Design of Column

The document provides design details for columns to support a building. It includes: - Material properties and load calculations for different building components. - Load calculations and design of three 250x250mm wooden columns, including checking bending stress, compressive stress, and stability. - The columns were determined to be safe to support the calculated loads from building components like trusses, girders and room loads.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
38 views

Design of Column

The document provides design details for columns to support a building. It includes: - Material properties and load calculations for different building components. - Load calculations and design of three 250x250mm wooden columns, including checking bending stress, compressive stress, and stability. - The columns were determined to be safe to support the calculated loads from building components like trusses, girders and room loads.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 20

DESIGN OF COLUMNS

Kind of Wood = YAKAL


Allowable Bending Stess = 24.5 Mpa
Modulus of Elasticity = 9780 Mpa
Allowable Compressive Stess = `15.8 Mpa
Height of Column = 4m
Distance of Girder from the Ground = 1.5 m
Wind Load = 0.497 kPa

REACTION FOR GIRDERS


Uniform Load Acting LENGTH REACTION
ROOMS
on Girders (kN/m) (m) (kN)
Classroom 1 7.01 5 17.54
Classroom 2 7.61 5 19.03
Library 22.05 5 55.13
Reading/ Working Room 10.11 5 25.08
Faculty 8.86 5 22.15
Conference Room 8.86 5 22.15
Guidance Office 7.67 5 19.17
Principal's Office 7.67 5 19.17
Storage Room 17.86 5 44.65
Hallway 13.67 5 34.17

DETERMINATION OF DEAD LOAD


Weight of Roofing Materials (Wrm) = 1.199kPa
Weight of Ceiling (Wc) = 0.48kPa
Weight of Bracing System (Wbs) = 0.072kPa
Wind Velocity = 200kph

FORMULA USED in DETERMINATION of WIND LOAD Determination of Wind Load acting


ɵ=tan-1 (height of truss/length of truss) Vertically:
Pn=P(2sinɵ)/(1+sin2ɵ) Pv= Pncosɵ
Weight of Wooden Truss (Wwt)
where= P= 0.0000437V2 Wwt= 23.927 + 11.722L
= 4.37E-05 (200)2 Total Weight for the Truss (Wt)
= 1.892 kPa Wt= Wrm + Wc + Wbs + Pv + Wwt

TRUSS NO. HEIGHT LENGTH ɵ Pn(kPa) Pv(kPa) Wwt(Pa) Wt(kPa)


MAIN TRUSS 2.2 7.5 16.35 0.987 0.491 199.757 2.898
DESIGN OF COLUMN 1

Pv= Pn cos(16.35) Pv= Pn cos(16.35)


Pv=0.987 cos(16.35) = 0.947 kPa Pv=0.987 cos(16.35) =

Weight of Truss = 2.898 kPa Weight of Truss


Total Weight acting on Column = 3.84 kPa Total Weight acting on

Reaction of Classroom 1,3,8,6 Girder = 17.54 kN Reaction of Classroom


Reaction of Hallway Girder = 34.17 kN Reaction of Hallway G
Tributary Area = 9.375 m 2 Tributary Area

Try: 250 mm x 250 mm Wooden Column Try:


P= 2(17.54) + 2(34.17) + 3.84(9.38)= = 139.42 kN P=
Per= 17.54+17.54 = 35.08 Per=
Pel= 34.17+13.17 = 68.34 Pel=
M = Pe L' 68.34(0.125) (1.5/4) - 35.08(0.125) (1.5/4) = 1.56 kN-m M = Pe L'
L L

CHECKING: CHECKING:
le = 3500 = 14 > 11 le =
d 250 d

k= 0.671 √ E / Fc = 16.69 k=

le >k THEREFORE: INTERMIDIATE COLUMN le


d d

F'c = 0.3E = 0.3(9780) = 14.97 Mpa F'c =


(le/d)2 (14 2)

fc = P= 139.42 = 2.23072 Mpa fc =


A 250X250
fb= 6M 6(1.56X10^6) = 0.599 Mpa fb=
bd2 (250)(250 2)

fa + fb < 1 fa +
Fa Fb Fa
2.23072 0.599 = 0.1734617 2.4323072
+
14.97 24.5 14.97
SAFE!
DESIGN OF COLUMN 2

Pv= Pn cos(16.35) Pv= Pn cos(16.35)


Pv=0.987 cos(16.35) = 0.947 kPa Pv=0.987 cos(16.35) =

Weight of Truss = 2.898 kPa Weight of Truss


Total Weight acting on Column = 3.84 kPa Total Weight acting on Colu

Reaction of Classroom 2,4,7,5 Girder = 19.03 kN Reaction of Conference Gird


Reaction of Hallway Girder = 34.17 kN Reaction of Hallway Girder
Tributary Area = 11.88 m 2 Tributary Area

250 mm x 250 mm Wooden Column Try:


2(19.03) + 2(34.17) + 3.84(11.88) = 152.0192 kN P=
19.03 + 19.03 = 38.06 Per=
34.17 + 34.17 = 68.34 Pel=
68.34(0.125) (1.5/4) - 38.06(0.125) (1.5/4) = 1.419375 kN-m M = Pe L'
L

CHECKING: CHECKING:
3500 = 14 > 11 le =
250 d

0.671 √ E / Fc = 16.69 k=

>k THEREFORE: INTERMIDIATE COLUMN le


d

0.3E = 0.3(9780) = 14.97 Mpa F'c =


(le/d)2 (14 2)

P= 152.0192 = 2.4323072 Mpa fc =


A 250X250
6M 6(1.42X10^6) = 0.54504 Mpa fb=
bd2 (250)(250 2)

fb < 1 fa +
Fb Fa
0.54504 = 0.184725301 2.26304
+
24.5 14.97
SAFE!
DESIGN OF COLUMN 3

Pv= Pn cos(16.35) Pv= Pn cos(16.35)


Pv=0.987 cos(16.35) = 0.947 kPa Pv=0.987 cos(16.35) =

Weight of Truss = 2.898 kPa Weight of Truss


Total Weight acting on Column = 3.84 kPa Total Weight acting on Column

Reaction of Conference Girder = 22.15 kN Reaction of Library Girder


Reaction of Hallway Girder = 34.17 kN Reaction of Hallway Girder
Tributary Area = 7.5 m 2 Tributary Area

250 mm x 250 mm Wooden Column Try: 250 mm x 250 mm Wo


2(22.15) + 2(34.17) + 3.84(7.5) = 141.44 kN P= 2(53.13) + 2(34.17) + 3
22.15 + 22.15 = 44.3 Per= 53.13
34.17 + 34.17 = 68.34 Pel= 34.17
68.34(0.125) (1.5/4) - 44.3(0.125) (1.5/4) = 1.126875 kN-m M = Pe L' 68.34(0.125) (1.5/4)-10
L

CHECKING: CHECKING:
3500 = 14 > 11 le = 3500 =
250 d 250

0.671 √ E / Fc = 16.69 k= 0.671 √ E / Fc =

>k THEREFORE: INTERMIDIATE COLUMN le >k


d

0.3E = 0.3(9780) = 14.97 Mpa F'c = 0.3E =


(le/d)2 (14 2) (le/d)2

P= 141.44 = 2.26304 Mpa fc = P=


A 250X250 A
6M 6(1.13X10^6) = 0.43272 Mpa fb= 6M
bd2 (250)(250 2) bd2

fb < 1 fa + fb < 1
Fb Fa Fb
0.43272 = 0.1688337 3.4848
+ +
24.5 14.97
SAFE!
DESIGN OF COLUMN 4 DESIGN

