second responsible supervisor!
When switching on the fin stabilizer or during stabilizer operation, it must be absolutely
sure, that the fins can move free without danger of getting contact to other ships, life
boats, swimming, diving or jumping people, quays, dolphins or to ground of sea, river or
harbor.
It is not allowed for anyone to be in this area!
The field of traverse must be blocked off!
WARNING! Inboard!
When switching the fin stabilizer on and off, it must be absolutely sure that nobody is on
the fin case in the area of the swivel arm or the swiveling cylinder; there would be a very
great danger getting crushed!
Only in presence of a second responsible supervisor it is permissible for qualified
personnel to go into this area!
Revision 00
- Fin Stabilizer
Chapter 1
Description
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
General description Page 1-1
1 Description
1.1 General description
The fin stabilizing system type S is used for damping the rolling motion of the ship at sea.
Revision 00
- Fin Stabilizer
General description Page 1-2
Revision 00
- Fin Stabilizer
General description Page 1-3
23 1 4 23
26 26
27 27
22 22
3 3
4506E-00_S800-517-05 Part A.doc
5 2 2 6
7 8
9 10
13 12 11 11 12 13
15 14E 14 14 14E 15
21 21
16 16
17 25 25 17
18 28 19 19 28 18
20 20
1804F1-3.wmf
Fig. 1-3 Fin stabilizing system type S
Revision 00
- Fin Stabilizer
General description Page 1-4
17 Fin
18 Rotary vane motor
19 Crux
20 Lubricating unit
21 Fin angle transmitter
22 Header tank, Stbd, Port
23 Bow thrusters connection (if installed)
25 Limit switch, housing and extending
26 From ship’s main electrical power supply
27 From ship’s emergency electrical power supply
28 Fin locking device
Electrical connection
Mechanical connection
Hydraulical connection
Revision 00
- Fin Stabilizer
General description Page 1-5
Sealing of the crux and the drive system against the outboard side is accomplished by means of
sealing systems.
An elevated header tank takes up hydraulic oil of the rotary vane motor. Due to the static height
of the header tank the oil filling in the crux and in the main sealing (10) is pressurized. Thus,
additional sealing and lubrication is attained.
Basically, the hydraulic power unit of the fin unit consists of the oil tank, oil cooling unit, valve
group, hydraulic fin control unit and pump units as well as the required fittings. The electrical
power supply is accomplished by means of an own fin control cabinet.
The hydraulic power unit comprises a main pump and an emergency pump.
The main pump serves to supply the fin unit with the required pressure oil.
In case of failure of the main pump or ship’s main electrical power supply the fin can be manually
centered and moved by means of the emergency pump unit. If the ship’s main electrical power
supply fails, the emergency pump unit is operated with emergency power from the emergency
electrical power supply.
Revision 00
- Fin Stabilizer
General description Page 1-6
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
General description Page 1-7
The fin stabilizing system can be switched on and off at the control panel bridge and fin control
cabinet. Switching on stabilization and switching off take place automatically after operation of
the respective push button.
Note!
The fins are automatically retracted and centered prior to extension. This measure is necessary
because:
a) The openings of the fin boxes (shell opening) have been kept very small.
b) During switching off, the fins are lowered to the floor of the fin box and
additionally protected there against sliding out by a stopper.
Revision 00
- Fin Stabilizer
General description Page 1-8
During retraction, the main pump (4) delivers hydraulic oil to the housing and extending
cylinder (30) via the directional valve (27), check valve (31) and throttle check valve (26).
The housing and extending cylinder (30) retracts the fin until the limit switch "Housed" de-
energizes the directional valve (27) via stabilizer control. The hydraulic fin control unit (2) then
receives zero signal and the fin is moved to zero position, i.e. the rotary vane motor (29) swivels
(centers) the fin.
After centering (zero position), pressure oil is fed to the housing and extending cylinder (30) via
the directional valve (27) and check valve plate (31). The fin is extended until the limit switch
"Extended" switches. Now directional valve (265) opens, oil flows via channel B3 to the locking
cylinder (294) and the fin is mechanically locked in the extended position.
The position of the locking piston is monitored by the limit switches (295, unlocked) and
(296, locked).
The directional valve (27) remains energized and the pressure is thus still applied in the housing
and extending cylinder (30).
The monitoring of the maximum fin angles is activated. The proportional control valve of the
hydraulic fin control unit (2) is controlled by the stabilizer control.
4506E-00_S800-517-05 Part A.doc
Stabilization begins.
Note!
During extension, the fin zero position is checked by the stabilizer control using the signal of the
fin angle transmitter. In the event of a deviation of > ± 3° from zero position, extension is stopped
and the fin is centered via the directional valve (32).
Extension is continued after centering.
After extension, the fins briefly receive a zero signal and stabilization begins at a fin angle < ± 3°.
The corresponding side of the stabilizer does not start stabilization if the fin angle is > ± 3°.
Stabilization
The control unit of the stabilizer (electrically/electronically part) works with the following data:
− roll angle acceleration ϕ°°,
− roll angle velocity ϕ°,
− roll angle ϕ and the
− ship’s speed V.
Further information about electric/electronic control see Technical Manual Part B (Electrical
Part).
Revision 00
- Fin Stabilizer
General description Page 1-9
Switching off
1. After operation of the push button "STOP", the fin is moved to zero position by the
proportional control valve of the hydraulic fin control unit (2). A voltage is then
applied to the directional valve (265), oil flows via channel A3 to the locking cylinder
(294) until the switch (295) is activated, the fin is unlocked. Now directional valve
(265) is de-energized and a voltage is applied to the directional valve (27). The main
pump (4) feeds to the housing and extending cylinder (30) via the directional valve
(27) and check valve plate (31), and the fin is then retracted. The fin zero position is
monitored in the same way as during switching on, i.e. if > ± 3° from zero position is
exceeded, retraction is interrupted and the fin is centered. Retraction is terminated
when the "Housed" limit switch switches.
Switching of the "Housed" limit switch results in the following:
− The directional valve (27) is de-energized and assumes zero setting, and the
fin is locked hydraulically.
− The directional valve (23), fin lowering, is energized. Pressure oil is routed to the
rotary vane motor (29) and the fin is lowered to the floor of the fin box.
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Technical data Page 1-10
Note!
The manufacturer / supplier for all components listed in the following is:
B+V Industrietechnik GmbH
Length : 302,5 m
Beam : 38,6 m
Draught : 8,65 m
Displacement : 70.960 t
Meta centric height : 2,2 m
Rolling period : 20,8 s
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Technical data Page 1-11
Type : S800
Number of fins : 2
Area of fin : 18,0 m²
Weight
• Fin : approx. 16.500 kg*
• Tail flap : approx. 2.550 kg*
• Fin + Tail flap : approx. 19.250 kg*
• Fin shaft : approx. 12.110 kg*
• Fin shaft + Fin + Tail flap : approx. 31.500 kg*
• Crux : approx. 16.400 kg*
• Rotary vane
4506E-00_S800-517-05 Part A.doc
Type : SSK:601-5633-051
Max. operating pressure : 250 bar / 25 MPa
Stroke : 1.634 mm
Weight : 2.360 kg
Type : SSK-664-2300-000-0000/20
Operating pressure : 160 bar / 16 MPa
Stroke : 110 mm
Weight : 19 kg
Revision 00
- Fin Stabilizer
Technical data Page 1-12
Main valve
1-16/3
with position control
1-16/4 Electronic amplifier Electrical connection
24V=
1-16/5 Pilot control valve
with position control
Revision 00
- Fin Stabilizer
Technical data Page 1-13
pressure
A-3/265 Directional valve, Electrical connection
fin locking and unlocking 24 V DC and
manual actuation
Revision 00
- Fin Stabilizer
Technical data Page 1-14
Starting : direct-on-line
(3) Components
Components
Revision 00
- Fin Stabilizer
Technical data Page 1-15
Revision 00
- Fin Stabilizer
Technical data Page 1-16
Revision 00
- Fin Stabilizer
Technical data Page 1-17
Revision 00
- Fin Stabilizer
Technical data Page 1-18
Revision 00
- Fin Stabilizer
Technical data Page 1-19
Revision 00
- Fin Stabilizer
Technical data Page 1-20
Weight : 1,1 kg
Remark : with electrical contamination
alarm
Revision 00
- Fin Stabilizer
Description Page 1-21
1.3 Description
The fin boxes (A-1/42) are welded into the ship’s structure on the port and starboard sides.
There is an opening in the shell plating of the hull wall through which the fin is retracted and/or
extended.
The crux (A-1/4) is supported in the fin box in crux bearings (A-1/1 and 7), and it rotates by 90°.
The swivel movement is accomplished hydraulically by means of the housing and extending
cylinder (A-1/22), and is controlled and monitored by limit switches (A-1/35 and 37).
When retracted, the crux is hydraulically locked by means of the locking cylinder (A-2/294) and
mechanically secured by lowering of the fin behind of the mechanical stop.
The fin shaft (A-1/27) is pivoted in the crux (A-1/4) in two plain bearings. A fin shaft liner (A-1/26)
provided on the fin shaft (A-1/27) and a main bearing bushing (A-1/28) serve as friction bearing
for the fin shaft (A-1/27) and fin (A-1/29).
Another bearing for fin shaft (A-1/27) and rotary vane motor (A-1/14) is formed by the bushing
(A-1/44) and fin shaft liner (A-1/45).
The fin (A-1/29) is connected to the fin shaft (A-1/27) by a straight pin (A-1/51) and can be
rotated by ± 22° (mechanical stop).
The movable tail flap (A-1/31) is supported in tail flap bearings (A-1/30) and located on the fin
(A-1/29). If the fin is rotated ± 18°, the tail flap will be rotated by ± 29° with respect to the fin axis
by a tail flap drive (A-1/34), thus increasing the effective area. (see Fig. 1-8)
Revision 00
- Fin Stabilizer
Description Page 1-22
The rotary vane motor (A-1/14) serves as driving unit for the fin (A-1/29) and consists of rotary
vane hub (A-1/46), rotary vane housing (A-1/18) and rotary vane cover ring (A-1/19). The rotary
vane hub transmits the rotating motion via splined hub on to the fin shaft (A-1/27).
The hydraulic power unit (A-2/5) supplies oil under pressure via pipes and hose assemblies to
the rotary vane motor.
The crux bearings (A-1/1/7) are supplied with lubricating oil by the lubricating unit (Fig. 1-9).
The electric pulses for retracting and extending, locking and unlocking as well as centering of the
fin are converted into hydraulic signals by the valve group 1 (A-2/302).
The hydraulic fin control unit (A-2/15) converts the electrical signals of the stabilizer control into
hydraulic signals. For further details see section 1.3.2.2.
The fin angle (angle of attack) is transmitted via control shaft (A-1/50) with sensor part (A-1/47)
from the fin to the fin angle transmitter (A-1/9).
The fin angle transmitter (A-1/9) monitors and controls centering of the fin during retraction and
extension. During stabilization, the fin angle transmitter transmits the actual value of the fin angle
to the stabilizer control for nominal/actual value comparison. In addition, the fin angle transmitter
serves for monitoring the maximum angle of attack. (see also Technical Manual Part B -
4506E-00_S800-517-05 Part A.doc
Electrical Part)
The limit switches (A-1/37 and A-1/35) serve to control retraction and extension of the fin and
limit switch (A-1/37) additional for monitoring the fin in retracted position.
Revision 00
- Fin Stabilizer
Description Page 1-23
The main bearing (A-1/15) transmits the major radial bearing forces to the crux (A-
1/4) via fin shaft liner (A-1/26) and main bearing bushing (A-1/28).
Inboard bearing
The inboard radial bearing consists of fin shaft liner (A-1/45) and bushing (A-1/44)
and transmits the minor radial bearing forces at the fin shaft to the crux (A-1/4).
Rotary vane hub (A-1/46) and bushing (A-1/44) form an axial bearing and take up
the axial forces of the fin shaft (A-1/27).
Revision 00
- Fin Stabilizer
Description Page 1-24
The cylinder chambers can be vented through vent valves. Throttle check valves
(Fig. 5-3/26) are used for setting the retraction and extension rates.
1 2 3 4 5
6
1 Cylinder bottom 4 Piston rod
2 Oil connection 5 Cylinder head
3 Piston 6 Cylinder tube
Revision 00
- Fin Stabilizer
Description Page 1-25
The rotary vane motor (A-1/14) serves as swivel drive for the fin (A-1/29).
Basically, it consists of the stationary rotary vane housing (Fig. 1-7/6) and the rotating rotary
vane hub (Fig. 1-7/1). In practice, the rotating rotary vane hub is called rotor and the stationary
rotary vane housing is called stator.
The rotary vane housing (A-1/18) is covered by the rotary vane bottom (A-1/16) and the rotary
vane cover ring (A-1/19). These parts are bolted together by socket-head cap screws (A-1/25)
and connected by hydraulically pre-tensioned tie rods (A-1/17) in the area of the fixed stops.
The rotary vane hub (Fig. 1-7/1) is connected to the fin shaft (Fig. 1-7/8) via the splined profile.
Four pressure chambers are formed by the two-bladed rotary vane hub (Fig. 1-7/1) and the two
fixed stops (Fig. 1-7/9) in the rotary vane housing (Fig. 1-7/6). Two pressure chambers, located
diagonally opposite each other, are interconnected by an oil bore (Fig. 1-7/7).
If oil under pressure is supplied, two pressure chambers A or B are pressurized with oil under
pressure and the rotary vane hub (Fig. 1-7/1) rotates with the fin into the appropriate direction.
From the other two pressure chambers the oil under pressure is forced back to the oil tank of the
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-26
A, B
PRESSURE CONNECTION
4 1
6
B A
2
5
4506E-00_S800-517-05 Part A.doc
3
8
9
Revision 00
- Fin Stabilizer
Description Page 1-27
The pressure oil feed to the rotary vane motor as well as the return is accomplished through
bores (A-1/12) in the crux (A-1/4).
The connection between the pipelines fixed to the fin box and the crux is accomplished by means of
hose assembly (A-1/10). These are connected via swivel device (A-1/13) and standpipes (A-1/11)
to the crux (A-1/4).
Due to the swivel device (A-1/13) the flexible connections are sealed to move freely when the crux
is rotated.
The header tank connection (A-1/24) between the crux and fixed pipeline corresponds to the
pressure oil feed or pressure oil return with respect to design.
The fin (A-1/29) is connected to the fin shaft (A-1/27) by means of a straight pin (A-1/51).
4506E-00_S800-517-05 Part A.doc
The tail flap (A-1/31) is pivoted by tail flap bearings (A-1/30) on the fin.
The tail flap lever (A-1/40) is connected to the tail flap (A-1/31) by means of a straight pin.
The tail flap (A-1/31) is connected to the crux (A-1/4) by means of the tail flap drive (A-1/34),
consisting of the tail flap lever (A-1/40), sliding block (A-1/49) and bearing trunnion (A-1/39).
Revision 00
- Fin Stabilizer
Description Page 1-28
6 2 7 3 1 4 5
°
33
4506E-00_S800-517-05 Part A.doc
°
29
47°
18°
2 2°
1906F1-8.wmf
1 Crux 5 Fin
2 Tail flap lever 6 Tail flap
3 Bearing trunnion 7 Sliding block
4 Fin shaft
Revision 00
- Fin Stabilizer
Description Page 1-29
The fin angle feedback basically consists of control shaft (A-1/50) with sensor part (A-1/47) and
fin angle transmitter (A-1/9). There is no connection between sensor part (A-1/47) and fin angle
transmitter (A-1/9).
The control shaft (A-1/50) is connected to the control pin (A-1/48) of the fin shaft (A-1/27) via rod
coupling (A-1/52). The control shaft (A-1/50) is located in a standpipe.
The rotary movement of the fin shaft (A-1/27) [change of the angle of attack of the fin] is
transmitted to the fin angle transmitter via the above mentioned components. The rotary
movement is converted to electrical signals by the fin angle transmitter.
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-30
The lubricating unit (Fig. 1-9) supplies the crux bearings with lubricating oil during the stabilizing
operation. It is automatically switched on when the fin stabilizing system is switched on, and it is
switched off after retraction to the final position.
Basically, the lubricating unit (Fig. 1-9) consists of the tank (Fig. 1-9/1) with the lubricating pump
(Fig. 1-9/9) which is driven by the electric motor (Fig. 1-9/4).
The pressure side of each pump is connected via test connection and pipeline to a crux bearing.
The lubricating oil pressure is restricted to 0,8 bar by means of pressure relief valves (Fig. 1-9/8). At
a pressure of >0,8 bar the pressure relief valves open and part of the lubricating oil flows back into
the tank (Fig. 1-9/1).
The level switch (Fig. 1-9/3) will trigger an alarm, if the oil level in the tank (Fig. 1-9/1) drops below
the minimum level.
When the electric motor is switched off the return line from the crux bearing top and crux bearing
bottom is closed by the check valve (Fig. 1-9/12).
When the electric motor is switched on the check valve (Fig. 1-9/12) is opened by the oil pressure in
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-31
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-32
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-33
Revision 00
- Fin Stabilizer
Description Page 1-34
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-35
The bladder accumulator (A-3/19) and main pump (A-3/4) form a bladder accumulator and supply
unit, i.e. if hydraulic oil is required, this will be taken from the bladder accumulator and the output of
the main pump (A-3/4) will be increased according to the hydraulic oil requirement.
In case of failure of electric power or main pump (A-3/4) the emergency pump unit (A-3/60)
supplies oil under pressure to the valve group 1 (A-3/3) and valve group 2 (A-3/3E) in order to allow
the fin to be manually centered and retracted.
The hydraulic oil in the oil tank (A-3/7) is circulated and cooled by the oil cooling circuit (A-3/6, A-
3/10) during operation.
For further details of the hydraulic power unit see section 1.3.2.1.
Revision 00
- Fin Stabilizer
Description Page 1-36
The main pump (A-3/4) and/or emergency pump (A-3/5) supply oil through the check valve (A-
3/12 or A-3/48) into the common pressure line.
The pressure line is connected to the valve group 1 (A-3/3), valve group 2 (A-3/3E) and
hydraulic fin control unit (A-3/2).
The bladder accumulator (A-3/19) is connected to the pressure line via the connecting block (A-
3/120). The connecting block (A-3/120) protects the bladder accumulator (A-3/19) from damage
due to overpressure and enables a shut-off from the pump circuit.
Revision 00
- Fin Stabilizer
Description Page 1-37
Function:
The main pump (A-3/4) automatically controls the output back to zero as soon as the
bladder accumulator (A-3/19) is full and the operating pressure has been reached.
If the hydraulic fin control unit (A-3/2), valve group 1 (A-3/3) or valve group 2 (A-
3/3E) require hydraulic oil, the bladder accumulator (A-3/19) supplies part of the
required hydraulic oil (approximately 50%), the main pump (A-3/4) is switched to
delivery and supplies the remaining part of the required hydraulic oil to the consumer
circuit.
The consumer circuit is protected from damage due to overpressure by the pressure
relief valve (A-3/14).
The pressure relief valve (A-3/14) is electrically controlled and opened in the
automatic switch-on mode. As a result, depressurized starting of the main pump is
possible. In the automatic switch-off mode it is also electrically controlled, opened,
and the bladder accumulator (A-3/19) is emptied.
The emergency pump unit (A-3/60) is additionally protected by a pressure relief valve
(A-3/35).
4506E-00_S800-517-05 Part A.doc
The shut-off valve (A-3/13) permits a filter circuit of the hydraulic oil over an extended
period in connection with the emergency pump (A-3/5).
The oil tank (A-3/7) is equipped with a man hole covers (A-4/220), an oil dipstick (A-
3/9) and a drain valve (A-3/153).
The hydraulic oil from the oil tank (A-3/7) is continuously circulated and cooled via
the water-cooled oil cooler (A-3/10) by the circulating pump A-3/6) during the
stabilizer operation. (see also Fig. A-4)
A thermometer and temperature switch (A-3/20) monitors the oil and temperature
and switches off the hydraulic power unit in case of over-temperature.
The oil pressure is indicated by the pressure gauge (A-3/18) and the oil level is
controlled by the oil level alarm (A-3/15).
The level switch (A-3/15) switches off the system if the oil drops or if there is a lack of
oil.
The oil tank can be filled up through a separate oil connection >13< by using a filling
filter with 5 µm filtration.
The return line filter (A-3/11) is installed in the common return line of the hydraulic fin
control unit (A-3/2), the valve group 1 (A-3/3) and the valve group 2 (A-3/3E) and is
supplied with an electrical contamination alarm. An alarm is given when it is
necessary to change the filter element (A-4/190) of the return line filter (A-3/11).
The pressure switch (A-3/38) switches off the fin stabilizer port or starboard
immediately when for example a hose assembly is broken and as a result of this the
oil pressure drops to a given minimum.
Revision 00
- Fin Stabilizer
Description Page 1-38
Revision 00
- Fin Stabilizer
Description Page 1-39
The cylinder (Fig. 1-12/8) is forced by the spring (Fig. 1-12/11) against the control
plate (Fig. 1-12/12); the latter containing control slots for the oil lifted by the suction
stroke and supplied by the delivery stroke.
The control plate (Fig. 1-12/12) constitutes the communicating member between the
rotating cylinder (Fig. 1-12/8) and the stationary pump housing (Fig. 1-12/1).
The swash plate (Fig. 1-12/5) is pivoted by the control piston (Fig. 1-12/6) until the oil
delivered has reached the operating pressure set at the pressure regulator (Fig. 1-
12/9). Then the swash plate (Fig. 1-12/5) is returned by the control piston (Fig. 1-
12/13).
Now the pump delivers only a minimum amount of oil to maintain the operating
pressure.
The attached circulating pump (Fig. 1-12/14) supplies circulating oil from the oil tank
(A-3/7) through the oil cooler (A-3/10) back to the tank.
with oil through the leak-oil connection prior to re-commissioning of the pump.
Don’t turn the flow regulator (Fig. 1-12/7).
Revision 00
- Fin Stabilizer
Description Page 1-40
4599F1-12 (2).tif
4506E-00_S800-517-05 Part A.doc
4599F1-12 (1).tif
Revision 00
- Fin Stabilizer
Description Page 1-41
(Fig. 1-13/5).
The gear wheel (Fig. 1-13/3) is driven by the drive shaft (Fig. 1-13/1). At the same
time, the gear wheel (Fig. 1-13/4) is driven. In the tooth gaps of the gear wheels the
hydraulic oil is passed from the suction side to the pressure side.
On the pressure side the oil carried in the tooth gaps is forced into the pressure line
by the intermeshing teeth of the gear wheels (Fig. 1-13/3 and Fig. 1-13/4).
Revision 00
- Fin Stabilizer
Description Page 1-42
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-43
(A-3/41).
(1) Construction (Fig. 1-14)
The bladder accumulator consists of a container (Fig. 1-14/5) of seamless rolled
steel in which an accumulator bladder (Fig. 1-14/4) of flexible oil-resistant material
with a gas valve (Fig. 1-14/1) is installed. If the bladder accumulator is empty, the
accumulator bladder is pre-filled with nitrogen via the gas valve (check valve with cap
nut).
The bottom connection of the steel container to the hydraulic system is equipped
with an oil valve (Fig. 1-14/3). Normally, this valve is fully open and it will not be
closed until the oil side is completely drained, by the expanding accumulator bladder
(Fig. 1-14/4).
(2) Function (Fig. 1-14)
The bladder accumulator becomes pressurized with hydraulic oil during the moving
and stabilizing operation.
If the pump pressure is higher than the pressure in the accumulator bladder (Fig. 1-
14/4), hydraulic oil flows through the oil valve (Fig. 1-14/3) into the bladder
accumulator. As a result, the accumulator bladder is compressed and the nitrogen
accumulates pressure energy.
If hydraulic oil is used, the pressure in the hydraulic system decreases and the
accumulator bladder expands. As a result, hydraulic oil flows from the bladder
accumulator until the pressure in the hydraulic system and in the accumulator
bladder is in balance.
Revision 00
- Fin Stabilizer
Description Page 1-44
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-45
The gear wheel (Fig. 1-14.1/3) is driven by the drive shaft (Fig. 1-14.1/1). At the
same time, the gear wheel (Fig. 1-14.1/4) is driven. In the tooth gaps of the gear
wheels the hydraulic oil is passed from the suction side to the pressure side.
On the pressure side the oil carried in the tooth gaps is forced into the pressure line
by the intermeshing teeth of the gear wheels (Fig. 1-14.1/3 and Fig. 1-14.1/4).
Oil cooler
The oil cooler (A-3/10) is designed as a heat exchanger with pipe assembly. Cooling
water flows through the pipe assembly on the inside and hydraulic oil flows around
on the outside.
Revision 00
- Fin Stabilizer
Description Page 1-46
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-47
Also in the leak oil line of the main pump, a filter (A-3/267) is installed in the flushing connection
from the main pump (4) to the oil tank (7).
section of passage of the filter element (Fig. 1-15/1) will be reduced. As a result, the
pressure at the filter inlet A increases. The electrical contamination alarm (Fig. 1-
15/5) responds. After changing of the filter element (Fig. 1-15/1) and cleaning of the
filter housing (Fig. 1-15/2) the electrical contamination alarm (Fig. 1-15/5) must no
longer be activated.
Revision 00
- Fin Stabilizer
Description Page 1-48
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-49
The most important part of the electric / hydraulic control is the hydraulic fin control unit (A-3/2).
The hydraulic fin control unit is used to hydraulically amplify the signals from the electric control
unit (stabilizer control) and to convert these signals into hydraulic output signals which serve to
control and regulate the flow of the hydraulic oil to the rotary vane motor and thus the movement
of the fin, fin angle and fin angle rate.
The hydraulic fin control unit consists of
− Connecting block (Fig.1-16/1)
− Proportional control valve (Fig. 1-16/6)
16/3) is deflected according to the electrical control of the pilot control valve (Fig. 1-
16/5).
As a result, the hydraulic oil is deflected into the respective direction and flows via
A or B and shut-off valve (A-3/8) to the rotary vane motor (A-3/29).
The return oil from the rotary vane motor flows via shut-off valve (A-3/8) and A or B
of the connecting block (Fig. 1-16/1) to the main valve (Fig. 1-16/3).
In this valve the oil is deflected by the main control piston and flows via the
connecting block (Fig. 1-16/1) into the oil tank (A-3/7).
Revision 00
- Fin Stabilizer
Description Page 1-50
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-51
This is deflected and control oil is flowing to the pressure chamber of the main valve (Fig. 1-
18/1) until the piston of the main valve has reached the required position. The pistons of the pilot
control valve (Fig. 1-18/2) and main valve are controlled by the positioning control (Fig. 1-18/4
and Fig. 1-18/5) and corrected if necessary.
The pressure oil flows from connection P via A to the rotary vane motor, i.e. the fin set angle α is
changed. The return oil from the rotary vane motor flows via connection B into the T-channel
and from there to the oil tank.
When switching on the stabilizer plant the proportional control valve will not yet receive electrical
setting signals as the fin must be extended, i.e. the main piston is kept in mid-position by spring
pressure.
The fin is retracted until the limit switch "HOUSED" is contacted. Then the proportional control
valve receives "ZERO SIGNAL", i.e. the proportional solenoid is activated. Pressure oil is
directed from P to the rotary vane motor via B and A respectively until the fin is centered.
Revision 00
- Fin Stabilizer
Description Page 1-52
Revision 00
- Fin Stabilizer
Description Page 1-53
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-54
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
Each valve group (A-3/3 and A-3/3E) consists of a connecting block on which directional valves
are located. The valves for valve group 1 (A-3/3) are electrically operated during automatic mode
or manually during emergency operation, at valve group 2 (A-3/3E) are these valves only for
manually operation designed, because the second valve group is for emergency operation only.
The directional valves are used to control retraction and extension, centering and lowering of the
fin.
The directional valve (A-3/23) is controlled after retraction of the fin to the final
position and forms a connection to the rotary vane motor (A-3/29). As a result,
lowering of the fin tip to the bottom of the fin box is performed.
The connected pressure reducing valve (A-3/39) serves to reduce the oil pressure of
the rotary vane motor if the fin is lowered.
The directional valve (A-3/32) is automatically controlled during switching on and off of
the stabilizer operation, if the fin angle is > ± 3° and the fin cannot be retracted or
extended with zero signal. It controls centering of the fin in zero position for retraction or
extension.
The directional valve (A-3/27) serves for retraction and extension of the fin via the
housing and extending cylinder (A-3/30). It is automatically controlled after centering
of the fin in zero position.
In zero position of the directional valve (A-3/27) the housing and extending cylinder
(30) is hydraulically locked by means of the connected check valve (A-3/31).
The directional valve (A-3/32), emergency operation with hand knob, is used for
centering of the fin if the ship’s electric power supply or main pump (A-3/4) fails.
The directional valve (A-3/27), emergency operation with hand knob, serves for
retraction and extension of the fin during emergency operation, if the stabilizer
control, main pump (A-3/4) or the electric power supply should fail.
See also Fig. 5-1.
Revision 00
- Fin Stabilizer
Description Page 1-55
Revision 00
- Fin Stabilizer
Description Page 1-56
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
The pressure switch (see Fig. 1-19 and A-3/38) is a piston hydro-electric type pressure switch.
It basically consists of the housing (Fig. 1-19/1), cartridge with piston (Fig. 1-19/2), pressure
spring (Fig. 1-19/3), adjustment element (Fig. 1-19/4) and micro switch (Fig. 1-19/5).
The pressure to be monitored is applied to the piston (Fig. 1-19/2) via orifice (Fig. 1-19/7). The
piston (Fig. 1-19/2) supports itself on the spring plate (Fig. 1-19/6) acts against the infinitely
variable force of the pressure spring (Fig. 1-19/3). The spring plate (Fig. 1-19/6) transfers the
movement of the piston (Fig. 1-19/2) to the micro switch (Fig. 1-19/5) and releases the same on
reaching the set pressure. Through this, the electric circuit is closed.
If the pressure to be monitored is below the set value then the micro switch (Fig. 1-19/5) is
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Description Page 1-57
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Chapter 2
4506E-00_S800-517-05 Part A.doc
Operating Instructions
Revision 00
- Fin Stabilizer
Operating instructions Page 2-1
Note!
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
2.1 Measures to be taken before setting into operation for the first
time
Prior to putting into operation for the first time after repair and/or an extended shut-down, the
following measures are to be carried out:
2.1.1 Checks
4506E-00_S800-517-05 Part A.doc
Note!
The oil level must be visible on the oil dipstick, replenish oil, if required.
