0% found this document useful (0 votes)
53 views

METSEPM5560: Product Data Sheet

This document provides product specifications for the PowerLogic PM5560 power meter. It is a 3-phase power meter with 4 digital inputs and 2 digital outputs that can measure up to the 63rd harmonic. Key features include Ethernet and RS485 communication, IEC 62053-22 class 0.2S accuracy for energy measurement, LCD display, and IP52 protection for indoor use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
53 views

METSEPM5560: Product Data Sheet

This document provides product specifications for the PowerLogic PM5560 power meter. It is a 3-phase power meter with 4 digital inputs and 2 digital outputs that can measure up to the 63rd harmonic. Key features include Ethernet and RS485 communication, IEC 62053-22 class 0.2S accuracy for energy measurement, LCD display, and IP52 protection for indoor use.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Product data sheet METSEPM5560

Characteristics PM5560 Meter, 2 ethernet, up to 63th H, 1,1M


4DI/2DO 52 alarms

Main
Range PowerLogic
Product name PowerLogic PM5000
Device short name PM5560
Product or component Power meter
type

It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products with respect to the relevant specific application or use thereof.
Complementary
Power quality analysis Up to the 63rd harmonic
Metering type Calculated ground current
Measured neutral current
Device application WAGES metering
Gateway

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications.
Multi-tariff
Power monitoring

Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the information contained herein.
Type of measurement Energy
Active and reactive power
Voltage
Current
Frequency
Power factor
Supply voltage 125...250 V DC
100...480 V AC (45...65 Hz)
Network frequency 60 Hz
50 Hz
[In] rated current 5A
1A
Type of network 3P + N
1P + N
3P
Power consumption in VA <= 10 VA at 480 V
Ride-through time 35 ms 120 V AC typical
129 ms 230 V AC typical
Display type Backlit LCD
Display resolution 128 x 128 pixels
Sampling rate 128 samples/cycle
Measurement current 5...10000 mA
Analogue input type Current (impedance 0.3 mOhm)
Voltage (impedance 5 MOhm)
Measurement voltage 20...400 V AC 45...65 Hz between phase and neutral
20...690 V AC 45...65 Hz between phases
Frequency measurement range 45...65 Hz
Number of inputs 4 digital

Sep 17, 2019


1
Measurement accuracy +/- 0.5 % apparent power
+/- 0.05 % frequency
+/- 0.2 % active energy
+/- 1 % reactive energy
+/- 0.2 % active power
+/- 0.1 % voltage
+/- 0.05 % power factor
+/- 0.15 °C current
Accuracy class Class 0.2S (active energy according to IEC 62053-22)
Number of outputs 2 digital
Information displayed Tariff 8
Communication port protocol Modbus RTU and ASCII 2 wires, : 9.6, 19.2 and 38.4 kbauds, even/odd or none,
insulation: 2500 V
JBUS
Modbus TCP/IP : 10/100 Mbit/s, insulation: 2500 V
Ethernet Modbus TCP/IP daisy chain
BACnet IP
Communication port support RS485
Ethernet
Communication gateway Ethernet/serial
Data recording Data logs
Alarm logs
Min/Max of instantaneous values
Time stamping
Event logs
Maintenance logs
Memory capacity 1.1 MB
Web services Web server
Alarm notification by e-mail
Diagnostic via predefined web pages
Real time viewing of data
Ethernet service SNMP-Traps
SNTP client
Connections - terminals Voltage circuit: 4 screw terminal block
Control circuit: 2 screw terminal block
Current transformer: 6 screw terminal block
RS485 link: 4 screw terminal block
Digital input: 8 screw terminal block
Digital output: 4 screw terminal block
Ethernet network: 2 RJ45 connector
Mounting mode Flush-mounted
Mounting support Framework
Standards EN 50470-3
UL 61010-1
EN 50470-1
ANSI C12.20
IEC 62053-24
IEC 62053-22
IEC 60529
Product certifications CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
BTL
Width 96 mm
Depth 72 mm
Height 96 mm
Product weight 450 g

2
Environment
Electromagnetic compatibility ● conducted and radiated emissions class class B, conforming to EN 55022
● limitation of voltage changes, voltage fluctuations and flicker in low-voltage,
conforming to IEC 61000-3-3
● limits for harmonic current emissions class class A, conforming to IEC
61000-3-2
● conducted RF disturbances class level 3, conforming to IEC 61000-4-6
● magnetic field at power frequency class level 4, conforming to IEC 61000-4-8
● electrostatic discharge class level 4 (8 kV ), conforming to IEC 61000-4-2
● radiated radio-frequency electromagnetic field immunity test, conforming to IEC
61000-4-3
● electrical fast transient/burst immunity test class level 4, conforming to IEC
61000-4-4
● surge immunity test class level 4, conforming to IEC 61000-4-5
● voltage dips and interruptions immunity test, conforming to IEC 61000-4-11
IP degree of protection IP52 (front) conforming to IEC 60529
IP30 (body) conforming to IEC 60529
Relative humidity 5...95 % 50 °C
Pollution degree 2
Ambient air temperature for operation -25...70 °C
Ambient air temperature for storage -40...85 °C
Operating altitude 3000 m

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW)
Compliant  - since  1340  -  Schneider Electric declaration of conformity Schnei-
der Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Product environmental profile
Available Product Environmental Profile
Product end of life instructions
Available End Of Life Information