Pv= Pn cos(16.35)
cos(16.35) = 0.947 kPa Pv=0.987 cos(16.35) =

= 2.898 kPa Weight of Truss


ght acting on Column = 3.84 kPa Total Weight acting on Column

f Library Girder = 53.13 kN Reaction of Reading Room Girder


f Hallway Girder = 34.17 kN Reaction of Hallway Girder
= 11.25 m 2 Tributary Area

250 mm x 250 mm Wooden Column Try: 250 mm x 250 mm Wooden Colum


2(53.13) + 2(34.17) + 3.84(11.25) = 217.8 kN P= 2(25.08) + 2(34.17) + 3.84(11.25)
+ 53.13 = 106.26 Per= 25.08 +
+ 34.17 = 68.34 Pel= 34.17 +
68.34(0.125) (1.5/4)-106.26(0.125) (1.5/4) = 1.7775 kN-m M = Pe L' 68.34(0.125) (1.5/4)-50.16(0.125)
L

CHECKING:
14 > 11 le = 3500 = 14 > 11
d 250

0.671 √ E / Fc = 16.69 k= 0.671 √ E / Fc =

THEREFORE: INTERMIDIATE COLUMN le >k THEREFORE: INTE


d

0.3(9780) = 14.97 Mpa F'c = 0.3E = 0.3(9780)


(14 2) (le/d)2 (14 2)

217.8 = 3.4848 Mpa fc = P= 161.7


250X250 A 250X250
6(1.78X10^6) = 0.68256 Mpa fb= 6M 6(0.85X10^6) =
(250)(250 2) bd2 (250)(250 2)

fa + fb < 1
Fa Fb
0.68256 = 0.2606452 2.5872 0.32724
+
24.5 14.97 24.5
SAFE! SAFE!
DESIGN OF COLUMN 5 DESIGN OF COLU

Pv= Pn cos(16.35)
0.947 kPa Pv=0.987 cos(16.35) = 0.947

= 2.898 kPa Weight of Truss


= 3.84 kPa Total Weight acting on Column

Room Girder = 25.08 kN Reaction of Faculty Room Girder


= 34.17 kN Reaction of Hallway Girder
= 11.25 m 2 Tributary Area

250 mm Wooden Column Try: 250 mm x 250 mm Wooden Column


2(34.17) + 3.84(11.25) = 161.7 kN P= 2(22.15) + 2(34.17) + 3.84(11.25)
25.08 = 50.16 Per= 22.15 + 22.15
34.17 = 68.34 Pel= 34.17 + 34.17
25) (1.5/4)-50.16(0.125) (1.5/4) = 0.8521875 kN-m M = Pe L' 68.34(0.125) (1.5/4)-44.3(0.125) (1.5/4)
L

CHECKING:
le = 3500 = 14 > 11
d 250

16.69 k= 0.671 √ E / Fc = 16.69

THEREFORE: INTERMIDIATE COLUMN le >k THEREFORE: INTERMIDIATE


d

= 14.97 Mpa F'c = 0.3E = 0.3(9780) =


(le/d)2 (14 2)

= 2.5872 Mpa fc = P= 155.84 =


A 250X250
6(0.85X10^6) = 0.32724 Mpa fb= 6M 6(1.13X10^6) =
(250)(250 2) bd2 (250)(250 2)

fa + fb < 1
Fa Fb
= 0.1861824 2.49344 0.43272 =
+
14.97 24.5
SAFE!
DESIGN OF COLUMN 6 DESIGN OF COLUMN 7

Pv= Pn cos(16.35)
kPa Pv=0.987 cos(16.35) = 0.947 kPa

= 2.898 kPa Weight of Truss =


= 3.84 kPa Total Weight acting on Column =

= 22.15 kN Reaction of Guidance Office Girder =


= 34.17 kN Reaction of Hallway Girder =
= 11.25 m 2 Tributary Area =

ooden Column Try: 250 mm x 250 mm Wooden Column


= 155.84 kN P= 2(19.17) + 2(34.17) + 3.84(6.25) =
= 44.3 Per= 19.17 + 19.17 =
= 68.34 Pel= 34.17 + 34.17 =
44.3(0.125) (1.5/4) = 1.126875 kN-m M = Pe L' 68.34(0.125) (1.5/4)-38.34(0.125) (1.5/4)
L