For the oil brand see List of Lubricants / Oil List.
Fill up pump housing of main pump (A-3/4) with hydraulic oil via hose assembly (A-3/55).
If the hydraulic circuit had been opened, carry out filter circuit operation with the emergency
pump unit, see Section 3.2.6.
Valve circuit:
Open the shut-off valves (A-3/8) on the fin unit and the shut-off valve (A-3/41) at the connecting
block (A-3/120).
Close the discharge valves A-3/13 and A-3/42 at the connecting block and throttle/shut-off valve
(A-3/17) of the pressure gauge (A3-3/18).
Set hand knob of the directional valves (A-3/27, 27E, A-3/32, 32E and A-3/23, 23E) to position
closed, by turning both knobs anti-clockwise as far as it will go.
Establish the cooling water supply to the oil cooler (A-3/10).
Revision 00
- Fin Stabilizer
Operating instructions Page 2-2
2.1.2 Venting
The hydraulic system can only be vented during operation.
Housing and extending cylinder (A-3/30) via venting valves (A-3/28).
Rotary vane motor (A-3/29) via venting valves (A-3/28).
Note!
The venting valve is automatically opened by screwing on the venting hose - oil is coming out -
and automatically closed when the venting hose is screwed off.
Note!
The system should be vented only when the fins are moving very small angles.
4506E-00_S800-517-05 Part A.doc
2.1.3 Testing
System test (see section 2.4).
Revision 00
- Fin Stabilizer
Operating instructions Page 2-3
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Note!
In order to allow the system to be switched on at any time, the system should be in the condition
described below.
Leakage control: - Pipeline system
4506E-00_S800-517-05 Part A.doc
Note!
The oil level must be visible on the oil dipstick, replenish oil, if required.
Valve circuit: - Shut-off valves (A-3/8) and shut-off valve (A-3/41) open.
- Shut-off valve (A-3/13), throttle/isolating valve (A-3/17) and
discharge valve (A-3/42)) closed.
Header tank - Valve (A-3/224, 227) open.
Valve (A-3/210) closed.
Housing / extending cylinder - Throttle check valve (A-3/26) open or partly closed.
- Three-way valves (A-3/276, 277, 278, 279) in correct position.
- Three-way valves (A-3/270, A1) and (A-3/271, B1) connected to
valve group 1
Locking cylinder - Three-way valves (A-3/272, 273, 274, 275) in correct position.
- Throttle check valve (A-3/299) open or partly closed.
- Three-way valves (A-3/268, B3), and (A-3/269, A3) connected to
valve group 1
Valve group 1 - Valves (A-3/284, P), (A-3/285, T), (A-3/221, A2) and (A-3/222,
B2) open.
- Three-way valves (A-3/270, A1) (A-3/271, B1), (A-3/268, B3),
and (A-3/269, A3) in correct position, see above.
- Throttle check valve (A-3/26) and throttle valve (A-3/62) open or
partly closed.
Revision 00
- Fin Stabilizer
Operating instructions Page 2-4
Valve group 2 - Valves (A-3/282, P), (A-3/283, T), (A-3/280, A2) and (A-3/281,
B2) open.
- Three-way valves (A-3/270, A1) (A-3/271, B1), (A-3/268, B3),
and (A-3/269, A3) in correct position, see above.
Fin Control Cabinet,
port and starboard: - Switch for the emergency pump in position "AUTO".
- Electric main power supply “ON”
- Electric emergency power supply “ON”
- Service switches in correct position, see Technical Manual
Electrical Part
Note!
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Operating instructions Page 2-5
Note!
Only authorized persons are allowed to switch off the stabilizer.
See also Chapter 0, General and safety.
retracted".
The fin stabilization is switched off.
Revision 00
- Fin Stabilizer
Operating instructions Page 2-6
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Note!
Re-tightening of pipe couplings only when the system is switched off.
Hydraulic oil temperature: - Check at the thermometer and temperature switch (A-3/20)
Revision 00
- Fin Stabilizer
Operating instructions Page 2-7
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Valve circuit: - Close the shut-off valves (A-3/8), (A-3/221, 222), (A-3/280, 281),
(A-3/282, 283, 284, 285) and shut-off valve (41).
- Open the shut-off valves (A-3/13), throttle/isolating valve (A-
3/17) and discharge valve (A-3/42). The throttle/shut-off valve
(A-3/17) has to stay open.
Revision 00
- Fin Stabilizer
Operating instructions Page 2-8
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
The inoperative fin will be housed fully or semi-automatically (see section 2.3.2) or it must be
housed using manual emergency operation (see section 2.3.4), dependent on the fault or design
of the system.
4506E-00_S800-517-05 Part A.doc
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Even in the case of a failure of the main electrical power supply each fin can be automatically
housed by emergency electrical power supply.
The control panel bridge (See also Technical Manual Electrical Part) is provided with two yellow
illuminated lamps EMERGENCY OPERATION to indicate the housing of the fin with emergency
electrical power supply.
If one of the push-buttons STOP port or STOP starboard is actuated, the emergency pump is
automatically started and the respective fin is automatically housed.
Revision 00
- Fin Stabilizer
Operating instructions Page 2-9
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
The tilting movement of one fin is interrupted by some disturbances and the respective fin is
automatically housed.
If the failure cannot be remedied immediately, take the inoperative fin out of operation according
to section 2.2.5.
Revision 00
- Fin Stabilizer
Operating instructions Page 2-10
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
In case of stabilizer control or main electrical power supply failure the following measures are to
be carried out:
1. In case of main electrical power supply failure establish the emergency electrical power
supply (fin control cabinet, port and starboard).
2. In case of stabilizer control failure
− Fin Control Cabinet: Switch on the motor for the emergency pump unit, port or
starboard, switch in position "MAN".
− Valve Group 1: Unlock the fin by operating the hand knob of the directional
valve (A-3/265).
Center the fin in zero position by operating the hand knob of
the directional valve (A-3/32).
Retract the fin to final position by operating the hand knob of
the directional valve (A-3/27).
Lower the fin to the bottom of the fin box by operating the
hand knob of the directional valve (A-3/23).
Note!
Don’t use both hand knobs of a directional valve at the same time.
Use valve group 2 if there is a failure in valve group 1. Close valves (A-3/284, 285)
and (A-3/221, 222). Changeover valves (A-3/270, 271) and (A-3/268, 269) to valve
group 2. Use the directional valves (A-3/265E, 32E, 27E and 32E) to unlock, center,
house and lower the fin.
− Fin Control Cabinet: Switch off the motor of the emergency pump unit, switch in
position "Auto".
To take the respective stabilizer unit out of operation see also section 2.2.5.
Revision 00
- Fin Stabilizer
Operating instructions Page 2-11
After remedy of the malfunction establish the operational condition in accordance with
section 2.2.
For more electrical details see also Technical Manual Electrical Part.
Note!
Only authorized persons are allowed to switch on and off the stabilizer.
See also Chapter 0, General and safety.
The test operation could be carried out during sea trial after repairs and after an extended shut-
down of the system by BVI-Service Personnel only.
− Forced rolling: Press the respective START button and keep it pressed until
a sufficient roll angle has been reached.
− Free rolling: When a sufficient roll angle has been reached press
additionally the stop button , the fin moves to zero.
− Stabilizing: When a sufficient roll angle has been reached release the
START button, the fin starts to stabilize.
After 1 to 2 periods of roll the roll motion must be
substantially damped.
Revision 00
- Fin Stabilizer
Chapter 3
Danger !
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Maintenance Page 3-1
3 Maintenance
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
system is
inoperative
Monthly Emergency pump unit operation 3.2.2
Oil change of lubricating unit. 3.2.10
Check oil flow with venting hose
Emergency operation 3.2.3
Check the bladder accumulator pre-pressure in 3.2.7.2
the switch off mode
Hydraulic system oil test 3.2.4
Semi- Sealing and lubricating system oil test 3.2.5
Annually Cleaning the filter of the lubricating unit 3.2.14.2
Check relays, contactors and terminals in the fin Manual
control cabinet and junction boxes, and check Electrical
terminals of the electric motors for secure Part
attachment.
Venting Or when 2.1.2
required
Cleaning the oil cooler. Or when 3.2.13
Check anodes required
Revision 00
- Fin Stabilizer
Maintenance Page 3-2
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Note!
- Daily extension and retraction of the fin serves the purpose of preventing deposits (marine
growth) from forming in the area of the sealing and bearing gaps.
- The header tank is filled up automatically when the stabilizer is switched on for stabilizing.
- For extension and retraction briefly put the stabilizing system into operation or take it out of
operation and, after retraction to the final position, establish the desired condition. (see
section 2.2).
Revision 00
- Fin Stabilizer
Maintenance Page 3-3
Note!
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work.
See also Chapter 0, General and safety.
Operate the emergency pump unit (A-3/60) to check the function of the emergency pump (A-3/5)
and to fill up the emergency system with oil.
Fin Unit: - Close shut-off valve (A-3/8, A-3/282, 283, 284, 285).
Fin Control Cabinet: - Switch on the motor for emergency pump, switch in position
"MAN" for some minutes (manual switch is located inside the fin
control cabinet).
Hydraulic Power Unit: - Close discharge valve (A-3/13) slowly, pressure is built up.
Fin Control Cabinet: - After some minutes switch off emergency pump, switch in
position "AUTO".
Hydraulic Power Unit: - Slowly open shut-off valve (A-3/13), until the pressure is
released then close shut-off valve (A-3/13) again.
Fin Unit: - Open shut-off valve (A-3/8, A-3/282, 283, 284, 285).
Note!
Check the smooth running of the pump during operation.
Revision 00
- Fin Stabilizer
Maintenance Page 3-4
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Perform an emergency operation as follows:
Fin Control Cabinet: - Switch on the motor for the emergency pump, switch in position
"MAN" (manual switch is located inside the fin control cabinet).
Hydraulic Power Unit: - Slowly close shut-off valve (A-3/13), pressure is built up
Valve group 1: - Unlocking of the fin by operating the hand knob of the directional
valve (A-3/265).
- Centering of the fin in zero position by operating the hand knob
of the directional valve (A-3/32). Fin tilting angle to be smaller
than ±3°.
- Extension or retraction of the fin by operating the hand knob of
the directional valve (A-3/27). Fin tilting angle ≤±3°.
- In retracted final position, lower the fin by operating the hand
knob of the directional valve (A-3/32) to the bottom of the fin box.
