17.PZ1000 Testing Tool, CSPC (With ARC Resistance)

The document describes the testing of a PZ1000 distance protection relay. It provides the zone and phase settings for zones 1 through 4 for both phase-to-phase and phase-to-earth faults. It also lists the directional line angle settings and settings for the pilot protection scheme (PSB) including resistance, reactance, and time delay. The settings were tested using the RELZ 100 relay characteristic simulator software from Doble Engineering Pvt Ltd in India.

Uploaded by

naran19794735
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
62 views15 pages

17.PZ1000 Testing Tool, CSPC (With ARC Resistance)

The document describes the testing of a PZ1000 distance protection relay. It provides the zone and phase settings for zones 1 through 4 for both phase-to-phase and phase-to-earth faults. It also lists the directional line angle settings and settings for the pilot protection scheme (PSB) including resistance, reactance, and time delay. The settings were tested using the RELZ 100 relay characteristic simulator software from Doble Engineering Pvt Ltd in India.

Uploaded by

naran19794735
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 15

Testing of distance Protection Relay Type PZ1000

Zone-1 settings:

Ph-Ph Fault settings


Z1ph 4.15 Ohm Ohms/Phase
Characteristic angle 68.8 ° Degree
t1 for Zone-1 0.04 s s

Ph-E Fault settings


X1N 4.35 Ohm Ohms/Loop
R1N 19.55 Ohm Ohms/Loop
Characteristic angle 68.8 ° Degree
t1 for Zone-1 0.04 s s
Kn 0.59 00.590,
Zone-2 settings:

Ph-Ph Fault settings


Z2ph 6.2 Ohm Ohms/Phase
R1ph 4.8 Ohm Ohms/Phase
Characteristic angle 68.8 ° Degree
t2 for Zone-1 0.44 s s
Ph-E Fault settings
X1N 6.4 Ohm Ohms/Loop
X1N 13.568 Ohm Ohms/Loop
R1N 34.08 Ohm Ohms/Loop
Characteristic angle 70 ° Degree
t2 for Zone-1 0.44 s s
Kn 1.12 01.120,
Zone-3 settings:

Ph-Ph Fault settings


X1ph 7.1 Ohm Ohms/Phase
R1ph 7.97 Ohm Ohms/Phase
Characteristic angle 70 ° Degree
t3 for Zone-1 0.8 s s
Ph-E Fault settings
X1N 18.3 Ohm Ohms/Loop
X1N 29.097 Ohm Ohms/Loop
R1N 41.22 Ohm Ohms/Loop
Characteristic angle 70 ° Degree
t3 for Zone-1 0.8 s s
Kn 0.59 00.590,
Zone-4 settings(Reverse
Zone):

Ph-Ph Fault settings


X1ph 10.99 Ohm Ohms/Phase
R1ph 1.99 Ohm Ohms/Phase
Characteristic angle 70 ° Degree
t4 for Zone-1 1.6 s s

Ph-E Fault settings


X1N 0.51 Ohm Ohms/Loop
X1N 0.8109 Ohm Ohms/Loop
R1N 2.3 Ohm Ohms/Loop
Characteristic angle 70 ° Degree
t4 for Zone-1 1.6 s s
Kn 0.59 00.590,

Directional Line Ang-1 115 ° Degree


Directional Line Ang-2 -15 ° Degree

PSB
R 25 Ohm Ohms
X 55 Ohm Ohms
t 50 ms ms

Doble Engineering Pvt Ltd


305-Sakar
Old padra road
Vadodara-390 015
India
Email: [email protected]
RELZ 100 RELAY CHARACTERISTIC SIMULATOR - KAMIN DAVE- DOBLE ENGINEERING PVT. LTD, 305-SAKAR, OLD PADRA R

PH-G Char with "RLOOP"


35

30

25

20

15
X in Ohms

10

0
-20 -10 0 10 20 30 40 50
-5

-10

-15 R in Ohms
PH-G
ZONE-1:
R X ANG1 Z' R' ANG2 R Z'
POINT1 19.55 0 25 #REF! #REF! -15 19.55 20.23893
POINT2 19.55 #REF!
POINT3 0 #REF!
POINT4 #REF! #REF!
POINT5 0 0
POINT6 19.55 -5.235626
POINT7 19.55 0

