Spaj 115 C Restricted Earth-Fault and Residual Earth-Fault Relay
Spaj 115 C Restricted Earth-Fault and Residual Earth-Fault Relay
B
∆I
I
2
I n = 1A 5A ( I o ) f n = 50Hz I o ∆I o IRF
5
I n = 1A 5A (∆I o ) 60Hz
SPAJ 115 C
STEP 2.5
80...265V –
~ ∆I o>
U aux [%]
18...80V – In STEP
0.5 5.0
SPCJ 2C30
20
REGISTERS I o>
[%] SG1
0 0 0 0 In 1
5.0 40 2
3
1 ∆ I o /I n [ % ] 4
5
2 I o /I n [ % ] 0.6 6
3 n (∆ I o> ) SGR 7
t o>[s] 8
4 n (I o> ) 1
k 0 1
2 0.1 1.0
5 t / t o> [ % ] 3
4
5 RESET
6
7
8
0 1
∆I o> I o>
1411
1304
Restricted earth-fault and residual earth-fault relay SPAJ 115 C 1MRS 750658-MUM EN
Combined restricted earth-fault and residual earth-fault
relay module SPCJ 2C30 1MRS 750659-MUM EN
General characteristics of C type relay modules 1MRS 750328-MUM EN
Features Sensitive restricted earth-fault protection stage Serial interface for two-way data communica-
for fast, selective earth-fault protection tion over fibre-optic bus between relay level and
superior system levels
Sensitive definite time or inverse time earth-
fault stage for back-up residual earth-fault pro- High immunity to electrical interference and
tection robust aluminium case to class IP54
Output relay functions freely configurable for Continuous self-supervision of hardware and
desired relay operations software, including auto-diagnostics
Flexible adaptation of the relay to a certain Powerful optional software support for setting,
application reading, copying and recording relay parame-
ters
Accurate settings and stable functions due to
fully digital relay design The relay is a member of the SPACOM product
family, which is compatible with PYRAMID™,
Local numerical display of setting values, meas- the coordinated protection and control concept
ured values and recorded fault values of ABB.
Application The combined restricted earth-fault and re- relay contains two energizing input circuits, that
sidual earth-fault relay SPAJ 115 C is intended is a differential earth-fault current circuit and a
to be used for the earth-fault protection of residual earth-fault current circuit.
power generators, motors and transformers. The
2
Principle of The combined restricted earth-fault and re- The start current of the restricted earth-fault
function sidual earth-fault relay SPAJ 115 C is a second- stage is set so high, that the stage cannot operate
ary relay which measures two energizing cur- on currents caused by external faults into the
rents; the differential current ∆I0 and the re- differential current circuit.
sidual current I0. When an earth-fault is de-
tected the relay operates, alarms and trips the When an earth-fault appears inside the area of
circuit breaker, according to the settings and protection, both transformers tend to feed cur-
configuration of the relay. rent into the differential current circuit and the
stage operates. To keep the resistance of the
The differential current is formed with an exter- secondary circuit as low as possible, the sum-
nal circuit, for instance the one shown in Fig. 2. ming point for the currents should be located as
close to the current transformers as possible.
The main earth-fault protection is formed by
the restricted earth-fault current stage ∆I0, which The back-up earth-fault protection is formed by
operates instantaneously, when the differential the residual current stage I0>, which can be
current exceeds the set start value of the re- given definite time or inverse time characteris-
stricted earth-fault stage. The restricted earth- tic.
fault stage operates exclusively on earth-faults
inside the area of protection. The area of protec- When the residual current exceeds the set star
tion is the area limited by the phase current value of the residual current stage I0>, the re-
transformers and the current transformer of the sidual current stage starts. After the set operate
neutral earthing circuit. The operation of the time t0> at definite time operation or the calcu-
restricted earth-fault stage on faults outside the lated operate time at inverse time operation the
area of protection is prevented with a stabilizing stage operates delivering a trip signal.
resistor, which is connected in series with the
matching transformer of the relay, see Fig. 2. When inverse time characteristic has been se-
lected four time/current curve sets according to
The operation of the restricted earth-fault stage IEC 60255 and BS 142 are available. The curve
exclusively on faults inside the area of protection sets are referred to as "Normal inverse", "Very
is based on the fact, that the impedance of a inverse", "Extremely inverse" and "Long-time
transformer decreases as the transformer is satu- inverse".
rated. The reactance of the excitation circuit of
a fully saturated transformer is zero and in these The start signal of the relay, obtainable as a
cases the impedance is composed purely of the contact function, can, for example, be used as a
resistance of the coil. Under the influence of the blocking signal for other protection relays.
stabilizing resistor in the differential current
circuit the secondary current of the non-satu- The relay is provided with one optically isolated
rated transformer is forced to flow through the control input, which can be used as a blocking
secondary circuit of the saturated transformer. input.
TRIP 1
∆ Io
INSTANTANEOUS RESTRICTED
87N
EARTH-FAULT PROTECTION STAGE
TRIP 2
Io
DEFINITE TIME OR INVERSE TIME
51N SIGNAL 1
NEUTRAL EARTH-FAULT STAGE
START 1
BLOCKING OF EITHER ONE OR BOTH
EARTH-FAULT PROTECTION STAGES
IRF
Fig. 1. Protection functions of the combined restricted earth-fault and residual earth-fault relay
SPAJ 115 C. The encircled numbers refer to the ANSI (=American National Standards Institute)
number of the concerned protection function.
3
Connections
L1
L2
0 -
L3
- Ι
I
+
0
+
Rx Tx
SPA-ZC_
+ (~)
Ru Uaux
- (~)
≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
∆Io> TS1
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 2. Connection diagram for the combined restricted earth-fault and residual earth-fault relay
SPAJ 115 C
4
25 61
Serial Port
26 62
SPA
27 65
37 66
38 68
39 69
Made in Finland
80
81
77
70 78
71 10
72 11
B470703
Fig.3. Rear view of the restricted earth-fault and residual earth-fault relay SPAJ 115 C.
Contacts Function
The combined restricted earth-fault and re- on the rear panel of the relay. The opto-con-
sidual earth-fault relay SPAJ 115 C connects to nectors of the fibre-optic cables are plugged into
the fibre-optic data communication bus by means the counter connectors Rx and Tx on the bus
of the bus connection module SPA-ZC 17 or connection module. The selector switch for the
SPA-ZC 21. The bus connection module is mode of operation of the bus connection mod-
fitted to the D-type connector (SERIAL PORT) ule is to be set in position "SPA".
5
Configuration of The trip signal of the ∆I0> stage is firmly wired addition, the following functions can be se-
output relays to output relay A and the trip signal of the I0> lected with the switches of the SGR switchgroup
stage is firmly wired to output relay B. In on the front panel:
SGR/2 Routes the start signal of the I0> stage to output relay D 1
SGR/4 Routes the operate signal of the I0> stage to output relay D 1
SGR/5 Routes the operate signal of the I0> stage to output relay C 1
SGR/6 Routes the operate signal of the I0> stage to output relay A 1
SGR/7 Routes the operate signal of the ∆I0> stage to output relay C 1
SGR/8 Routes the operate signal of the ∆I0> stage to output relay B 1
The circuit breakers can be directly controlled output relay and two separate circuit breakers
with output relay A or output relay B. Thus can be controlled with the same earth-fault
either operation stage may have its own trip relay.
6
Start and B
with the RESET push-button. An unreset
∆I
operation 2
I indicator does not affect the operation of the
indicators I n = 1A 5A ( I o ) f n = 50Hz
5
I o ∆I o IRF relay.
I n = 1A 5A (∆I o ) 60Hz
SPAJ 115 C 2. The yellow LEDs (∆I0 and I0) on the upper
80...265V –
~ ∆I o>
STEP 2.5 black part of the front plate indicate, when lit,
18...80V – U aux In
[%]
0.5 5.0
STEP
that the value of the energizing current of the
SPCJ 2C30
concerned protection stage is being dis- played.
20
REGISTERS I o>
[%] SG1
0 0 0 0 In
5.0 40
1
2
3
3. The red IRF indicator of the self-supervision
∆ I o /I n [ % ]
1
2 I o /I n [ % ] 0.6
4
5
6
system indicates, when lit, that a permanent
3
4
n (∆ I o> )
n (I o> )
SGR
1
t o>[s]
7
8 internal relay fault has been detected. The
k 0 1
5 t / t o> [ % ]
2
3
4
0.1 1.0
fault code appearing on the display once a
RESET
5
6
7
fault has been detected should be recorded
0 1
8
and notified when service is ordered.
∆I o> I o>
1411
1304
Power supply The combined power supply and I/O module The power supply and I/O module is available
and I/O module (U2) is located behind the system front panel of in two versions which have different input volt-
the protection relay and can be withdrawn from age ranges:
the relay case after removal of the system front
panel. The power supply and I/O module incor- - type SPTU 240S1 Uaux = 80...265 V ac/dc
porates a power unit, four output relays, the - type SPTU 48S1 Uaux = 18...80 V dc
control circuits of the output relays and the
electronic circuitry of the external control in- The input voltage range of the power supply and
put. I/O module incorporated in the relay on deliv-
ery is marked on the system front panel of the
The power unit is transformer connected, that relay.
is, the primary circuit and the secondary circuits
are galvanically isolated. The primary circuit is
protected by a slow 1 A fuse F1, placed on the
PC board of the module. When the power
source operates properly, the green Uaux LED
on the front panel is lit.
7
Technical data Energizing inputs 1A 5A
(modified 2002-04) Terminals 25–27, 37–39 25–26, 37–38
Rated current In 1A 5A
Thermal withstand capability
Continuous carry 4A 20 A
Make and carry for 10 s 25 A 100 A
Make and carry for 1 s 100 A 500 A
Dynamic current withstand capability,
half-wave value 250 A 1250 A
Input impedance <100 mΩ <20 mΩ
Rated frequency fn acc. to order 50 Hz or 60 Hz
Signalling contacts
Terminals 70-71-72, 77-78, 80-81
Rated voltage 250 V ac/dc
Carry continuously 5A
Make and carry for 0.5 s 10 A
Make and carry for 3 s 8A
Breaking capacity for dc, when the signalling
circuit time constant L/R ≤ 40 ms,
at the signalling voltages
- 220 V dc 0.15 A
- 110 V dc 0.25 A
- 48 V dc 1A
8
Combined restricted earth-fault and residual earth-fault relay module SPCJ 2C30
Restricted earth-fault current stage ∆I0>
Start current ∆I0>, setting range 0.5...5% x In
Operate time 35 ms
Residual earth-fault current stage I0>
Start current I0>, setting range 5…40% x In
Selectable operation characteristic
- definite time characteristic
- operate time t0> 0.1…100 s
- inverse definite minimum time (IDMT) characteristic
- curve sets acc. to IEC 60255-3 and BS 142 Normal inverse
Very inverse
Extremely inverse
Long-time inverse
- time multiplier k 0.05...1.00
Data communication
Transmission mode Fibre-optic serial bus
Data code ASCII
Selectable data transfer rates 300, 1200, 2400, 4800 or 9600 Bd
Fibre-optic bus connection module,
powered from the host relay
- for plastic fibre cables SPA-ZC 21 BB
- for glass fibre cables SPA-ZC 21 MM
Fibre-optic bus connection module,
powered from external power source
- for plastic fibre cables SPA-ZC 17 BB
- for glass fibre cables SPA-ZC 17 MM
Insulation Tests *)
Dielectric test IEC 60255-5 2 kV, 50 Hz, 1 min
Impulse voltage test IEC 60255-5 5 kV, 1.2/50 µs, 0.5 J
Insulation resistance measurement IEC 60255-5 >100 MΩ, 500 Vdc
Environmental conditions
Specified ambient service temperature range -10...+55°C
Long term damp heat withstand acc. to IEC 60068-2-3 <95%, +40°C, 56 d/a
Relative humidity acc. to IEC 60068-2-30 93...95%, +55°C, 6 cycles
Transport and storage temperature range -40...+70°C
Degree of protection by enclosure
for panel mounted relay IP 54
Weight of relay including flush mounting case 3.0 kg
*) The tests do not apply to the serial port, which is used exclusively for the bus connection module.
9
Current The sensitivity and reliability of a resistor-stabi- Ikmax = Maximum through-fault current, for
transformer lized restricted earth-fault protection depends which the relay must not operate
requirements to a great extent on the current transformers to Rin = Resistance of the CT secondary circuit
be used. The number of turns of all the current Rm = Total resistance of the longest measur-
transformers of the same differential circuit ing circuit (to and from)
must be equal. n = CT transforming ration
10
Examples of
L1
application L2
L3
Example 1. TRIPPING OF EXCITATION
Generator earth- CIRCUIT BREAKER AND
SHUT DOWN OF PRIME
fault protection MOVER
TRIPPING OF
GENERATOR
CIRCUIT
BREAKER
Rx Tx
SPA-ZC_
Ru
Ir + (~)
Iu Uaux
- (~)
5A
1A
≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
TS1
∆Io>
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 5. Generator earth-fault protection using the restricted earth-fault and residual earth-fault relay
SPAJ 115 C. The selector switch positions are shown in the table on the following page.
The restricted earth-fault stage ∆I0> acts as main ers, the current flows through the current trans-
earth-fault protection. The residual earth-fault formers and causes no relay operation. When
stage I0> acts as busbar earth-fault protection the earth-fault arises inside the area of protec-
and back-up earth-fault protection for the net- tion the current transformers feed current
work. through the differential current circuit and the
relay operates.
The stability of the restricted earth-fault protec-
tion stage is based on the fact that the impedance An external stabilizing resistor Rs is needed in
of a current transformer decreases when the the differential current measuring circuit. The
transformer saturates. The reactance of the exci- purpose of the stabilizing resistor is to prevent
tation circuit of a fully saturated current trans- the relay from operating on faults outside the
former is zero and thus the impedance is purely area of protection. The short time power with-
composed of the winding resistance. The stabi- stand capability of the stabilizing resistor must
lizing resistor in the differential current circuit be high enough to stand for the power appearing
forces the secondary current of the unsaturated in the differential current circuit. The most
current transformer to flow through the second- suitable resistor type is an open wire-wound
ary circuit of the saturated current transformer. resistor.
The start current of the restricted earth-fault
stage is set so high, that the protection does not The purpose of the voltage dependent resistor is
operate on currents induced in the circuit dur- to prevent the voltage from exceeding the insu-
ing faults outside the zone of protection. lation voltage level during in-zone faults. The
voltage dependent resistor must be so selected
When the earth-fault appears outside the zone that the current through the resistor at the
of protection limited by the current transform- stabilizing voltage level is as low as possible.
11
Current transformers with the same transform- The excitation current Ie corresponding to the
ing ratios and equal numbers of winding turns stabilizing voltage Us is determined either from
are selected. In order to minimize the length of the excitation curves provided by the CT manu-
the CT secondary circuits the summing point of facturer or by assuming a linear excitation curve
the secondary currents is to be located as close for voltage values below the knee-point voltage.
to the CT terminals as possible.
The value of the stabilizing resistor can be
The calculations for the restricted earth-fault calculated from the expression:
protection are performed using an iteration
Us
method. First the current transformers are de- Rs =
fined and then their suitability for the intended Ir
application is checked. The start current Ir can be changed, if needed,
by changing the value of Rs. It is recommended
The stabilizing voltage Us required by the pro- that the start current Ir is greater than the sum of
tection in through-fault situations is determined the excitation currents of the CTs. That is, the
according to the following expression: start current is to be Ir ≥ m x Ie, where m is the
number of CTs in the differential current cir-
I x (Rin + Rm)
Us = kmax cuit.
n
Ikmax = Maximum through-fault current, for The primary current value corresponding to the
which the relay must not operate. If the start current Ir is obtained from the expression:
current is unknown the generator is
given the value Ikmax ≈ 6 x In Iprim = n x (Ir + m x Ie + Iu)
Rin = Resistance of the CT secondary circuit
Rm = Total resistance of the longest measur- Iu = current through the varistor at Us,
ing circuit, i.e. from the summing point see Fig. 5.
to the current transformer
n = CT transforming ration, for example The selector switches of the relay SPAJ 115 C
n = 2000/5 A = 400 can be given the following settings:
Contact Function
65-66 Trip signal from the restricted earth-fault stage; opens the excitation CB and
stops the prime mover of the generator
68-69 Trip signal from the restricted earth-fault stage or the residual earth-fault stage;
opens the generator CB
80-81 Signal on operation of the restricted earth-fault stage
77-78 Signal on operation of the residual earth-fault stage
70-71-72 Self-supervision alarm signal
12
Example 2.
Earth-fault
L1
protection of the L2 TRIPPING OF THE
HIGH-VOLTAGE SIDE
high-voltage side of L3 CIRCUIT BREAKER
a power transformer
TRIPPING OF THE
LOW-VOLTAGE SIDE
CIRCUIT BREAKER
Rx Tx
Ru
SPA-ZC_
Iu Ir
+ (~)
Rs Uaux
- (~)
5A
1A ≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
TS1
∆Io>
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 6. Transformer earth-fault protection using the restricted earth-fault and residual earth-fault
relay SPAJ 115 C. The selector switch positions are shown in the table on the next page.
13
The calculations are performed in the same way The selector switches of the relay SPAJ 115 C
as in the previous example. If the maximum can be given the following settings:
through-fault current Ikmax is not known, the
value 16 x In can be used when the settings for
the transformer protection are calculated.
∑ 172
Contact Function
65-66 Trip signal from the restricted earth-fault stage; opens the low-voltage side CB
68-69 Trip signal from the restricted earth-fault stage or the residual earth-fault stage;
opens the high-voltage side CB
80-81 Signal on operation of the restricted earth-fault stage
77-78 Signal on operation of the residual earth-fault stage
70-71-72 Self-supervision alarm signal
14
Example 3.
Earth-fault L1
protection of the L2
low-voltage side of L3
a power transformer
TRIPPING OF THE
HIGH-VOLTAGE SIDE
CIRCUIT BREAKER
TRIPPING OF THE
LOW-VOLTAGE SIDE
CIRCUIT BREAKER
Rx Tx
Ru
SPA-ZC_
Iu Ir
+ (~)
Uaux
Rs - (~)
5A
1A
≅_ E D C B A
U3
+ - 1 1 1 1
SGR/1
U3
IRF SGR 2 4 7 5 8 6
∆Io> TS1
35 ms
SGB
4
5 SS2
t>,k TS2
Io>
U1 I/O
SPAJ 115 C U2
Fig. 7. Transformer earth-fault protection using the restricted earth-fault and residual earth-fault
relay SPAJ 115 C. The selector switch positions are shown in the table on the next page.
15
In this example the residual earth-fault stage is the residual earth-fault stage operates. An in-
used as a fast feeder cubicle and busbar earth- coming blocking signal is routed to the residual
fault protection. Should the fault appear on the earth-fault stage by means of switch SGB/5 in
feeder, the feeder earth-fault relay transmits a the relay module SPCJ 2C30.
blocking signal to the residual earth-fault stage
of the infeeder cubicle. Should the earth-fault, The selector switches of the protection relay
however, appear in the infeeder cubicle or on the module SPAJ 115 C can be set as follows:
busbars, no blocking signal will be obtained and
∑ 12
Contact Function
65-66 Trip signal from the restricted earth-fault stage; opens the high-voltage side CB
68-69 Trip signal from the restricted earth-fault stage or the residual earth-fault stage;
opens the low-voltage side CB
80-81 Signal on operation of the restricted earth-fault stage
77-78 Signal on operation of the residual earth-fault stage
70-71-72 Self-supervision alarm signal
16
Recorded The data registered by the relay can be used to values can be compared with the residual cur-
information analyze the faults and the behaviour of the rent values measured by the relay under normal
protection. operation conditions.
Register 1 contains the maximum value of the Register 3 records the number of operations of
differential current as a percentage of the rated the differential current stage ∆I0>.
current of the used energizing input. The regis-
ter is updated, if The number of starts of the the residual earth-
- the value of the measured current exceeds the fault stage, register 4, provides information about
value already in the register how frequently earth-faults appear in the net-
- the relay operates. At relay operation the value work. Frequent starts may indicate an imminent
of the current at operation is recorded. earth-fault caused, for instance, by a broken
isolator or some kind of disturbance apt to cause
The value of the differential current measured an earth-fault. The reason may also be too low
during a fault shows the magnitude of the earth- a start current setting. The residual earth-fault
fault current. When the earth-fault current of stage, unlike the restricted earth-fault stage, also
the total network is known, the probable loca- detects faults outside the zone of protection.
tion of the fault inside tha transformer can be
judged. The value in register 1 shows how close The values recorded in register 5 shows the
the set relay start current value is to the real fault duration of the latest start of the residual earth-
current value. Correspondingly, the set start fault stage, expressed as a percentage of the set
current values can be compared with the differ- operate time. Any new start resets the counter,
ential current values measured by the relay un- which always starts counting from zero. If the
der normal operation conditions. stage operates, the value of the register will be
100 [%].
Register 2 contains the maximum value of the
residual current as a percentage of the rated Register 5 provides information on the duration
current of the used energizing input. The regis- of the earth-fault and the safety margins of the
ter is updated, if grading times of the protection. Should, for
- the value of the measured current exceeds the instance, the duration recorded by the earth-
value already in the register fault relay, functioning as a back-up relay for the
- the relay operates. At relay operation the value feeder earth-fault relay show the value 75 [%]
of the current at operation is recorded. after that the feeder earth-fault relay has tripped,
the safety margin of the selective protection has
The value of the residual current measured been 25% counted on the operate time of the
during a fault shows the magnitude of the earth- residual earth-fault relay.
fault current. When the earth-fault current of
the total network is known, the degree of devel- The registers 1…5 are reset, either by pressing
opment of the earth-fault can be judged. The the STEP and RESET push-buttons simultane-
value in register 2 shows how close the set relay ously or with a command, V102, over the SPA
start current value is to the real fault current bus.
value. Correspondingly, the set start current
17
Secondary The secondary testing should always be per- DANGER!
injection testing formed in accordance with national regulations Do not open the secondary circuit of a cur-
and instructions. rent transformer during testing, if the pri-
mary circuit is live. The high voltage pro-
The protection relay incorporates an IRF func- duced by an open CT secondary circuit could
tion that continuously monitors the internal be lethal and may damage measuring instru-
condition of the relay and produces an alarm ments and insulation.
signal on detection of a fault. According to the
manufacturer’s recommendations the relay When the auxiliary voltage is connected to the
should be submitted to secondary injection test- protection relay, the relay performs a self-testing
ing at five years’ intervals. These tests should program. The self-testing does not include the
include the entire protection chain from the matching transformers and the contacts of the
instrument transformers to the circuit breakers. output relays. The operational condition of the
relay is tested by means of ordinary relay test
The secondary testing described in this manual equipment and such a test also includes the
is based on the relay’s setting values in the matching transformers, the output relays and
concerned application. If necessary, the second- the accuracy of the operate values.
ary testing can be extended by testing the protec-
tion stages throughout their setting ranges. Equipment required for testing:
- adjustable voltage transformer 0...260 V, 1 A
As switch positions and setting values may have - current transformer
to be altered during the test the correct positions - ammeter, accuracy ±0.5%
of switches and the setting values of the relay - stop watch or counter for time measurement
during normal operation conditions have to be - dc voltage source for auxiliary supply
recorded, for instance, on the reference card - switches and indicator lamps
accompanying the relay. - supply and pilot wires
- calibrated multimeter
To enable secondary injection testing the relay
has to be disconnected, either through dis- The secondary current of the current trans-
connectable terminal blocks or a test plug fitted former is to be selected on the basis of the rated
on the relay. current, 1 A or 5 A, of the relay energizing input
to be tested. The energizing inputs are specified
under the heading "Technical data, Energizing
inputs".
18
Uaux
U2
+ (~)
- (~)
6
A
1
TRIP1
65 66
TIMER STOP
8
TRIP2
68 69
5
C
SIGNAL1
7
80 81
L3
4
D
1
START1
SGR 2
77 78
TS1
L2
SS2
TS2
I/O
E
IRF
35 ms
70 71 72
t>,k
IRF
U3
L1
∆Io>
Io>
≅_
61 62
+ -
SGB
U1
4
5
SGR/1
S2
11
BS
10
TIMER START
25 26 27 37 38 39
1A
5A
1A
SPAJ 115 C
5A
A
U3
S1
L1 N
Fig. 8. Secondary test circuit for the earth-fault relay SPAJ 115 C.
The auxiliary voltage can be connected to the The correctness of the test connection can be
relay, as the test connection has been finished verified by using a multimeter.
and the selector switches properly set.
19
Checking the Pure sinusoidal energizing current is fed to the The measurement can be made at the rated
matching relay. Compare the current value shown in the current of the relay. The matching transformers
transformers display with the current reading of the ammeter. are tested separately.
Checking the The switches of switchgroup SGR should be set Start function
restricted earth- as follows:
fault stage ∆I0> Close switch S1 and slowly increase the test
Switch Position current until the relay operates, indicator L3 is
lit. Read the start current value from the am-
1 1 meter.
2 0
3 - Operate time
4 0
5 0 The operate time of the restricted earth-fault
6 0 stage is measured at a test current equal to 2
7 1 times the set start value of stage ∆I0>. The timer
8 0 is started when switch S1 is closed and stopped
by contact 65-66 on operation of output relay A.
The output relays have the following functions: The operation of output relay C is indicated by
LED L3.
Output Function
(terminals) When the relay operates, the indicator ∆I0> in
the right bottom corner of the front panel of the
A (65-66) Trip signal of stage ∆I0> relay module turns red.
B (68-69) Not in use
C (80-81) Signal on tripping of stage ∆I0> Blocking
(L3)
D (77-78) Not in use Switch 4 and 5 of switchgroup SGB on the PC
E (71-72) Self-supervision alarm signal (L1) board of the relay module and switch SGR/1 on
the front panel are to be set in position 1 (ON).
20
Checking the The switches of switchgroup SGR should be set Start function
restricted earth- as follows:
fault stage I0> The measuring current is slowly increased until
Switch Position the stage starts and indicator L2 is lit. The start
current is read from the ammeter.
1 1
2 1 Operate time
3 0
4 0 Definite time characteristic
5 1
6 0 The operate time of the residual earth-fault
7 0 stage is measured at a test current equal to 2
8 0 times the set start value of I0> stage. The timer
is started by closing switch S1 and stopped by
contact 68-69 on operation of output relay B.
The output relays have the following functions:
Inverse time characteristic
Output Function
(terminals) At inverse time characteristic the operate time of
the stage is measured at two current values (2 x
A (65-66) Not in use I0> and 10 x I0>). The operate times thus
B (68-69) Trip signal of stage I0> received are compared with the operate times
C (80-81) Signal on tripping of stage I0> shown in the current/time curves for the corre-
(L3) sponding inverse time characteristic.
D (77-78) Start signal of stage I 0> (L2)
E (71-72) Self-supervision alarm signal (L1)
Checking the self- The self-supervision system and its operation "General characteristics of C-type relay mod-
supervision system indicator IRF and output relay E can be tested ules" of this manual. The operation of output
in the Trip-Test mode described in section relay E is indicated by the LED indicator L1.
21
Maintenance When used under the conditions specified in the relay specifications, the relay should be given
and repair the section "Technical data", the relay requires a proper overhaul. Minor measures, such as
practically no maintenance. The relay includes exchange of a faulty module, can be undertaken
no parts or components that are liable to abnor- by personnel from the customer’s instrument
mal physical or electrical wear under normal work-shop, but major measures involving meas-
operating conditions. ures in the electronic circuitry are to be taken by
the manufacturer. Please contact the manufac-
If the environmental conditions on site differ turer or his nearest representative for further
from those specified, as to temperature and information about checking, overhaul and
humidity, or if the atmosphere around the relay recalibration of the relay.
contains chemically active gases or dust, the
relay should be visually inspected during the Note!
relay secondary testing. The visual inspection The protection relays contain electronic circuits
should focus on: which are liable to serious damage due to elec-
- Signs of mechanical damage on relay case and trostatic discharge. Before withdrawing a mod-
terminals ule from the relay case, ensure that you are at the
- Dust accumulated inside the relay cover or same electrostatic potential as the equipment by
case; remove carefully with compressed air or touching the case.
a soft brush
- Signs of corrosion on terminals, case or com- Note!
ponents inside the relay Static protection relays are measuring instru-
ments and should be handled with care and
If the relay fails to operation or if the operation protected against damp and mechanical stress,
values considerably differ from those stated in especially during transport and storage.
Ordering Combined restricted earth-fault and residual earth-fault relay SPAJ 115 C
numbers
SPAJ 115 C RS 421 012 -AA, CA, DA, FA
Combined restricted earth-fault and residual earth-fault relay SPAJ 115 C with
test adapter RTXP 18
The two last letters of the ordering number designate the rated frequency fn and
the Uaux voltage range of the relay as follows:
22
Dimensions and The relay case is basically designed for flush- by 80 mm and type SPA-ZX 112 reduces the
instructions for mounting. The mounting depth can be reduced depth by 120 mm. The relay can also be mounted
mounting by the use of a raising frame: type SPA-ZX 111 in a case for surface mounting, type designation
reduces the depth behind the mounting panel SPA-ZX 115.
by 40 mm, type SPA-ZX 112 reduces the depth
250
142
216 34
30 186
136
162
129 ±1 a b
139 ±1
Panel cut-out
Raising frame a b
SPA-ZX 111 176 74
SPA-ZX 112 136 114
SPA-ZX 113 96 154
Fig. 9. Dimensions of the restricted earth-fault and residual earth-fault relay SPAJ 115 C.
The relay case is made of profile aluminium and along the edge of the cover provides an IP54
finished in beige. degree of protection between the case and the
cover.
A rubber gasket fitted on the mounting collar
provides an IP54 degree of protection between All input and output wires are connected to the
relay case and mounting panel, when the relay is screw terminal blocks on the rear panel. Each
flush mounted. terminal is dimensioned for one max. 6 mm2
wire or two max. 2.5 mm2 wires. The D-type
The hinged cover of the relay case is made of a connector connects to the serial communica-
clear, UV stabilized polycarbonate, and pro- tion bus.
vided with a sealable fastening screw. A gasket
B
∆I
I
I o ∆I o IRF
STEP 2.5
∆I o>
[%] STEP
In
0.5 5.0
20
I o>
[%] SG1
In 1
5.0 40 2
3
4
5
0.6 6
7
t o>[s] 8
k 0 1
0.1 1.0
RESET
∆I o> I o>
1411
SPCJ 2C30
1MRS 750659-MUM EN
SPCJ 2C30
Issued 1997-02-26
Modified 2002-05-15 Differential current and
Version B (replaces 34 SPCJ 11 EN1)
Checked MK
Approved OL
neutral current module
Data subject to change without notice
Features Sensitive differential current stage ∆I0> with Flexible configuration of the relay module to
short operate time, 35 ms. Setting range 0,5…5 obtain the desired protection functions
% x In
All settings may be entered using the push-
Neutral overcurrent stage I0> with definite time buttons and the display on the front panel of the
characteristic or inverse time characteristic. Set- module or they may be set using a personal
ting range 5…40% x In computer
The operation of both protection stages can be Continuous self-supervision including both
blocked with an external control signal module hardware and software. At a permanent
fault the alarm output relay operates and the
Local display of measured currents, set start other relay outputs are blocked.
values, recorded fault data and other parameters
2
Operation The combined differential current and neutral The setting range of the neutral current stage
principle current module SPCJ 2C30 measures two cur- I0> is 5…40% x In. The neutral current stage
rents; the differential current ∆I0 and the neu- can be assigned definite time or inverse time
tral current I0. The differential current is formed characteristic. The selection is made with switch
with an external connection. The relay module SG1/6. At definite time characteristic three op-
holds two protection stages, one for each cur- erate time ranges are available; 0.1…1s, 1…10
rent. s and 10…100 s. The operate time setting range
is set with switch SG1/7 and SG1/8.
The differential current stage ∆I0> operates
instantaneously and provides an operate signal At inverse time characteristic of the I0> stage
TS1, if the measured differential current ex- four time-current characteristic curve groups
ceeds the set start current. can be selected. The selection is made with
switches SG1/7 and SG1/8.
The neutral current stage I0> starts if the meas-
ured neutral current exceeds the set start cur- The two protection stages can separately be
rent. On starting the stage provides a start signal given a latching function, which means that the
SS2 and at the same time the operation indicator operate output remains high, althoug the fault,
turns yellow. After the set or calculated operate which caused the relay to operate, has disap-
time t0> the stage provides an operate signalTS2, peared. The lached state is reset locally by press-
if the fault still persists. ing the STEP and RESET push-buttons simul-
taneously or remotely by means of the com-
The indicator of the stage that operates turns mands V101 or V102 via the SPA bus. The
red. The start and operation indications can be latching function of stage ∆I0> is selected with
given self-reset or manual-reset mode of opera- switch SG1/3 and the latching function of stage
tion, see switch SG2. The latched indications I0> with switch SG1/4.
are reset locally by pressing the RESET push-
button on the front panel or remotey by means The differential current input and the neutral
of the commands V101 or V102 via the SPA current input are provided with low-pass filters
bus. which suppress harmonics of the input current,
see. Fig. 1.
The operation of stage ∆I0> can be blocked by
means of an external control signal to input
BTS1. Correspondingly the operation of stage dB 5
I0> can be blocked by means of an external
0
control signal to input i BTS2. The incoming
blocking signals are distributed to the desired -5
protection stages with switches of switcgroup
SGB. -10
3
Block diagram
Fig. 2. Block diagram of the differential current and neutral current relay module SPCJ 2C30.
NB!
All input and output signals of the relay module particular protection relay are shown in section
are not necessarily wired to the terminals of any "Signal diagram" in the general manual of the
protection relay incorporating the above relay concerned protection relay.
module. The signals wired to the terminals of a
4
Front panel
B
∆I
I Simplified device symbol
Display
STEP 2.5
∆I o>
Indicator and setting knob for [%] STEP
the start current of stage ∆I0>- In
0.5 5.0
Step push-button
20
Indicator and setting knob for I o>
[%] SG1
the start current I0> or time In 1
5.0 40
multiplier k of stage I0> 2
3 Selector push-button SG1
4
5
0.6 6
7
Indicator and setting knob for t o>[s] 8
Reset push-button
∆I o> I o>
Operation indicators
1411
Fig. 3. Front panel of the differential current and neutral current relay module SPCJ 2C30.
Indicators The operation indicator of the differential cur- An unreset operation indicator does not affect
rent stage ∆I0> is lit with red colour, when the the protection functions of the relay module.
stage operates. The operation indicator of the The relay module is always operative, whether
neutral current stage I0> is lit with yellow colour the indicators have been reset or not.
when the stage starts and with red colour, when
the stage operates. The self-supervision alarm indicator IRF indi-
cates that the self-supervision system has de-
The indicators can separately be assigned a tected a permanent internal relay module fault.
latching function, which means that the indica- The IRF indicator is lit with red light shortly
tor will remain lit, although the fault that caused after the fault has been detected. At the same
the indication has disappeared. If, for example, time the relay module delivers a control signal to
the trip indication of stage I0> has been assigned the self-supervision system output relay of the
the latching function, the indicator normally protection relay unit.
turns yellow when the stage starts and turns red
when the stage operates. When the stage resets Additionally, in most fault cases, a fault code
the red indicator remains lit. The latched indi- showing the fault type appears on the display of
cators are reset locally by pressing the RESET the relay module. The fault code consists of a red
push-button on the front panel or remotely by figure one (1) and a green three-digit code
means of commands V101 or V102 via the SPA number. When a fault message appears on the
bus. display, the code number should be noted to
facilitate trouble-shooting and repair.
5
Settings The setting values are shown by the three LED indicator below a setting knob shows that
rightmost digits of the display. When lit, the the concerned setting value is being displayed.
∆I0>/In Start current of stage ∆I0> in percent of the rated current of the used relay energizing
input, setting range 0,5…5% x In
I0>/In Start current of stage I0>in percent of the rated current of the used relay energizing
input, setting range 5…40% x In
t 0> Operate time of stage I0> at definite time characteristic. The setting range is k> selected
with switche SG1/7and SG1/8 , setting ranges 0.1...1.0 s, 1…10 s and 10...100 s.
Time multiplier k> at inverse time characteristic, setting range 0.1…1.0.
Further, the checksum of the selector switch- the switchgroup has been set and that the indi-
group SG1 is indicated on the display when the vidual switches work properly. An example of a
LED indicator under the switchgroup is lit. In checksum calculation is given in manual "Gen-
this way a check can be carried out to prove that eral characteristics of C type relay modules".
Selector switches Additional fuctions required in different appli- numbers 1...8 and the switch positions 0 or 1 are
cations are selected with the switches of switch- marked on the front panel
group SG1 on the front panel. The switch
Switch Function
SG1/3 Selection of the latching function for the operate signal TS1 of stage ∆I0>
When SG1/3=0, the operate signal TS1 returns to normal (= output relay drops),
when the measured current falls below the set start current of the stage.
When SG1/3=1, the operate signal TS1 remains high (=output relay picked up),
although the measured current falls below the set start current of the stage. The operate
signal is reset locally by pressing the STEP and RESET push-buttons simultaneously
or remotely by means of the command V101 via the SPA bus. When the STEP- and
RESET push-buttons are used the recorded information is also erased.
SG1/4 Selection of the latching function for the operate signal TS2 of stage I0>
When SG1/4=0, the operate signal TS2 returns to normal (= output relay drops),
when the measured current falls below the set start current of the stage.
When SG1/4=1, the operate signal TS2 remains high (=output relay picked up),
although the measured current falls below the set start current of the stage. The operate
signal is reset locally by pressing the STEP and RESET push-buttons simultaneously
or remotely by means of the command V101 via the SPA bus. When the STEP- and
RESET push-buttons are used the recorded information is also erased.
6
Switch Function
SG1/6 With switch SG1/6 definite or inverse time characteristic is selected for stage I0>.
SG1/7 With switches SG1/7 and SG1/8 the operate time setting range is selected at definite
SG1/8 time characteristic and the time multiplier setting range at inverse time characteristic.
The software switchgroup SG2 is located in the defined to be self-reset or latching. The setting
third submenu of the checksum register of switch- is performed by defining a checksum for the
group SG1. The operation principle of the switchgroup as described in the table below. As
operation indicators is defined with switch- a default setting the start signal is set to be self-
group SG2. The operation indicators can be reset and the operate signals to be latching.
Checksum Σ 14 10
The possible external blocking signals applied to The alternatives, which can be selected with the
the relay are routed to the protection stages with switches of switchgroup SGB, are shown in the
switches SGB/4…8. Any start signals to be general part of the maual of the different relays
routed to a cooperating auto-reclose relay are which incorporate the differential current and
configured with switches SGB/2 and SGB/3. neutral current module SPCJ 2C30.
Switch SGB/1 is not in use.
Measured data The measured values are displayed with the rently displayed value is indicated by an illumi-
rightmost three digits of the display. The cur- nated LED indicator on the front panel.
∆I0 Differential current displayed in percent of the rated current In of the relay.
If the measured current exceed about 60% x In, a symbol "- - -" will be shown in
the display.
7
Recorded The leftmost digit of the display indicates the
information number of the register and the three rightmost
digits show the content of the register.
1 Measured maximum differential current ∆I0 in percent of the relay rated current.
The register content is updated if on of the following conditions is fulfilled:
If the value of the measured differential current exceeds approximately 60% x In, the
register content will be shown as "- - -".
2 Measured maximum neutral current I0 in percent of the relay rated current. The
register content is updated if on of the following conditions is fulfilled:
3 Number of operations of the differential current stage ∆I0>, n(∆I0>) = 0 ... 255
4 Number of operations of the neutral current stage I0>, n(I0>) = 0 ... 255
5 Duration of the last start situation of stage I0> in percent of the set operate time t0>
at definite time characteristic or calculated operate time at inverse time characteristic.
The counter always starts counting from zero. When the module operates (trips) the
counter reading will be 100 [%].
0 Status of the external blocking inputs. The rightmost digit of the display shows the
status of the blocking inputs. The following alternatives are available:
0 = No blocking
1 = The operation of stage ∆I0> is blocked
2 = The operation of stage I0> is blocked
3 = The operation of both stages (∆I0> and I0>) is blocked
The middle digit of the register is always zero. The third digit from the right indicates
the status of a possible remote reset input. The following alternatives are available:
0 = Remote reset input not activated
1 = Remote reset input activated
From register 0 the TRIP TEST mode can be reached. In the TRIP TEST mode the
start and operate signal of the module can be activated on by one. A detailled
description of the TRIP TEST mode is to be found in the manual "General
characteristics of C type relay modules".
8
Register/ Recorded information
STEP
A Module address code for the communication system. If the register value is zero the
serial communicatio is not in use. The subregisters of register A are:
1) Selection of the data transfer speed. Selectable values 300, 1200, 2400, 4800 or
9600 Bd. Default setting 9600 Bd
2) Bus communication monitor. If the module is connected to a data communi-
cation device and the communication system is working, the communcation
counter is 0. If the communication is interrupted the numbers 0…255 are
scrolling in the display.
3) Password required for remote setting of relay parameters
When the display is dark you can proceed to the if the auxiliary power supply to the module is
beginning of the display menu by pressing the interrupted. The address code of the relay mod-
STEP push-button once. ule, the value of the data transfer rate of the serial
communication and the password are not erased
The content of the registers 1...5 are erased by by an auxiliary voltage interruption. Instruc-
pressing push-buttons STEP and RESET si- tions for setting the address and the data transfer
multaneously or with the remote control com- rate are given in the user's manual "General
mand V102. The register values are also erased characteristics of C-type relay modules".
9
Menu chart The diagram below shows the main menu and general principles for navigating in the menues
the submenus of the differential current and are described in the user's manual "General
neutral current relay module SPCJ 2C30. The characteristics of C type relay modules".
Normal state, display dark = parameter, which can be set in the setting mode
S
T
E Neutral current Io
P
B
A BACKWARD STEP 0.5 s FORWARD STEP 1 s
C Differential current ∆Io SUBMENU
K
W
A
R Enforced start current of Remotely set Remotely set
D
S stage ∆Io percentage p1 value ∆Io x p1
.5
s Enforced start current of Remotely set Remotely set
stage Io> percentage p2 value Io> x p2
1
s
4 Number of starts of stage Io>
Fig. 4. Menu chart of the differential current and neutral current relay module SPCJ 2C30.
10
Inverse time The operation of the neutral current stage I0> is The slope of the characteristic curve is defined
characteristic based on either definite time or inverse time by parameter α and β as follows:
(modified 2002-05) characteristics. The desired characteristic is se-
lected with switch SG1/3, see chapter "Selector Slope of the charac- α β
switches". teristic curve
At inverse time characteristic the operate time of Normal inverse 0.02 0.14
stage I0> is a function of the current; the higher Very inverse 1.0 13.5
the current the shorter the operate time. The Extremely inverse 2.0 80.0
relationship between time and current is de- Long time inverse 1.0 120.0
fined in the BS 142.1966 and IEC 60255-3
standards as follows: According to the standard BS 142.1966 the
normal current range is defined as 2...20 times
kxβ
t= the setting current. Additionally the relay must
α
( II0> ) - 1 start at the latest when the measurd current
exceeds 1.3 times the set sarting value, when the
time/current characteristic is normal inverse,
where, very inverse or extremely inverse. When the
t = operate time in seconds characteristic is long time inverse, the normal
k = time multiplier range accordance to the standards is 2...7 times
I = measured current the set starting value and the relay must start
I0> = set start current when the current exceeds 1.1 times the set
starting value.
The relay module includes four standard curve
groups. The desired curve group is selected with The following requirements regarding toler-
switch SG1/7and SG1/8, see chapter "Selector ances of the operation time are specified in the
switches". standard (E denotes accuracy in percent, - = not
specified):
I/I0> Normal inverse Very inverse Extremely inverse Long time inverse
11
Time/current
characteristic of
the combined t/s
differential current 70
and neutral current 60
module SPCJ 2C30 50
40
30
20
10
9
8
7
6
5
1
0.9
0.8
0.7
0.6
0.5
0.4
0.3
k
0.2 1.0
0.8
0.6
0.1 0.4
0.09
0.08 0.3
0.07
0.2
0.06
0.05
0.1
0.04
0.05
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
I = measured current
I0> = set start current
t = operate time
k = time multiplier
12
t/s
70
60
50
40
30
20
10
9
8
7
6
5
1
0.9
0.8 k
0.7 1.0
0.9
0.6
0.8
0.5 0.7
0.6
0.4
0.5
0.3 0.4
0.3
0.2
0.2
0.1
0.09 0.1
0.08
0.07
0.06
0.05
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
I = measured current
I0 > = set start current
t = operate time
k = time multiplier
13
t/s
70
60
50
40
30
20
10
9
8
7
6
5
3 k
1.0
2 0.9
0.8
0.7
0.6
0.5
1
0.9 0.4
0.8
0.7 0.3
0.6
0.5
0.2
0.4
0.3
0.1
0.2
0.05
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
1 2 3 4 5 6 7 8 9 10 20 I/I>
I = measured current
I0> = set start current
t = operate time
k = time multiplier
14
t/s
700
600
500
400
300
200
100
90
80
70
60
50
40
30
20
10
9
8
k
7
1.0
6 0.9
5 0.8
0.7
4
0.6
0.5
3
0.4
2
0.3
0.2
1
0.9
0.8
0.7
0.1
0.6
0.5
0.4
0.05
0.3
0.2
I/I>
1 2 3 4 5 6 7 8 9 10 20
I = measured current
I0> = set start current
t = operate time
k = time multiplier
15
Technical data Differential current stage ∆I0>
Start current 0.5…5% x In
Fixed operate time, typ. 35 ms
Reset time, typ. 60 ms
Reset ratio, typ. 0.97
Operate time accuracy ±25 ms
Operation accuracy
- within the setting range 0.5…1.5% x In ±5% of the set value
- within the setting range 1.5…5% x In ±3% of the set value
16
Event codes A substation level communication device can The event mask is formed by multiplying the
read event messages via the SPA bus from the above numbers by 0, event not included in
combined differential current and neutral cur- reporting or 1, event included in reporting and
rent relay module SPCJ 2C30. On request the by adding the numbers received.
module transmits its event messages in the form;
time (ss.sss) and event code. The event codes of The event mask may have a value within the
the module are E1…E6, E50 and E51. The range 0…255. The factory set default value is
communication device may also form event mes- 21, that is all the sart and operate events are, on
sages related to the data communication system. request, tranmitted to the communication
device,but the resettings are not transmitted.