(mechanical locking).
Fin Control Cabinet: - Switch off the motor for the emergency pump, switch in position
AUTO.
Hydraulic Power Unit: - Slowly open shut-off valve (A-3/13) to make the bladder
accumulator (A-3/19) pressure less and close it again.
Fin Unit: - For normal operation with stabilizer control open shut-off valves
(A-3/8) again.
Revision 00
- Fin Stabilizer
Maintenance Page 3-5
To use valve group 2 (if failure in valve group 1) close valves (A-3/284, P), (A-3/285, T), (A-
3/221, A2), (A-3/222, B2) and changeover valve (A-3/270, A1) and (A-3/271, A2) to enable fin
housing, changeover valve (A-3/268, B3) and (A-3/269, A3) to enable fin unlocking, check
correct position of the three-way valves. The valves (A-3/282, P), (A-3/283,T), (A-3/280, A2) and
(A-3/281, B2) must remain in open position.
The function of the valves 27 and 27E, 265 and 265E, 32 and 32E is identical.
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
4506E-00_S800-517-05 Part A.doc
Take an oil sample under hot operating conditions from the venting valves (A-3/28) and test
connection (A-2/71) and test it as follows:
− Test the oil quality (viscosity, etc.) with the onboard oil test set.
Further details of the oil brand (see List of Lubricants / Oil List).
− Fill the oil sample into two test tubes, extract water from one oil sample by heating up and
check for water and dirt deposits by comparing both oil samples.
Note!
- If water or poor oil quality is detected the oil must be changed (see Section 3.2.6).
- If dirt deposits are detected, carry out filter operation for several hours (see Section 3.2.6) or
change the oil if necessary.
B+V Industrietechnik recommend a hydraulic oil with a permissible contamination class of 8
according to NAS 1638.
Revision 00
- Fin Stabilizer
Maintenance Page 3-6
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Take an oil sample from the following system components with the system in operation:
Lubricating unit - via the test connection (Fig. 5-6/14; Fig. 5-6/27)
− Test the oil quality (viscosity, etc.) with the onboard oil test set
(Further details of the oil brand see List of Lubricants / Oil List.)
− Fill the oil samples into test tubes and check for water and dirt
deposits.
4506E-00_S800-517-05 Part A.doc
− Depending on the result of the oil test, carry out an oil change, if
required (see Section 3.2.10).
− Clean the filter element, see Section 3.2.14.2.
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Revision 00
- Fin Stabilizer
Maintenance Page 3-7
Note!
Only lint-free cleaning rags must be used for cleaning.
− Prior to closing the man hole cover check the cover seal and replace it, if required.
− Tighten the hexagon nuts of the man hole cover uniformly in the cross-wise manner.
− Fill the oil tank (A-4/7) with hydraulic oil through the filling connection >13< via a separate
filter with a filtration grade of 5 µm.
− Fill the header tank (Fig. 5-4/204) with hydraulic oil via screw plug (Fig. 3-6/4).
(Type of oil: See List of Lubricants / Oil List.)
Note!
The header tank is connected to the hydraulic power unit as well as to the fin unit. Check the oil
level of the hydraulic power unit when filling up the header tank.
4506E-00_S800-517-05 Part A.doc
− After the oil change operate the filter circuit with the emergency pump unit for one or two
hours.
− To do this, switch on the emergency pump unit on the fin control cabinet (FCC) and open
discharge valve (A-3/13).
Note!
After filter circuit operation replace filter element of the return line filter (A-4/11), if necessary
(see Section 3.2.14.1).
Revision 00
- Fin Stabilizer
Maintenance Page 3-8
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Note!
The fin stabilizing system must be in-operative.
The bladder accumulator must be completely depressurized on the hydraulic oil side.
− Slowly open the discharge valve (A-3/42) and check the pressure drop in the hydraulic
system on the pressure gauge (A-4/18).
− Subsequently, close valve (A-3/42).
(1) Preparation (Fig. 3-1)
− Unscrew the protective cap (Fig. 3-1/6) and cap nut (Fig. 3-1/7) from the gas valve,
remove O-ring (Fig. 3-1/8).
− Screw the filling and testing device (Fig. 3-1/5) with the transition piece (Fig. 3-1/4) on
the gas valve (Fig. 3-1/9).
(2) Test
− Screw in the valve screw (Fig. 3-1/2) until the test pressure gauge indicates the nitrogen
pre-pressure in the accumulator bladder.
Note!
For the nitrogen pre-pressure see section 1.2.4.5. Refill the nitrogen pre-pressure, if required.
− Back off the valve screw (Fig. 3-1/2) and check by opening the relief valve (Fig. 3-1/1) if
the gas valve is closed.
Revision 00
- Fin Stabilizer
Maintenance Page 3-9
(3) Filling Up
Note!
If the filling pressure of the nitrogen bottle is higher than 160 bar, a pressure reducing valve must
be connected.
− Before tightening the filling hose, briefly open the valve of the nitrogen bottle (venting of
the filling hose).
− Screw in the valve screw (Fig. 3-1/2) until the test pressure gauge indicates pressure.
4506E-00_S800-517-05 Part A.doc
− Carefully open the shut-off valve on the nitrogen bottle and slowly fill up the pre-
pressure to the specified value.
Note!
After approximately five minutes (temperature equalization) check the pre-pressure, replenish, if
required.
− Back off the valve screw (Fig. 3-1/2) and remove the filling hose and nitrogen bottle
(4) Pressure Reduction
If the nitrogen pre-pressure should be too high, it can be reduced as follows:
− Screw in the valve screw (Fig. 3-1/2).
− Reduce the nitrogen pre-pressure to the desired value by carefully opening the relief
valve (Fig. 3-1/1).
(5) Final Measures
− After releasing the transition piece (Fig. 3-1/4) remove the filling and testing device.
− Check the gas valve (Fig. 3-1/9) for leaks by applying soapsuds with a brush.
− Fit O-ring (Fig. 3-1/8) and cap nut (Fig. 3-1/7) and slightly tighten it by hand or with a
wrench.
Note!
Do not apply force, otherwise the O-ring (Fig. 3-1/8) will be damaged.
− Screw on the protective cap (Fig. 3-1/6) by hand.
Revision 00
- Fin Stabilizer
Maintenance Page 3-10
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Maintenance Page 3-11
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Observe the pressure gauge (Fig. A-4/18) during switching off mode. The oil pressure decreases
uniformly until the bladder accumulator is empty, subsequently the oil pressure drops rapidly to
zero. The last pressure indication corresponds to the pre-filling pressure of the accumulator
bladder.
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
The oil level switch (A-3/15) is installed vertically from above in the oil tank.
When reaching the minimum admissible oil level, the stabilizer side involved is switched off by
the level switch (A-3/15) and the fin will be housed. During this operation the pressure switch (A-
3/38) will still control the system pressure and will stop the housing, if the pressure will decrease
below the setting.
1. Check setting of level switch with switched off fin stabilizer:
− lower oil level, for example during oil change
− or unscrew fitting screws of the unit and pull out the unit vertically until the switch
point is reached
− check operation of switch with buzzer
2. Check circuit of level switch with switched on stabilizer:
− open circuit at terminal box or level switch, the fin stabilizer must switch off.
Revision 00
- Fin Stabilizer
Maintenance Page 3-12
Note!
The fin stabilizer involved can only be switched on again after the fault has been remedied and
the alarm has been acknowledged.
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Fin Control Cabinet: - Notice the normal position of all Service Switches.
Switch Service Switch MANUAL to position “I”.
- Switch Service Switch BYP. VALVE_Y14 to position "I”,
directional valve (A-3/14.2) is activated and thus directional
cartridge valve (A-3/14.1) is open, no pressure can be build up.
Fin Unit: - Close the shut-off valves (A-3/8, A-3/282, 283, 284, 285).
Fin Control Cabinet: - Switch on the motor for the main pump, Service Switch
MAIN_PUMP in position “I”.
- Switch Service Switch BYP. VALVE_Y14 to position “0”.
Directional valve (A-3/14.2) is deactivated and thus directional
cartridge valve (A-3/14.3) is closed, pressure is built up.
Revision 00
- Fin Stabilizer
Maintenance Page 3-13
Hydraulic Power Unit: - Unscrew the protective cap (Fig. 3-3/4) of pressure regulator
(Fig. 3-3/2).
- Loosen the lock nut (Fig. 3-3/5) of the adjusting screw (Fig. 3-
3/6).
- Increase the operating pressure by turning the adjusting screw
(Fig. 3-3/6) to the right. Note the number of turns.
Hydraulic Power Unit: - Check on the pressure gauge (A-3/18) when the pressure relief
valve (A-3/14) opens.
(For the opening pressure, see section 1.2, TECHNICAL DATA.)
4. Lock the adjusting screw (Fig. 3-4/3) with the lock nut (Fig. 3-4/2).
5. Fit the protective cap (Fig. 3-4/1).
Hydraulic Power Unit: - Back off the adjusting screw (Fig. 3-3/6) by the respective
number of turns until the operating pressure has been reached.
Observe the pressure gauge (A-3/18).
- Lock the adjusting screw (Fig. 3-3/6) with the lock nut (Fig. 3-
3/5), fit protective cap (Fig. 3-3/4).
Revision 00
- Fin Stabilizer
Maintenance Page 3-14
Fin Control Cabinet - Switch off main pump motor, Service Switch MAIN_PUMP in
position "0".
- Switch Service Switch BYP. VALVE_Y14 to position “I” until the
bladder accumulator is empty, then Service Switch in position
“0”.
Switch Service Switch MANUAL to position “0”.
- Check all Service Switches for normal position.
Hydraulic Power Unit: - Slowly open discharge valve (A-3/42) until the hydraulic power
unit is pressure less, then close it again.
Fin Unit: - Open shut-off valve (A-3/8, A-3/282, 283, 284, 285).
Revision 00
- Fin Stabilizer
Maintenance Page 3-15
4506E-00_S800-517-05 Part A.doc
1 Protective cap
2 Lock nut
3 Adjusting screw
4 Directional valve, pilot control valve
5 Control cover
Revision 00
- Fin Stabilizer
Maintenance Page 3-16
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Note!
Carry out the measure when the system is at operating temperature.
- Switch off the fin stabilizing system and secure it against switching on.