CHECKING:
le = 3500 = 14 > 11
d 250

k= 0.671 √ E / Fc = 16.69

ORE: INTERMIDIATE COLUMN le >k THEREFORE: INTERMIDIATE COLUM


d

14.97 Mpa F'c = 0.3E = 0.3(9780) = 14.97


(le/d)2 (14 2)

2.49344 Mpa fc = P= 130.68 = 2.09088


A 250X250
0.43272 Mpa fb= 6M 6(1.41X10^6) = 0.54
bd2 (250)(250 2)

fa + fb < 1
Fa Fb
0.1842245 2.09088 0.54 = 0.1617122
+
14.97 24.5
SAFE!
GN OF COLUMN 7 DESIGN OF COLUMN 8

Pv= Pn cos(16.35)
Pv=0.987 cos(16.35) = 0.947 kPa

2.898 kPa Weight of Truss = 2.898


3.84 kPa Total Weight acting on Column = 3.84

19.17 kN Reaction of Principal's Office Girder = 19.17


34.17 kN Reaction of Hallway Girder = 34.17
6.25 m 2 Tributary Area = 5

Try: 250 mm x 250 mm Wooden Column


130.68 kN P= 2(19.17) + 2(34.17) + 3.84(5) = 125.88
38.34 Per= 19.17 + 19.17 = 38.34
68.34 Pel= 34.17 + 34.17 = 68.34
= 1.40625 kN-m M = Pe L' 68.34(0.125) (1.5/4)-38.34(0.125) (1.5/4) =
L

CHECKING:
le = 3500 = 14 > 11
d 250

k= 0.671 √ E / Fc = 16.69

ERMIDIATE COLUMN le >k THEREFORE: INTERMIDIATE COLUMN


d

Mpa F'c = 0.3E = 0.3(9780) = 14.97 Mpa


(le/d)2 (14 2)

Mpa fc = P= 125.88 = 2.01408 Mpa


A 250X250
Mpa fb= 6M 6(1.41X10^6) = 0.54 Mpa
bd2 (250)(250 2)

fa + fb < 1
Fa Fb
2.01408 0.54 = 0.1565819
+
14.97 24.5
SAFE!
LUMN 8 DESIGN OF COLUMN 9

Pv= Pn cos(16.35)
Pv=0.987 cos(16.35) = 0.947 kPa

kPa Weight of Truss = 2.898 kPa


kPa Total Weight acting on Column = 3.84 kPa

kN Reaction of Storage Room Girder = 44.65 kN


kN Reaction of Hallway Girder = 34.17 kN
m2 Tributary Area = 8.75 m 2

Try: 250 mm x 250 mm Wooden Column


kN P= 2(44.65) + 2(34.17) + 3.84(8.75) = 191.24 kN
Per= 44.65 + 44.65 = 89.3
Pel= 34.17 + 34.17 = 68.34
1.40625 kN-m M = Pe L' 68.34(0.125) (1.5/4)-89.3(0.125) (1.5/4) = 0.9825
L

CHECKING:
le = 3500 = 14 > 11
d 250

k= 0.671 √ E / Fc = 16.69

TE COLUMN le >k THEREFORE: INTERMIDIATE COLUMN


d

F'c = 0.3E = 0.3(9780) = 14.97 Mpa


(le/d)2 (14 2)

fc = P= 191.24 = 3.05984 Mpa


A 250X250
fb= 6M 6(0.98X10^6) = 0.37728 Mpa
bd2 (250)(250 2)

fa + fb < 1
Fa Fb
3.05984 0.37728 = 0.2197973
+
14.97 24.5
SAFE!