The events represented by the codes E1...E6 can The events represented by the codes E50…E54
be included or excluded from the event report- cannot be excluded from the reporting.
ing. This is done via the SPA bus by writing a so
called event mask (V155) to the relay module. The event codes of the combined differential
The event mask is a binary number coded to a current and neutral current relay module SPCJ
decimal number.The even codes E1…E6 corre- 2C30 :
spond with the weighting factors 1, 2, 4…32.
Remote transfer In addition to the event data transfer the SPA altered by commands given over the SPA bus.
data bus allows reading of all input data (I data) of the All the data are available in channel 0.
module, setting values (S data), information
recorded in the memory (V data), and some R = data that can be read from the module
other data. Further, part of the data can be W = data that can be written to the module
17
Data Code Data Value or function
direction
18
Data Code Data Value or function
direction
The data transfer codes L, B, C and T have been plied by the set values given with the setting
reserved for the event data transfer between the knobs. The settings S21...S24 can be both read
relay module and the substation level communi- and written. A condition for writing is that the
cation device. password, V160, for remote setting has been
opened and the potentiometer settings are
The event register can be read only once by the alerted, V150=0. The variables S31...S34 con-
L command. Should a fault occur, for instance, tain the actual remotely set values
in the data transfer, it is possible, by using the B
command, to re-read the contents of the event The remote setting percentage of variables
register once read by means of the L command. S21...S23 can be given a percentage value within
When required the B command can be re- the range 0...999. This means that certain pa-
peated. Normally the event register is empty. rameters can be given set values outside the
limits of the specified setting range. However,
Parameters S1...S4 contain the enforced set proper operation of the relay is guaranteed only
values currently used by the relay module. These for set values within the limits of the setting
values may originally have been set by means of range specified in section "Technical data".
the setting knobs and selector switches or by
remote control. The main settings S11...S14 are When the self-supervision system is activated
given with the setting knobs and the selector (V165) the operation of the relay module is
switches of the relay module. The values blocked and the IRF indicator is lit.
S21...S24 are percentage factors to be multi-
19
Fault codes Shortly after the self-supervision system has and a green, one-, two- or three-digit code
detected a permanent internal fault the red fault number. It is recommended that the fault code
indicator IRF on the relay module front panel is number is noted down and passed forward to
lit. At the same time the self-supervision system the service shop when overhaul and repair of a
generates a control signal to the output relay of faulty relay module is ordered.
the self-supervision system. Further, in most
fault situations a self-diagnostic fault code is The combined differential current and neutral
shown on the display of the relay module. The current relay module SPCJ 2C30 displays the
fault code is composed of a red figure one (1) following fault codes:
20
General characteristics of
C-type relay modules
User´s manual and Technical description
B
I >
I >>
I L1 I L2 I L3 IRF
Self-supervision alarm indicator
Indicators for measured values (Internal Relay Fault)
Display, 1 + 3 digits
STEP 1.5
I>
Setting knob 1 In STEP
with indicator 0.5 2.5
Step push-button (STEP)
Stage 1 0.5
t > [ s] SG1
Setting knob 2 k
1
with indicator 0.05 1.0 2
3
4
5
Programming switches SG1
13 6
7
I >>
Setting knob 3 20 8
In
with indicator 2.5
0 1
Switchgroup indicator
RESET
Stage 2
0.5
Reset push-button (RESET)
Setting knob 4 t >> [ s ]
with indicator 0.04 1.0
I> I >>
Start/operation indicators
1309
SPCJ 3C3
1MRS 750328-MUM EN
General characteristics of
Issued 96-02-19
Version A (replaces 34 SPC 2 EN1)
Checked L-W U
C-type relay modules
Approved TK
Push-buttons The front panel of the relay module contains settings, e.g. for setting the address of the relay
two push-buttons. The STEP button is used for module and the data transfer rate for the serial
stepping forward in the display and the RESET communication when the modules are used in
button for resetting the red indicators. Addi- relay packages provided with this quality. (See
tionally, the push-buttons are used for certain section Display).
Programming Part of the settings and the selections of the checksum of the switchgroup is shown on the
switches SG1 operating characteristics for the relay modules display. The checksum can be used for checking
in various applications are made with the pro- that the switches are properly set. Fig. 2 gives an
gramming switches SG1 on the front panel. The example of calculating the checksum.
indicator of the switchgroup glows when the
When the checksum calculated according to the The function of the programming switches of
example is equal to the checksum indicated on the individual measuring relay modules is speci-
the display of the relay module, the switches are fied in the description of the module concerned.
properly set.
2
Setting knobs Most of the operating values and operating In addition to the settings made with the setting
times are set by means of the setting knobs on knobs, most modules allow so called remote
the front panel of the relay module. Each setting setting. This means that the settings made by
knob has its own (LED) indicator which glows means of the setting knobs of the module and
when the concerned setting value is shown on the checksum of the programming switchgroup
the display. may be altered through an instruction over the
serial communication bus. Remote setting is
If a setting knob is turned while the display is possible if the password in the register A is
showing another measured or set value, the known, and the remote settings are not acti-
value being set automatically appears on the vated, i.e. parameter V150=0. The circumstance
display. Simultaneously, the indicator for the that the remote settings are activated is shown
concerned setting starts glowing. with a flashing light of the indicator of the
setting knob, the value of which currently is
being displayed.
Display The measured and set values as well as the data When the auxiliary voltage is connected to a
recorded are shown on the display of the meas- measuring relay module, the module initially
uring relay module. The display consists of four tests the display by stepping through the digits
digits. The three digits (green) to the right 1...9 for about 15 seconds. When the test is
indicate the measured, set or stored value and finished the display turns dark. The testing can
the digit at the extreme left (red) the number of be interrupted by pressing the STEP button.
the register. The measured or set value displayed The protective functions of the module are
is indicated by a yellow LED indicator. The operative throughout the testing.
number of the register glows only when a stored
value is displayed.
Display main menu All the data required during normal operating From a dark display only forward movement is
conditions are accessible from the main menu possible. When keeping the STEP button de-
which presents the measured values in real-time, pressed, the display is continuously moving in
the normal setting knob settings as well as the forward direction stopping for a while at the
most important memorized data. dark point.
The data to be shown in the main menu are Unless the display is switched off by stepping to
selected to the display in a certain sequence by the dark point, it remains activated for about 5
means of the STEP button. When pressing the minutes from the last pressing of the STEP
STEP button for about one second, the display button and then goes out.
moves forward in the display sequence. When
pressing it for about 0.5 seconds, the display
moves backwards in the display sequence.
3
Display submenu Less important values and values not very often display moves forward when pressing the STEP
set are displayed in the submenus. The number button for one second and backward when
of submenus varies with different relay module pressing it for 0.5 seconds. The return to the
types. The submenus are presented in the de- main menu has taken place when the red STEP
scription of the concerned module. display turns dark.
A submenu is entered from the main menu by When entering a submenu from a measured or
pressing the RESET button for about one sec- set value indicated by a LED indicator, the
ond. When the button thereafter is released, the indicator remains glowing and the address win-
red digit (STEP) of the display starts flashing, dow (STEP) of the display starts flashing. A
indicating that one is in a submenu. Going from flashing address window when no LED indica-
one submenu to another or back to the main tor is lit indicates that the submenu of a register
menu follows the same principle as when mov- has been entered.
ing from the main menu display to another; the
Fig. 3. Example of the main and submenus for the settings of the overcurrent relay module SPCJ
3C3. The settings made with the setting knobs are in the main menu and they are displayed by
pressing the STEP button. In addition to the setting knob settings the main menu contains the
measured current values as well as the registers 1…5, as well as 0 and A. The remote setting
percentage and remote setting value are located in the submenus for the settings and are activated
on the display by pressing the RESET button.
Setting mode The registers of the main menu and the submenus pressed slightly in excess of the STEP button.
also contain parameters to be set. The settings Return from the setting mode to the main menu
are made in the so called setting mode, which is or submenu is possible by pressing (for about 10
accessible from the main menu or a submenu by s) the RESET button until the green digits on
pressing the RESET button, until the digit at the display stop flashing. If the module is left in
the extreme right starts flashing (about 10 s). the setting mode, it will return automatically to
The flashing digit is set by means of the STEP the start condition after about 5 minutes.
button. The flashing is moved on from digit to
digit by pressing the RESET button. The values to be set in the setting mode are for
instance the address code of the relay module
A set value is stored in the memory by pressing and the data transfer rate for the serial commu-
the push-buttons STEP and RESET simultane- nication. Further the percentage values for the
ously. In practice the RESET button must be remote settings can be changed.
4
Example 1: Function in the setting mode. Manual setting of g)
the address code of a relay module and the data Set the digit by means of the STEP button.
transfer rate for the serial communication. The
initial value for the address code is 146.
a)
Press push-button STEP until register address A
appears on the display. h)
Store the set address number in the memory of
the relay module by pressing the RESET and
STEP button simultaneously. At the moment
the information enters the memory, the three
green dashes flash in the display, i.e. A—.
b)
Press the RESET button for about 10 s until the
right most digit starts flashing.
i)
Leave the setting mode by pressing the RESET
button for about 10 s, until the display stops
flashing.
c)
Press the STEP button repeatedly to set the digit
to the value desired.
j)
Then enter submenu 1 of register A by pressing
the RESET button for approx. one second. The
d) register address A is then replaced by a flashing
Press the RESET button to make the middle of 1. This submenu is used for setting the data
the green digits flash. transfer rate of the serial communication.
e) k)
Set the middle address digit by means of the The data transfer rate for the serial communica-
STEP button. tion is set and stored in the same way as the
address, see sections b...i, except that the con-
tinuously glowing register address has been re-
placed by a flashing 1.
l)
After storing the data transfer rate for the serial
f) communication you may return to the main
Press the RESET button to make the left most menu of register A by pressing the STEP button
green digit flash. for about 0.5 second.
5
Stored information The parameter values measured at the moment Register A contains the address code of the relay
when a fault occurs are recorded in the registers, module as required by the serial communication
in some modules also the setting values. The system. Example 1 on page 4 shows how the
recorded data, except for some setting param- address code is altered. Submenu 1 of register A
eters, are set to zero by pressing the push- contains the data transfer rate value expressed in
buttons STEP and RESET simul-taneously. kilobaud for the serial communication.
The data in normal registers are erased if the
auxiliary voltage supply to the relay is disrupted, Submenu 2 of register A contains a bus traffic
only the set values and the number of monitor for the SPACOM system. If the protec-
autoreclosings are maintained in the registers at tive relay, which contains the relay module, is
a voltage failure. linked to a system including the control data
communicator and the data communication
The number of the registers varies with different system is operating, the counter reading of the
module types. The function of the registers are monitor will be zero. Otherwise the digits 1...255
illustrated in the descriptions of the separate are continuously rolling in the monitor.
relay modules. Additionally, the system panel
contains a simplified list of the data recorded by Submenu 3 contains the password required for
the various relay modules of the relay assembly. changing the remote settings. The address code,
the data transfer rate for the serial communica-
All C-type relay modules are provided with two tion and the password can be set manually or via
general registers: register 0 and register A. the serial communication bus. For manual set-
ting see example 1.
Register 0 contains, in coded form, the informa-
tion about e.g. external blocking signals and The start value for the address code and the
status information for the circuit breaker. The password is 001 and that for the data transfer
codes are explained in the descriptions of the rate 9.6 kilobaud.
relay modules.
6
Trip-test mode Register 0 also allows access to the so called The selected starting or tripping is activated by
Trip-test function, which allows the output simultaneous pressing of the push-buttons STEP
signals of the relay module to be activated one by and RESET. The signal remains activated as
one. If the auxiliary relay module of the protec- long as the two push-buttons are being pressed.
tion assembly is in place, the auxiliary relays will
be included in the testing. The self-supervision output is activated by press-
ing the STEP button once when no setting knob
When pressing the RESET button for about 10 indicator is flashing. The IRF output is acti-
seconds, the three green digits to the right start vated in about 5 seconds after pressing of the
flashing to indicate that the relay module is in STEP button, and resets after that. Simultane-
test position. The indicators of the setting knobs ously, the display returns to the main menu and
indicate by flashing which output signal can be performs the initial testing indicated by rolling
activated. The required output function is se- digits 0...9 in the display several times.
lected by pressing the RESET button for about
1 second, until the following LED indicator The signals are selected in the order illustrated in
starts flashing. fig. 4.
Fig. 4. Sequence order for selecting the output signals in the Trip-test mode.
If e.g. the indicator of the setting knob 2 (second Trip-test sequence scheme, by pressing the
from the top) is flashing, and the push-buttons RESET button for about 10 seconds. If the
STEP and RESET are being pressed, the signal module is left in the Trip-test mode, it will
TS1 (tripping of stage 1) is activated. Return to return automatically after approx. 5 minutes.
the main menu is possible at any stage of the
7
Example 2: Trip-test function. Forced activation of the out- d)
puts is made as follows: Press the RESET button for about 1 second
until the indicator of the second setting knob
starts flashing.
a)
Step forward on the display to register 0.
e)
Press the push-buttons RESET and STEP si-
multaneously to activate tripping of stage 1 (e.g.
b) the I>-stage of the overcurrent module SPCJ
Press the RESET button for about 10 seconds 3C3). The indicator of the concerned stage
until the three green digits to the right and the starts glowing red.
LED indicator of the uppermost setting knob
start flashing.
f)
Starting and tripping of the second stage is
c) activated in the same way as stage 1. The indica-
Press the push-buttons RESET and STEP si- tor of the third or fourth setting starts flashing to
multaneously. Then the starting of stage 1 (e.g. indicate that the concerned stage has been acti-
the I>-stage of the overcurrent module SPCJ vated.
3C3) is activated and, simultaneously, the indi-
cator of the stage starts glowing yellow. g)
To activate the self-supervision output step to-
wards the test position, where no indicator is
flashing. Press the STEP button once. In about
5 seconds the red IRF indicator starts glowing
and the IRF output is activated. Shortly thereaf-
ter the indicator goes out and the output auto-
matically resets. At the same time the module
leaves the test position.
h)
It is possible to leave the trip test mode at any
step of the sequence scheme by pressing the
RESET button for about 10 seconds until the
three digits to the right stop flashing.
8
Operation A measuring relay module is provided with two The operation indicator starts glowing yellow
indicators separate operating stages, each of which with its when the operating stage starts and red when a
own yellow/red operation indicator on the lower delayed tripping operates. The functions of the
part of the front plate of the relay module. start and operation indicators are described in
detail in the different protection relay module
manuals.
Fault codes In addition to the protective functions the relay In most fault situations a fault code, indicating
module is provided with a self-supervision sys- the nature of the fault, appears on the display of
tem which continuously supervises the function the module. The fault code, which consists of a
of the microprocessor, its program execution red digit (1) and a three digit green code number,
and the electronics. cannot be removed from the display by reset-
ting. When a fault occurs, the fault code should
When the self-supervision system has detected a be recorded and stated when service is ordered.
permanent fault in the relay module, the red
IRF indicator on the panel starts glowing soon
after the fault was discovered. At the same time
the module puts forward a signal to the self-
supervision contact of the relay assembly.
9
1MRS 750658-MUM EN
ABB Oy
Substation Automation
P.O.Box 699
FIN-65101 VAASA
Finland
Tel. +358 (0)10 22 11
Fax.+358 (0)10 22 41094
www.abb.com/substationautomation