- Clean the filter according to Section 3.2.14.2
4506E-00_S800-517-05 Part A.doc
- Unscrew the screw plug (Fig. 3-5/7) and catch the oil flowing out (oil pan, container, etc.).
- Check the drained oil for contamination.
Note!
If heavy contamination of the oil is detected, open and clean the tank (Fig. 3-5/1). Only use lint-
free rags for cleaning.
- Check the function of the lubricating pump (Fig. 3-5/9) at the test connection (Fig. 5-6/14,
Fig. 5-6/27), oil must coming out.
Note!
The test connections are automatically opened when the venting hose (See Section 5.2) is
screwed on, oil is coming out, and they are automatically closed when the venting hose is
screwed off.
Revision 00
- Fin Stabilizer
Maintenance Page 3-17
Fin Control Cabinet - Switch off the electric motor (Fig. 3-5/4) of the lubricating unit
(Fig. 3-5), Service Switch LUB_PUMP in position “0”.
- Switch Service Switch MANUAL to position “0”.
- Check all Service Switches for normal position.
A, B, to crux bearing
T, from crux bearing
Revision 00
- Fin Stabilizer
Maintenance Page 3-18
Note!
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work.
See also Chapter 0, General and safety.
Note!
If possible, carry out the oil change of the header tank in connection with the hydraulic system oil
change (see section 3.2.6).
4506E-00_S800-517-05 Part A.doc
- Switch off the fin stabilizing system and secure it against switching on.
- Drain header tank (Fig. 5-4/204) via shut-off valve (Fig. 5-4/210), the breather and vent
valve (Fig. 3-6/5) is automatically opened.
Note!
Only use lint-free cleaning rags.
- If the header tank had been drained through the shut-off valve (Fig. 5-4/210), the valve
must be closed.
- Before filling the hydraulic power unit fill up the fin unit with hydraulic oil via the threaded
socket of the screw plug (Fig. 3-6/4) or shut-off valve (Fig. 5-4/210) via a separate filling
filter (10 µm).
(For the type of oil see List of Lubricants / Oil List.)
Revision 00
- Fin Stabilizer
Maintenance Page 3-19
Note!
The header tank is connected to the hydraulic power unit as well as to the fin unit. Check the oil
level of the hydraulic power unit when filling up the fin unit via header tank. (See also Fig. 6-1.)
- Prior to switching on the stabilizer check the system according to section 2.2.1.
Revision 00
- Fin Stabilizer
Maintenance Page 3-20
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Maintenance Page 3-21
Note!
Only skilled workers who are specialized to work on this stabilizing system are qualified to do
this work.
See also Chapter 0, General and safety.
Carry out this measure every two years, after 10.000 operating hours or according to the
recommendation of the electric motor manufacturer.
- Switch off the fin stabilizing system and secure it against switching on.
- Interrupt the electric power supply of the respective electric motor by removing the fuses.
- Mark the cables and cable connections and disconnect the electric motor.
4506E-00_S800-517-05 Part A.doc
- Check the individual parts such as bearing brackets for reuse, replace the respective parts,
if required.
Note!
Do not force on the ball bearings, heat up the ball bearings to approximately 80 °C in an oil bath,
if required.
- Fill the ball bearings with grease according to the List of Lubricants / Oil List.
- Connect the electric motor in accordance with the markings of the cable connections.
Revision 00
- Fin Stabilizer
Maintenance Page 3-22
- Check the electric motor and pump for heating up and excessive noise.
Note!
If excessive noise or heating up is detected, stop the pump and determine the cause.
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Maintenance Page 3-23
Note!
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work.
See also Chapter 0, General and safety.
- Switch off the fin stabilizing system and secure it against switching on.
- Close the oil cooler cooling water inlet and outlet valves.
- Depressurize the oil cooler on the cooling water side and oil side.
Note!
Prior to removing the connecting and deflecting bottom, mark the installation position.
- The water boxes are equipped with anodes to protect the oil cooler against corrosion.
- Remount the connecting and deflecting bottom paying attention to the markings of the
installation position, by using NEW sealing (seals / O-rings)
Revision 00
- Fin Stabilizer
Maintenance Page 3-24
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
3.2.14.1 Changing the filter element of return line and leak oil line filter
Change the filter element of the return line filter (A-3/11) and the leak oil line filter (A-3/267)
when there is an electrical contamination alarm.
- Switch off the fin stabilizing system and secure it against switching on.
- Unscrew the filter head (Fig. 3-7/3) from the filter housing (Fig. 3-7/2) and remove the filter
4506E-00_S800-517-05 Part A.doc
- Clean the filter housing (Fig. 3-7/2) with a lint-free cleaning rag.
- Check the O-rings (Fig. 3-7/6 and Fig. 3-7/8) for further serviceability, replace the O-rings,
if required.
- Check the filter imprint of the new filter element. For permissible filter elements see
Section 6.3.
- Assemble the filter element (Fig. 3-7/1) and the contamination retainer (Fig. 3-7/4).
- Assemble the filter head ensuring that the O-rings (Fig. 3-7/6 and Fig. 3-7/8) as well as the
filter element (Fig. 3-7/1) and the filter head (Fig. 3-7/3) are properly seated.
Revision 00
- Fin Stabilizer
Maintenance Page 3-25
4506E-00_S800-517-05 Part A.doc
Fig. 3-7 Return line and leak oil line filter, hydraulic power unit
Revision 00
- Fin Stabilizer
Maintenance Page 3-26
Note!
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work when they are additionally watched by another authorized person..
See also Chapter 0, General and safety.
- Switch off the fin stabilizing system and secure it against switching on.
- Unscrew the filter head (Fig. 3-8/3) and pull the filter element (Fig. 3-8/1) out of the filter
housing (Fig. 3-8/2).
- Clean the filter element (Fig. 3-8/1) and filter head (Fig. 3-8/3) in clean fuel.
- Dry the filter element (Fig. 3-8/1) and filter head (Fig. 3-8/3) by blowing with compressed
4506E-00_S800-517-05 Part A.doc
air.
- Clean the filter housing (Fig. 3-8/2) with a lint-free cleaning rag.
- Check the O-rings (Fig. 3-8/6 and Fig. 3-8/8) for further serviceability, replace the O-rings,
if required.
- Assemble the return line filter ensuring that the O-rings (Fig. 3-8/6 and Fig. 3-8/8) as well
as the filter element (Fig. 3-8/1) and the filter head (Fig. 3-8/3) are properly seated.
- Tighten the cylinder screws (Fig. 3-8/9) uniformly in the crisscross manner.
Revision 00
- Fin Stabilizer
Maintenance Page 3-27
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Maintenance Page 3-28
Note!
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
- Switch off the fin stabilizing system and secure it against switching on.
- Unscrew the filter element (Fig. 3-9/2) from the filter head (Fig. 3-9/1) of return line filter (A-
3/225), oil is coming out, use a drip pan.
4506E-00_S800-517-05 Part A.doc
- Clean the filter head (Fig. 3-9/1) with a lint-free cleaning rag.
- Check the filter imprint of the new filter element. For permissible filter elements see
section 6.3. Provide spare filter elements in time.
- Assemble the new filter element (Fig. 3-9/2), grease the sealing (Fig. 3-9/3) with hydraulic
oil.
Revision 00
- Fin Stabilizer
Maintenance Page 3-29
4506E-00_S800-517-05 Part A.doc
1 Filter head
2 Filter element
3 Sealing
Revision 00
- Fin Stabilizer
Maintenance Page 3-30
- Switch off the fin stabilizing system and secure it against switching on.
- Unscrew the filter housing (Fig. 3-10/2) from the filter head (Fig. 3-10/3) and remove the
filter element (Fig. 3-10/1).
- Clean the filter head (Fig. 3-10/3) with a lint-free cleaning rag.
- Check the O-rings (Fig. 3-10/5 and 3-10/6) for further serviceability, replace the O-rings, if
required.
- Check the filter imprint of the new filter element. For permissible filter elements see
4506E-00_S800-517-05 Part A.doc
Section 6.3.
- Assemble the filter housing (Fig. 3-10/2) ensuring that the O-rings (Fig. 3-10/5 and 3-10/6)
as well as the filter element (Fig. 3-10/1) and the filter housing (Fig. 3-10/2) are properly
seated.
Revision 00
- Fin Stabilizer
Maintenance Page 3-31
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Maintenance Page 3-32
Note!
Only skilled workers who are specialized to work on this fin stabilizer system are qualified to do
this work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
- Visually check the crux bearings, crux, rotary vane motor, sealing and the fin for any
damage.
Revision 00
- Fin Stabilizer
Chapter 4
4506E-00_S800-517-05 Part A.doc
Troubleshooting
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-1
4 Troubleshooting
Detection and correction of faults.
The faults are analyzed and processed by the control system.
Single faults are indicated inside the Fin Control Cabinet (FCC) by indicator lamps.
Note!
For fault messages see also Technical Manual Electrical Part.
For the correct position of the Service Switches in the FCC see Technical Manual Electrical Part.
Troubleshooting for mechanical and hydraulically part see following pages Item-No. 4.1 - 4.4.1.
Note!
4506E-00_S800-517-05 Part A.doc
Only skilled workers who are specialized to work on this hydraulic system are qualified to do this
work when they are additionally watched by another authorized person.
See also Chapter 0, General and safety.
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-2
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-3
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-4
leakage
Pressure relief valve Check pressure relief valve
(A-3/14) not closed
Pressure relief valve Disassemble and check
(A-3/35) not fully closed pressure relief valve
(A-3/35)
Pressure relief valve Adjust or replace pressure
(A-3/35) misadjusted or relief valve (A-3/35)
defective
Pump sucks air due to lack - Check oil level,
of oil or leakage in suction replenish, if required
line - Determine the cause for
lack of oil
- Check suction line
and eliminate any leaks
Motor electrically Change direction of rotation
incorrectly connected and of motor
thus wrong direction of
rotation
Emergency pump defective Overhaul or replace
emergency pump
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-5
4.1.8 Motor for main pump Coupling between main Check coupling, repair or
(A-3/4) running, however, pump (A-3/4) and replace if required
the hydraulic oil is not cooled circulating pump defective
Circulating pump defective Overhaul or replace
circulating pump
Lack of cooling water, See 4.2.3
oil cooler (A-3/10)
contaminated
Pump sucks air due to lack - Check oil level,
of oil or leakage in suction replenish, if required
line - Determine the cause for
4506E-00_S800-517-05 Part A.doc
lack of oil
- Check suction line and
eliminate any leaks
4.1.9 Lubricating unit (Fig.1-9) See Item No. 4.1.3, motor See Item No. 4.1.3, motor for
does not start for main pump (A-3/4) main pump (A-3/4)
4.1.10 Lubricating unit (Fig.1-9) Return line filter (Fig.1-9/2) Clean return line filter
running, but does not contaminated,
generate the required oil Lack of oil Replenish oil and determine
flow cause for lack of oil
Pressure relief valve Replace pressure relief valve
defective (Fig.1-9/8)
Coupling defective Check coupling, repair or
replace, if required
Lubricating pump (Fig.1- Repair or replace lubricating
9/9) mechanically damaged pump
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-6
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-7
280, 281).
Check closed position of all
hand knobs.
Hydraulic fin control unit:
Check shut-off valves (A-
3/8).
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-8
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-9
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-10
Revision 00
- Fin Stabilizer
Troubleshooting Page 4-11
Revision 00
- Fin Stabilizer
Chapter 5
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Spare parts and special tools Page 5-2
Hose Assembly
1 SAE2 x 1750* A-2/27 SSK-664-1001-000-0000/27
5-5/215 Stock-No.: 167882/10/27
1 SAE2 x 1950* A-2/28 SSK-664-1001-000-0000/28
5-5/214 Stock-No.: 167883/10/28
5-1/320,321
5-10/320,321
1 4 SH 25 PP-1150 A-2/32 SSK-664-1001-000-0000/32
5-3/290,291 Stock-No.:161014/10/32
4506E-00_S800-517-05 Part A.doc
5-3/292,293
1
4 SH 32 PP-900 A-2/59 SSK-664-1001-000-0000/59
5-2/203 Stock-No.: 108603/10/59
1 SAE2-6000PSIx700* A-2/72 SSK-664-1001-000-0000/72
5-7/211,212 SSK-664-1501-000-0000/4/5
Stock-No.: 160424/10/72
1 SAE11/2-6000PSIx900* A-2/74 SSK-664-1001-000-0000/74
5-7/202 SSK-664-1501-000-0000/6
Stock-No.: 163414/10/74
1 2 SN 12 PP-500 A-2/100 SSK-664-1001-000-0000/100
5-9/288,289 Stock-No.: 108467/10/100
1 2 SN 12 PP-1300 A-2/101 SSK-664-1001-000-0000/101
5-9/286,287 Stock-No.: 162521/10/101
1 4 SH 32 PP-1200 A-2/159 SSK-664-1001-000-0000/159
5-2/203 Stock-No.: 162577/10/159
1 Cooling Water A-3/63 SSK:664-1800-201/7
Hose Assembly* 5-11/3 Stock-No.: 157999/18/7
1 GH506-20 DN31-PN350 A-4/51 SSK:601-5908/51
2xGH10235-20 x 1000 Stock-No.: 6034039/Hyd
1 2681-20 DN31-PN65 A-4/52 SSK:601-5908/52
2xGH10251-20 x 1000 Stock-No.: 6034038/Hyd
Revision 00
- Fin Stabilizer
Spare parts and special tools Page 5-3
Drawing No./
Quantity Designation Fig.
Part No.
Hose Assembly
1 GH793-16 DN25-PN175 A-4/53 SSK:601-5908/53
2xGH10249-16 x 400 Stock-No.: 6034040/Hyd
1 2681-12 DN25-PN90 A-4/55 SSK:601-5908/55
2xGH10251-16 x 1250 Stock-No.: 6034037/Hyd
Filter Element
2 0660 R 010 BN3HC A-4/190 SSK:601-5908/190
3-9/2 Stock-No.: 113167/20/190
2 0660 D 010 BH3HC A-4/297 SSK:601-5908/297
3-10/1 Stock-No.: 110181/20/297
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Spare parts and special tools Page 5-4
Drawing No./
Quantity Designation/Type Fig.
Part No.
Contact the manufacturer for original spare parts and special tools:
4506E-00_S800-517-05 Part A.doc
E-Mail: [email protected]
Revision 00
- Fin Stabilizer
Illustration Page 5-5
5.3 Illustration
4506E-00_S800-517-05 Part A.doc
1804F5-1A-turned.wmf
Revision 00
- Fin Stabilizer
Illustration Page 5-6
27 31 3.1
B1 A1
265
B3 A3
309
325
G 1/2
B2 A2
32 M G 1/4
Ø6.5
4506E-00_S800-517-05 Part A.doc
B2 A2
88
8
255
1804F5-1B.wmf
T P
3.2
P
A B
T
a b
P
A B
T
a b
P
X
A B
T
a b
P
A B
T
a b
T P
1804F5-1BB.wmf
Fig. 5-1B Valve Group 1, normal operation, directional valves
Revision 00
- Fin Stabilizer
Illustration Page 5-7
Revision 00
- Fin Stabilizer
Illustration Page 5-8
Only skilled workers who are specialized to work on this hydraulic system are qualified to use
the service connection and to operate valves.
4506E-00_S800-517-05 Part A.doc
4600F5-2.doc
0700F5-2(2).tif
Fig. 5-2 Return line filter connection
Revision 00
- Fin Stabilizer
Illustration Page 5-9
operate the valves, to change the setting point of the pressure relief valve and to change the
filter elements.
Revision 00
- Fin Stabilizer
Illustration Page 5-10
View Z:
278
26
292
B1
293
279
4506E-00_S800-517-05 Part A.doc
1804F5-3A.wmf
18 28
276
B1 A1
291
290
277
18
28
Z
1804F5-3B.wmf
Fig. 5-3 Housing and extending cylinder connection
Revision 00
- Fin Stabilizer
Illustration Page 5-11
Revision 00
- Fin Stabilizer
Illustration Page 5-12
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Illustration Page 5-13
T2
203 B1
T2
16 T2
23
P
T
24
4506E-00_S800-517-05 Part A.doc
WA 215 214
WE
1804F5-5.wmf
Revision 00
- Fin Stabilizer
Illustration Page 5-14
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Illustration Page 5-15
1 Oil tank
2 Oil dipstick
3 Oil filler and air breather
4 Lubricating pump
4.1 Elastic coupling
5 E-motor
6 Lubricating unit, design 2
7 Level switch
8 Pressure relief valve, setting point 0.8 bar
11 Check valve, pilot operated
14 Test connection, venting connection
27 Test connection, venting connection
30 Return line filter
197 Filter element
Revision 00
- Fin Stabilizer
Illustration Page 5-16
T2
A
P
T2
B2 B2 T2
A2
A2
B3
T
A3
A1
4506E-00_S800-517-05 Part A.doc
A3
B3
1804F5-7.wmf
1 Swivel device
8 Shut-off valve, pressure connection, A2, B2 ............................ A-2/205
202 Hose assembly, return line connection, T2 ................................ A-2/74
211 Hose assembly, pressure connection, B2 .................................. A-2/72
212 Hose assembly, pressure connection, A2 .................................. A-2/72
>18< Test connection, venting connection
Caution: Approx. 160 bar / 16 MPa
Further information: See Fig. A-2, Arrangement of Hydraulic Pipes
See Fig. A-3, Hydraulic Diagram
Revision 00
- Fin Stabilizer
Illustration Page 5-17
2 203
202
28,B2 18
28,P 18
18 18
1804F5-8A.wmf
4506E-00_S800-517-05 Part A.doc
T2 B2 A2
B2
A2
T
P
T2
8 B2
A1
T
202
P
X A2
1804F5-8B.wmf
Fig. 5-8 Hydraulic Fin Control Unit Connection
Revision 00
- Fin Stabilizer
Illustration Page 5-18
Revision 00
- Fin Stabilizer
Illustration Page 5-19
B3
294 274 289 272 287
286
299
288
273,B3
275,A3
268
269
1804F5-9A.wmf
4506E-00_S800-517-05 Part A.doc
294
A 286
B2 T2
A2
A2 287
B3
A3
269
299
A3
B3
299
268
1804F5-9B.wmf
Fig. 5-9 Locking Cylinder Connection
Revision 00
- Fin Stabilizer
Illustration Page 5-20
Revision 00
- Fin Stabilizer
Illustration Page 5-21
4506E-00_S800-517-05 Part A.doc
1804F5-10A-turned.wmf
Revision 00
- Fin Stabilizer
Illustration Page 5-22
B1 A1
G 1/2
B3 A3
234
250
M G 1/4
265E
B2 A2
4506E-00_S800-517-05 Part A.doc
Ø6.5
8
88
245
32E
1804F5-10B.wmf
3.2 T P
3.2
P
A B
T
a b
P
A B
T
X
a b
P
A B
T
a b
T P
1804F5-10BB.wmf
Fig. 5-10B Valve Group 2, emergency operation, valves
Revision 00
- Fin Stabilizer
Illustration Page 5-23
283 Shut-off valve, return line connection, TV, valve group 2 .................................A-2/331
284 Shut-off valve, pressure oil connection, PV, valve group 1 ..............................A-2/316
285 Shut-off valve, return line connection, TV, valve group 1 .................................A-2/316
299 Throttle/check valve, A3, B3 ..............................................................................A-2/109
Revision 00
- Fin Stabilizer
Illustration Page 5-24
Kühlwasseranschluß
COOLING WATER CONNECTION
Raccord de l'eau refroidissement
15
B 14
3-4 M
1
C
10
CWL
2
4506E-00_S800-517-05 Part A.doc
6 13
3
12
B
Kühlwasseranschluß
COOLING WATER CONNECTION
Raccord de l'eau refroidissement
Einbaulage: senkrecht
ASSEMBLY POSITION: VERTICAL
Pose: vertical
17
4
5
11
A
1804F5-11.wmf
Revision 00
- Fin Stabilizer
Illustration Page 5-25
1 Header tank
2 Pipe connection
3 Cooling water hose assembly
4 Shut-off valve, normally open
5 Shut-off valve, normally closed
6 Shut-off valve, normally closed
A Fin Unit
B Hydraulic Power Unit
4506E-00_S800-517-05 Part A.doc
C Header Tank
Revision 00
- Fin Stabilizer
Illustration Page 5-26
10
4506E-00_S800-517-05 Part A.doc
1804F5-12.wmf
Revision 00
- Fin Stabilizer
Chapter 6
Service Information
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Service information Page 6-1
6 Service information
6.1 Hydraulic system
4506E-00_S800-517-05 Part A.doc
Revision 00
- Fin Stabilizer
Service information Page 6-2
Revision 00
- Fin Stabilizer
Service information Page 6-3
Note!
