Coordinated Power System Protection

This technical manual from the US Army provides guidance on coordinated power system protection. It discusses electrical power system overcurrents such as normal current, overload current, short-circuit current and ground-fault current. It also covers overcurrent protective devices like motor overload relays, fuses, circuit breakers and protective relays. The bulk of the document focuses on protective device coordination, including primary and low-voltage coordination as well as ground-fault coordination. It provides examples and discusses protection of various electrical system components.

Uploaded by

socee
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
104 views

Coordinated Power System Protection

This technical manual from the US Army provides guidance on coordinated power system protection. It discusses electrical power system overcurrents such as normal current, overload current, short-circuit current and ground-fault current. It also covers overcurrent protective devices like motor overload relays, fuses, circuit breakers and protective relays. The bulk of the document focuses on protective device coordination, including primary and low-voltage coordination as well as ground-fault coordination. It provides examples and discusses protection of various electrical system components.

Uploaded by

socee
Copyright
© Attribution Non-Commercial (BY-NC)
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

TM 5-811-14

A
TECHNICAL MANUAL HEADQUARTERS
No. 5-811-14 DEPARTMENT OF THE ARMY
Washington, DC, 25 February 1991

COORDINATED POWER SYSTEM PROTECTION


Paragraph Page
CHAPTER 1. GENERAL REQUIREMENTS
Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1 1-1
Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2 1-1
References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3 1-1
Electrical power systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-4 1-1
Design procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-5 1-1
CHAPTER 2. ELECTRICAL POWER SYSTEM OVERCURRENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-1 2-1
Normal current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2 2-1
Overload current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3 2-1

APPROVED FOR PUBLIC RELEASE: DISTRIBUTIONS IS UNLIMITED


Short-circuit current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4 2-1
Ground-fault current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5 2-1
Sources of short-circuit current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6 2-2
Time variation of short-circuit current . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7 2-3
Symmetrical and asymmetrical short-circuit current . . . . . . . . . . . . . . . . . . 2-8 2-5
CHAPTER 3. OVERCURRENT PROTECTIVE DEVICES
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-1 3-1
Motor overload relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2 3-1
Fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-3 3-1
Motor short-circuit protectors (MSCP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4 3-3
Circuit breakers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5 3-3
Protective relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6 3-9
Automatic reclosing devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-7 3-10
CHAPTER 4. PROTECTIVE DEVICES COORDINATION
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-1 4-1
The coordination study . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-2 4-1
Primary and medium-voltage coordination . . . . . . . . . . . . . . . . . . . . . . . . . 4-3 4-3
Low-voltage coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4 4-5
Ground-fault coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-5 4-5
Coordination requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6 4-6
Maintenance, testing, and calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7 4-7
Example of phase coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8 4-7
Example of ground-fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-9 4-23
CHAPTER 5. ELECTRICAL SYSTEM PROTECTION TECHNIQUES
Generator protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-1 5-1
Transformer protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2 5-6
Conductor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3 5-15
Motor protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4 5-20
Bus and switchgear protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5 5-29
Ground-fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-6 5-34
Miscellaneous equipment protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-7 5-44
Appendix A. REFERENCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Appendix B. TYPICAL PROTECTIVE DEVICE SETTINGS . . . . . . . . . . . . . . . . . . . B-1
Appendix C. TYPICAL TIME-CURRENT CHARACTERISTIC CURVES . . . . . . . . C-1
Appendix D. TYPICAL DEVICE AND EQUIPMENT RATINGS . . . . . . . . . . . . . . . . D-1
Appendix E. PARTIAL RELAY DEVICE NUMBERS LIST . . . . . . . . . . . . . . . . . . . . E-I
Appendix F. REPRESENTATIVE PROTECTIVE DEVICE OPERATING TIMES . . F-1
Appendix G. COORDINATION EXAMPLES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-1
Appendix H. COMPUTER SOFTWARE APPLICATIONS . . . . . . . . . . . . . . . . . . . . . . H-1
BIBLIOGRAPHY . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Bibliography-1
GLOSSARY ........................................................... Glossary-1

i
TM 5-811-14
LIST OF FIGURES
Figure No. Title Page
2-1. Short-circuit waveforms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-4
2-2. Symmetrical and asymmetrical current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
3-1. Solid-state circuit breaker characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-4
3-2. Solid-state ground-fault characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-5
4-1. Army ammunition plant single-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-4
4-2. Ground-fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
4-3. Single-line diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-8
4-4. Key protection points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-10
4-5. LC feeder protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-12
4-6. IC MAIN protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14
4-7. Switchgear feeder protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-16
4-8. Switchgear main protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-18
4-9. Composite time-current curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20
4-10. Composite time-current curve using solid-state devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22
4-11. Low-voltage ground-fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24
5-1. Single-isolated low-voltage generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-2
5-2. Multi-isolated medium-voltage generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-3
5-3. Medium industrial generators (up to 12.5MVA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-4
5-4. Large industrial generators (greater than 12.5MVA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-5
5-5. Through-fault protection curve for liquid-immersed category I transformers (5kVA to 500kVA single-
phase, 15kVA to 500kVA three-phase) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-8
5-6. Through-fault protection curves for liquid-immersed category II transformers (501kVA to 1667kVA
single-phase, 501kVA to 5000kVA three-phase) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-9
5-7. Through-fault protection curves for liquid-immersed category Ill transformers (1668kVA to 10,000kVA
single-phase, 5001kVA to 10,000kVA single-phase, 5001kVA to 30,000kVA three-phase) . . . . . 5-10
5-8. Through-fault protection curve for liquid-immersed category IV transformers (above 10,000kVA single-
phase, above 30,000kVA three-phase) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-11
5-9. Transformer overcurrent protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-13
5-10. Phase differential relaying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-15
5-11. Maximum short-circuit current for insulated copper conductors; initial temperature 75 degrees C; final
temperature 200 degrees C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-17
5-12. Emergency overload current percent of continuous rating EPR-XLP insulated 40 degrees C ambient . 5-19
5-13. Motor circuit requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-21
5-14. Minimum protection for induction motor less than 1500 Hp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-23
5-15. Minimum protection for induction motor 1500 HP and larger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-24
5-16. Minimum protection for MV, brushless synchronous motor less than 1500 Hp . . . . . . . . . . . . . . . . . . . 5-25
5-17. Minimum protection for MV, brushless synchronous motor 1500 Hp and larger . . . . . . . . . . . . . . . . . 5-26
5-18. Motor self-balance differential protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-28
5-19. Single bus scheme with bus differential relaying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-30
5-20. Sectionalized bus scheme with bus differential relaying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-31
5-21. Double bus scheme with bus differential relaying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-32
5-22. Synchronizing bus scheme with bus differential relaying . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-33
5-23. Residual or common relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-35
5-24. Zero-sequence relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-36
5-25. Ground return relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-37
5-26. Ground differential relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-38
5-27. Standard overcurrent protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-40
5-28. Main-only ground-fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-41
5-29. Improved ground-fault protection and coordination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-42
5-30. Main and feeder ground-fault protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-43
C-1. Time-current characteristic curves for typical motor overload relay . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-2
C-2. Time-current characteristic curve for typical solid state circuit breaker . . . . . . . . . . . . . . . . . . . . . . . . . C-3
C-3. Time-current characteristic curve for typical ground fault attachment . . . . . . . . . . . . . . . . . . . . . . . . . . C-4
C-4. Time-current characteristic curve for typical protective relay (50/51) . . . . . . . . . . . . . . . . . . . . . . . . . . C-5
C-5. Time-current characteristic curve for typical medium-voltage fuse . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-6
C-6. NEMA damage curves (through 1200A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-7
C-7. NEMA damage curves (through 5000A) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . C-S
G-1. Example electrical system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-2
G-2. 14kV switchgear feeder No.4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-3
G-3. 15kV switchgear feeder No.7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-4

ii
TM 5-811-14
LIST OF FIGURES — Continued
Figure No. Title Page
G-4. M1 starting, overload, and CB short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-7
G-5. M2 starting, overload, and CB short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-8
G-6. M3 starting, overload, and CB short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-9
G-7. M4 starting, overload, and CB short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-10
G-8. Composite time-current curves for Example 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-11
G-9. M1 starting, overload, and MCP short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-14
G-10. M2 starting, overload, and MCP short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-15
G-11. MS starting, overload, and MCP short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-16
G-12. M4 starting, overload, and MCP short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-17
G-13. Composite time-current curves for Example 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-18
G-14. M1 starting, overload, and fuse short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-20
G-15. M2 starting, overload, and fuse short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-21
G-16. M3 starting, overload, and fuse short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-22
G-17. M4 starting, overload, and fuse short-circuit protection curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-25
G-18. Ground-fault protection at main only (nonselective, single-zone) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-25
G-19. Ground-fault protection at main feeder, and branch (selective, time coordinated) . . . . . . . . . . . . . . . . . G-26
G-20. Impedance diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-28
G-21. Per unit diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-29
G-22. M5 staffing, overload and fuse short-circuit curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-31
G-23. Protective relays 1, 2, 3, 5, 6 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-33
G-24. Protective relays 1, 2, 3, 4, 7 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-35

LIST OF TABLES
Table No. Title Page
3-1. UL fuse classifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-2
3-2. Circuit breaker trip ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-6
3-3. Circuit breaker application comparision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-9
4-1. Maximum overcurrent protection (in percent ) per NFPA 70 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-7
4-2. Summary of initial protective device settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
4-3. Summary of new settings using solid-state devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23
D-1. Low voltage fuse ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-1
D-2. Distribution fuse cutouts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D-3. Expulsion-type power fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D-4. Boric acid type power fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D-5. Current-limiting power fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D-6. Typical tap ranges and settings of time-overcurrent relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
D-7. Typical reactances of three-phases synchronous machines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . D-2
F-1. Relayed circuit breakers, 2.4-13.8kV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
F-2. Power air circuit breakers, below 600V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
F-3. Molded-case circuit breakers, below 600V . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
F-4. Medium-and high-voltage fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
F-5. Low-voltage fuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . F-1
G-1. Summary of device settings for figure G-23 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-32
G-2. Summary of device settings for figure G-24 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . G-34

iii