ZONE-2:
R X ANG1 Z' R' ANG2 R Z'
POINT1 34.08 0 25 14.96909 -6.323209 -15 34.08 35.28096
POINT2 34.08 13.568
POINT3 0 13.568
POINT4 -6.323209 13.568
POINT5 0 0
POINT6 34.08 -9.126861
POINT7 34.08 0

ZONE-3:
R X ANG1 Z' R' ANG2 R Z'
POINT1 41.22 0 25 32.10168 -13.56032 -15 41.22 42.67257
POINT2 41.22 29.097
POINT3 0 29.097
POINT4 -13.56032 29.097
POINT5 0 0
POINT6 41.22 -11.039
POINT7 41.22 0

ZONE-4:
R X ANG1 Z' R' ANG2 R Z'
POINT1 -2.3 0 25 -0.894637 0.377911 -15 -2.3 -2.381051
POINT2 -2.3 -0.8109
POINT3 0 -0.8109
POINT4 0.377911 -0.8109
POINT5 0 0
POINT6 -2.3 0.615956
POINT7 -2.3 0
PVT. LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA

Z1
Z2
Z3
Z4

30 40 50
X'
-5.235626

X'
-9.126861
X'
-11.039

X'
0.615956
RELZ 100 RELAY CHARACTERISTIC SIMULATOR - KAMIN DAVE- DOBLE ENGINEERING PVT. LTD, 305-SAKAR, OLD PADRA R

PH-PH Char
80

60

40

20
X in Ohms

0
-30 -20 -10 0 10 20 30

-20

-40

-60

R in-80Ohms
PH-PH
ZONE-1:
R X ANG1 Z' R' ANG2 R Z'
POINT1 #REF! 0 25 4.578546 -1.934059 -15 #REF! #REF!
POINT2 #REF! 4.15
POINT3 0 4.15
POINT4 -1.934059 4.15
POINT5 0 0
POINT6 #REF! #REF!
POINT7 #REF! 0

ZONE-2:
R X ANG1 Z' R' ANG2 R Z'
POINT1 4.8 0 25 6.840238 -2.889438 -15 4.8 4.969149
POINT2 4.8 6.2
POINT3 0 6.2
POINT4 -2.889438 6.2
POINT5 0 0
POINT6 4.8 -1.285473
POINT7 4.8 0

ZONE-3:
R X ANG1 Z' R' ANG2 R Z'
POINT1 7.97 0 25 7.833175 -3.308873 -15 7.97 8.250858
POINT2 7.97 7.1
POINT3 0 7.1
POINT4 -3.308873 7.1
POINT5 0 0
POINT6 7.97 -2.134421
POINT7 7.97 0

ZONE-4:
R X ANG1 Z' R' ANG2 R Z'
POINT1 -1.99 0 25 -12.12487 5.121762 -15 -1.99 -2.060126
POINT2 -1.99 -10.99
POINT3 0 -10.99
POINT4 5.121762 -10.99
POINT5 0 0
POINT6 -1.99 0.532936
POINT7 -1.99 0

PSB:
R X
POINT1 25 0
POINT2 25 55
POINT3 0 55
POINT4 -25 55
POINT5 -25 0
POINT6 -25 -55
POINT7 0 -55
POINT8 25 -55
POINT9 25 0
PVT. LTD, 305-SAKAR, OLD PADRA ROAD, VADODARA

Z1
Z2
Z3
Z4
PSB
20 30
X'
#REF!

X'
-1.285473
X'
-2.134421

X'
0.532936
Testing of REL100 Distance Protection
Create RIO file for testing. "Press" on "Create RIO-File" button. It will create RIO file. Same RIO file have to be "Import" in F6TEST Software.

Nominal values
Generator CT / VT
Vn 6.6 kV KnI 2500 A / 1A
Sn 25 MVA KnV 6600 V / 110 V

secondary

DOBLE ENGINEERING PVT LTD