Provide spare filter elements in time.
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-1
Chapter 7
4506E-00_S800-517-05 Part A.doc
7 Appendix / Drawings
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-2
Consumption normally none Verbrauch normalerweise keiner DIN 51 517 dann einmal
ISO VG 100 once every year
Reserve (recomm.) l 100 100 100 100 100 100 100 100 Vorrat (empfohlen) l 100 100 100 100 100 100 100 100 ISO VG 100 jährlich
DIN 51 519
DIN 51 519
Bearings electric motors After 2000 Lager der Elektromotoren Nach 2000
System C
Sea water
Total capacity kg 1 1 1 1 1 1 1 1 service hours, Gesamtinhalt kg 1 1 1 1 1 1 1 1 Seewasser- Betriebsstunden,
resistant
but at least beständiges mindestens
Consumption normally none ball bearing Verbrauch normalerweise keiner
once every Wälzlagerfett einmal alle
Reserve (recomm.) kg 1 1 1 1 1 1 1 1 grease Vorrat (empfohlen) kg 1 1 1 1 1 1 1 1
2 years 2 Jahre
Attention: Above capacities apply to a complete stabilizer of 2 fin units. Bemerkung: Die obigen Werte sind die Gesamtmengen für eine kompl. Stabilisatoranlage mit 2 Flosseneinheiten.
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-3
AGIP BP Castrol CEPSA Chevron DEA Esso Fina Gulf Mobil Q8 Shell TOTAL Vickers
ENERGOL
HLP-HM 68 GULF
System A
DEA
ENERGOL MECHANISM
CHEVRON ASTRON HLP 68 FINA MOBIL Q8-OIL
THB 77 HYSPIN DELFIN H 5 NUTO H 68 LP 52, (68) SHELL TELLUS TOTAL AZOLLA
AGIP OTE 68 MECHANISM DEA HYDRAN 68 DTE 16M HÄNDEL HYDROX 550
BARTRAN AWH-M68 (DELFIN H 68) * UNIVIS N 68 GULF OIL T 68 ZS 68
LPS 68 ASTRON ISO HVLP ISO VG 68
HV 68 HARMONY
HVLP 68
BARTRAN 54 AW (68)
SHF-HV 68
System B
GULF SHELL
SPHEEROL
AGIP ENERGREASE DURA-LITH GLISSANDO EP2 BEACON 3 FIN GREASE CROWN Q8 GREASE ALVANIA TOTAL
EPL 2 ARGA L 2 MOBILUX 2
GR MU 3 LS 3 GREASE EP 2 CARON 2 BEACON 2 MARSON HTL 2 GREASE REMBRANDT 3 GREASE MULTIS
GREASE
NO. 2 R3
* ISO VG
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-4
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-5
4506E-00_S800-517-05 Part A.doc
1804FA-1A.tif
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-6
38
4506E-00_S800-517-05 Part A.doc
53
42 37 49 34 40 39 30 31
1804FA-1B.tif
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-7
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-8
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-9
A3
12 B3
T B2 501
4506E-00_S800-517-05 Part A.doc
T P
A2 P A2
B2 T
B1 A1 P
T
P
A1
B1
10
1
1804FA-2A.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-10
72 74
Fig. 5-4 25
X A
T2
Fig. 5-2
294
4506E-00_S800-517-05 Part A.doc
A
17 P
T2 T2
B2
11 B2 T2
A2
A2
B3
T
A3
T2
B1
Fig. 5-3 A1
T2 Z
160
A Fig. 5-3 A3
P
T
B3
B1
75
5 12 14 15 27 28 32 32
1804FA-2B.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-11
Detail T:
302
T U
B2 A2
18 (43),321
B2 A2
320,(43) 18
TV PV
103
316
B2 A2
323
4506E-00_S800-517-05 Part A.doc
T
V 316
331
P
Fig. 5-1A
Fig. 5-1B
Detail U:
322
352 316
109
Detail V:
(43) 18 321 18 (43),503
Fig. 5-6
TV PV 103
A2
501
B2 Fig.5-10A
Fig.5-10B
331
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-12
A-A
203 208, 18 (43) A2 Detail X:
32
15
602
19 P
B2 18 (43),208 T Fig. 5-2
68
401
Fig. 5-8
T2
207 207
(43) 18 P (43) 18 T
4506E-00_S800-517-05 Part A.doc
View Z:
T2 B2 A2
21
27 28
205 411
22
T
P 16
B2
A2
T 59
T2
P 32 T2
606
T2
159
A2 A1
B2
32
B2 20
T
202
P
604 (43) 18
Fig. 5-8
68 68,22 11 13 19 A2 7.8 Fig. A-2, Arrangement of Hydraulic Pipes (4/4)
17
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-13
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-14
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-15
18 Test/venting connection
19 Pressure connection A2
20 Pressure connection B2
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-16
183 A2 T 3E
227 227 B2
183 203 281
2E PV
26 26 3E TV
203 13 8 VALVE GROUP 1
HYDRAULIC POWER UNIT HYDR. FIN CONTROL UNIT
31 27 3
2 221 222 B1 A
19 20 A1 B
28
18 18 18 a b
28
18
28 28 P T
A B
S U
23 B3 A 265
18 P T A3 B
XY 282
a b
21 28 P T
283
28 32
215 B2 A
24 B
214 18 A2
22 a b
15 P T
WE
63 39 23
WA 63 285
B2 A
14 A2 B
284
a b
18
28 P T
16 T P
62 TV 3 2 PV
16
13 12
1804FA-3A_01 wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-17
T3
G1"
1
19 p0=60bar
19.1 19.2
P1 SAE 1 1/2
48
35 100 bar NG25
NG20 266
B DF 660
P G1 1/2
120
T4 G 1 1/4 P2 SAE 1 1/2 Y T5 SAE 2 G11/2" WE
266.1
10 G11/2" WA
G1 1/2 m
A
10
51 46
DN32 SAE1 1/4" DN31 DN32
47 Ø3,0 6000PSI 180
67 59 180
B1 B MB
180
52 55
52
T2 G1" DN31
251 DN31
DN25
252 SAE1 1/4"
250 P
T2 G1"
20
4 3000PSI
SAE3" 11
NG660
M 6
A
G3/4
267
RF 110
22 3000PSI S SAE2"
-S* A 3000PSI
60 11.1 S MS K1 K2 T R(L)
15 -..
-S* 254 267.1
-S* SAE3"
9 min
max
-M*
-.. M B
10
m
-.. 3000PSI
DN80 54 DN50 56
G3/4
10
m
257 G3 B
5 53
255 7
26,9x2,3
NG63 DN25 153
1000 cdm
S P
F2
G 1 1/2
258
1804FA-3B_01 wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-18
4 Main pump
5 Emergency pump
6 Circulating pump
7 Oil tank
9 Oil dipstick
10 Oil cooler
11 Return line filter
11.1 Electrical contamination alarm
12 Check valve, cartridge type
13 Shut-off valve
14 Pressure relief valve, consisting of 14.1, 14.2, 14.3
14.1 Control cover
14.2 Directional valve, pilot control valve
14.3 Directional cartridge valve
15 Level switch
17 Throttle/Isolating valve
18 Pressure gauge
4506E-00_S800-517-05 Part A.doc
19 Bladder accumulator
20 Thermometer and temperature switch
22 Oil filler and air breather
35 Pressure relief valve
38 Pressure switch
41 Shut-off valve
42 Discharge valve
43 Pressure relief valve
46 Check valve
47 Check valve
48 Check valve, cartridge type
51 Hose assembly, pressure oil, main pump
52 Hose assembly, pressure oil, circulating pump, flushing oil, main pump
53 Hose assembly, pressure oil, emergency pump
54 Compensator, suction pipe, main pump
55 Hose assembly, flushing oil, main pump
56 Compensator, suction pipe, circulating pump
60 Emergency pump unit
67 Orifice
87 Orifice
100 Pump set, main pump, circulating pump
115 Junction box E
120 Connecting block
153 Shut-off valve, drain valve
180 Test connection
190 Filter element, return line filter
191 Anodes for oil cooler
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-19
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-20
18 Test/Venting connection
21 Pressure connection P
4506E-00_S800-517-05 Part A.doc
22 Pressure connection T
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-21
4506E-00_S800-517-05 Part A.doc
1804FA-4E.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-22
C
254
13
T3 B
A
4506E-00_S800-517-05 Part A.doc
ca.1930
220, 220.1 18 17 20 53 5 255, 257
90 1832
90 2012
ca.2360
1804FA-4.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-23
47
View A View B
F2 28
4506E-00_S800-517-05 Part A.doc
D D
WA
G1 1/2" 15 ca.202
19 19
WE
G1 1/2" 14 T2 P T 965 50
16 21 22 1065
ca. 1470
1804FA-4A-B.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-24
View C
250 251, 252 52 4 52 100 6
35
4506E-00_S800-517-05 Part A.doc
38
51
42
43
13, 87 55
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-25
View D
52
52
4506E-00_S800-517-05 Part A.doc
56
54
258
165 4 x Ø13
200 7 46 10, 191 67
1804FA-4C.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-26
120
4506E-00_S800-517-05 Part A.doc
T3 MP T5
12 38 P1 P2 35 14
43 P3
48
42
P4 41
13
T2
Sp2
T1
Sp1
18
P
1804FA-4ValveBloc.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-27
Legend of Fig. A-5 and A-6 (7.17 and 7.18), Mounting of fin unit and dismantling of fin
1 Fin
2 Crux
3 Rotary vane motor
4 Fin box
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-28
19.300 off CL
17.278 off CL
2
4506E-00_S800-517-05 Part A.doc
632
185 0
0
188
0
3174
20°
2541
4
1
BASE
1804FA-5.wmf
Revision 00
- Fin Stabilizer
Appendix / Drawings Page 7-29
3
2
4506E-00_S800-517-05 Part A.doc
6,32
185 m
0
188
0
~3
m
4
1
BASE
~ 0,9 m
1804FA-6.wmf
Revision 00
- Fin Stabilizer
Notes
4506E
Notes:
4506E-00_S800-517-05 Part A.doc
Revision 00