Lecture Notes Transient & Power Factor Correction
Lecture Notes Transient & Power Factor Correction
Solutions
Transients
3
Power Quality Causes and
Solutions
Transients
10
Power Quality Causes and
Solutions
In the figure shown, the first arrester is connected from the line to the neutral-ground
bond at the service entrance. It limits the line voltage V1 from rising too high relative
to the neutral and ground voltage at the panel. When it performs its voltage-limiting
action, it provides a low-impedance path for the surge current to travel onto the
ground lead.
The first arrester at the service entrance is electrically too remote to provide
adequate load protection.
Therefore, a second arrester is applied at the load, directly across the insulation to
be protected.
This solution has multiple benefits including providing correction for the displacement
power factor, controlling harmonic distortion levels within the facility, and limiting the
concern for magnified capacitor-switching transients.
- Paragraph taken from Power Quality Book, CRC Press 2002, C. Sankaran
--
--
How to improve PF ?
TWO (2) ways:
How to improve PF ?
1)Installing capacitors (kVAR generators)
How to improve PF ?
How to improve PF ?
How to improve PF ?
2) Minimizing the operation of idling or
lightly loaded motors
- Fully loaded motors generally have a power factor of about 80%.
However, if the motor is under loaded, the fraction of reactive power
(for the coil) to actual power (for mechanical work) increases and the
power factor decreases.
Example :
The highest power factor registered during the period for which we were
supplied with electricity data was for March 2000, when the plant power factor
was 74% and the peak power was 594 kW. If the power factor during this
month were corrected to 97%, the power factor during the rest of the year
would never exceed 97%. Determine the size of capacitor to achieve the
targeted PF.
Example PF calculation:
Cosθ = kW / kVA
θ = Cos-1 (PF)
θ= Cos-1 (74%) = 42.27 o
The reactive power was about:
Tanθ = kVAr / kW
kVAr = kW x tanθ
kVAr = 594 kW x tan (42.27) = 540 kVAr
Example PF calculation:
If the power factor were increased to 97%, the reactive power would be about:
Cosθ = kW / kVA
θ = Cos-1 (PF)
θ = Cos-1 (97%) = 14.07 o
kVAr = kW x tanθ
kVAr = 594 kW x tan (14.07) = 149 kVAr
Thus, the amount of capacitance required to boost your power factor from 74%
to 97% during March 2000 would be about:
Example PF calculation:
Example PF calculation:
Example PF calculation:
Example PF calculation: