MiCOM P12x PDF
MiCOM P12x PDF
Protection Relays
MiCOM P12x/y
Three phase and earth fault overcurrent relays
The MiCOM P12x/y relays provides features for easy adaptation and are
suitable for all applications where overcurrent and earth-fault protection are
required.
The MiCOM P12x non-directional relays ranges from the single phase/earth
fault P120 up to the multifunction three phase and earth fault P123.
The MiCOM P12y directional relays ranges from the single phase/earth fault
P125 up to the multifunction three phase and earth fault P127, complete of
voltage and frequency protection functions.
Users particularly appreciate the friendliness of the Human Machine
Interface and the easy setting of the relays (that can be fully set through the
front HMI or using MiCOM S1 setting software).
In addition to its protection function, MiCOM P12x/y provides full
measurement and monitoring information necessary for efficient
maintenance and post-fault analysis.
Several communication protocols allow easy interfacing of the MiCOM
P12x/y relays in most of substation control or SCADA systems.
The MiCOM P12x/y range is housed in the same draw out 4U metal case for
panel or rack mounting with 20TE width (P120, P121, P122, P123 and P125)
or 30TE width (P126 and P127).
Application
MiCOM P12x/y provides a wide range of protection functions allowing its
use in several applications:
• Main or backup protection on MV&HV systems
Customer benefits • Overhead lines and underground cables as a backup on HV systems
• Neutral systems protection (Insolated, solid earthed, resistance earthed
• Integration of function leading to cost- and Petersen coil earthed)
effective solution • MV subscribers, Industry, Transport
• Generator and transformer scheme
• User friendly Human Machine Interface • High impedance scheme for busbar and machine protection
ANSI codes Features P120 P121 P122 P123 P125 P126 P127
50/51P/N 1 phase or earth overcurrent • •
50/51 3 phase overcurrent • • • • •
50/51N Earth overcurrent • • • • •
67P 3 phase directional overcurrent •
67N Earth fault directional overcurrent • • •
51V Voltage controlled overcurrent •
37 3 phase undercurrent • • • •
46 Negative phase sequence overcurrent • • • •
27/59 Phase under/over voltage (AND & OR mode) •
59N Residual over voltage • • •
Inrush blocking • • •
Switch on to fault (SOTF) • • •
Phase rotation • • •
CT/VT supervision (CTS/VTS) •
PROTECTION FUNCTIONS
Three-Phase Overcurrent (50/51) & Earth
Overcurrent (50N/51N)
Three independent stages are available either
for phase and earth fault protection. For the first
and second stage the user may independently
select definite time delay (DTOC) or inverse time
delay (IDMT) with different type of curves (IEC,
IEEE/ANSI, RI, RECT, EDF BPN). The third stage
can be configured for peak detection and with
definite time only. Each stage and related time
delay can be programmed to provide maximum A fourth earth overcurrent threshold based on derived earth current
selectivity. The IDMT stages have reset definite calculation is available on MiCOM P122, P123 and P127 (when no earth CT
or IDMT timer to reduce clearance times when is available).
intermittent faults occur. The MiCOM P12x/y relays have separate instantaneous and delayed
information for each stage. MiCOM P123, P126 & P127 can indicate the
phase(s) in fault by configuring output relays (first stage only)
Functional Overview (Description of ANSI code nos., see Protection Function Overview)
>`]bSQbW]\ :]UWQS_cObW]\a
CTs &W\RS^S\RS\baS_cObW]\a
! N # N /<2<=B=@UObSa
$% $% N 7SQ]a ## # N !% 46 "$01 "' #04
$^O`O[SbS`aW\SOQVS_cObW]\
@SacZb]\ZSRa]cb^cba
>]aaWPWZWbgb]W\VWPWbOZO`[
;SOac`S[S\b METERING
2Wa^ZOQS[S\bTOQb]` D]ZbOUSB62
1Ba >VOaSQc``S\b
3\S`UWSa 6O`O[]\WQdOZcSac^b]bVSbV
:W\SO\R^VOaSd]ZbOUS
1c``S\bB62B22 /\UZSdOZcSa
/QbWdSO\R`SOQbWdS^]eS`
Time
voltages. A synchronous polarising function is provided to ensure a correct I>
operation of the overcurrent elements for close-up three phase faults where t>
the collapse of the polarising line voltages occurs. In addition to the residual I>>
current, the residual voltage must be connected to a dedicated input or
internally calculated as vector sum (P127 only) in order to make possible t>>
I< I>>> t>>>
the directional operation of the earth-fault. Each earth-fault directional stage
measures the residual current, the residual voltage, and the angle between
residual voltage and current.
Current
Negative Sequence Overcurrent (46) All the 50/51 stages can be used for this
The MiCOM P122/3 & P126/7 relays include a programmable function application, the third stage configured in peak
specially designed to detect unbalanced load or fault conditions. mode is recommended for the best performance.
The three stages of negative sequence overcurrent have the same setting
ranges and time delay as the phase overcurrent.
RCA
angle
U
Broken Conductor (46BC)
I
A typical unbalanced fault that can occur on the system is an open circuit
fault. This fault can arise from broken conductor, discrepancy of one
switchgear poles position or blowing of a fuse. ard
Forw g
p in
MiCOM P122/3 and P126/7 relays are able to measure the ratio of negative trip
zo n e
to positive sequence current (I2/I1). This fully programmable function allows
more sensitivity and stability than pure negative sequence measurement.
270
Rate of Frequency (81R) 90
Q
Time delayed rate of frequency protection in 2°
180
MiCOM P127 is used for severe disturbances when shedding load in small
steps may not be sufficient.
It can also compliment the generator control system to reduce or shed
Directional Active Over / Under Protection
generation when the frequency rises above the nominal frequency at a high
rate.
MiCOM P12x/y:
the easy, safe and fast
way to detect the fault
in your power system
06
Protection Relays MiCOM P12x/y
Time
characteristics
to the load profile, avoiding unwanted trips.
Setting value can be increased by 800% during a settable duration. To
trigger this function, either CB close position can be use or an automatic
detection based on a sudden raise of current value.
Autorecloser (79)
MiCOM P123 and P126/7 relays include a 4-shot triphase autorecloser. All
the programmed protection functions may independently start any of the
shots and the user can program which functions are allowed to trip after any Nominal threshold Current
of the shots. This makes possible special reclosing cycles e.g. as requested
for coordination with fuses in distribution with tapped transformers.
To prevent excessive number of reclosing cycle in a short period of
time, a setting can be used to define the maximum number of reclosing
cycle allowed in a period of time after first one was detected. Dead and OPERATION & MAINTENANCE
reclaim times are freely adjustable. A counter stores the number of reclose Setting Groups
commands. This information is free locally or remotely. To inform operator External conditions may request the need for
that autorecloser has been blocked internally or externaly, output relays can different settings. MiCOM P122/3 and P125/6/7
be assigned to theses signals. provide two independents setting groups.
In MiCOM P127, up to 8 settings groups are
Outputs Contacts available to have a flexible management of
Any outputs, including trip, can be latched. Reset of the latched outputs is customer application schemes.
possible by digital input, operator action on the Human Machine Interface Target settings change (1 to 8) should be
or by remote communication (Digital Control System). performed by DCS or HMI since digital input
The two first output contacts (RL1 & RL2) can be used as failsafe relays to status change can only swich from one group
provide a “fail safe alarm” in case of power supply loss or major hardware to another. Duplication facilities have been
failure. Other available relays can be inverted to reverse NO relays implemented to ease engineering work.
operating condition (output relays closing when logical state of the signal
changes from 1 to 0). Circuit Breaker Command
To allow an easy and secured command of the
Communication & Synchronization circuit breaker through the HMI, a dedicated
The MiCOM P12x/y offers a wide range of communication protocols, menu has been created in MiCOM P122 / P123
allowing its utilization in most of the network control and data acquisition / P125 / P126 / P127. It’s now possible to send a
systems (via Modbus, IEC 60870-5-103, DNP3.0 & Courier/K-Bus). It has local open/close command through the HMI after
been designed for permanent multidrop connection through the rear RS485 operator confirmation.
communication port. A second RS485 is optionaly available on MiCOM
P127 for maintenance purpose with Modbus or IEC 60870-5-103.
The MiCOM P12x/y incorporates an internal clock to allow a 1ms accuracy
time tagging of alarms, events, fault and disturbance record. To avoid any
drifting of the time tagging clock, it’s necessary to periodically synchronize
the relays. To do this P12x/y offers two solutions:
Proven protection
as safe, simple and
versatile as your
application needs
07
Protection Relays MiCOM P12x/y
Trip Led
Fault Recording
The last 25 faults are stored inside the MiCOM P12x/y relays.
Alarm Led
Each fault includes: Record number/ Fault time / Active setting group /
Faulted phase / Protection operation / Magnitude of input quantities. Fault
Device fail.
indicator helps the user to clearly identify the fault and to monitor relay
Cursor
Power setting and operations as all information are available on the relay HMI.
Keys
Supply
Fault records are stored on a non volatile flash memory.
Freely
Programmable Disturbance Recording
Leds RS 232 Up to 5 disturbance files are stored in the relays. Even if the total duration
is fixed to 15s, it can be fully adjustable for easy adaptation to customer
requirements (1s / 3s / 5s / 7s / 9s).
Battery is not used anymore
There are stored in COMTRADE format.
The disturbance recording function is triggered either by any of
the programmed thresholds or by an external input, or through the
Circuit Breaker Monitoring and Supervision communications. All digital and analogical information are stored in a flash
Circuit-breaker preventive maintenance is an memory and can be transferred using the front communication port or the
advanced function provided by the MiCOM rear port to be used by an external data analyser. Disturbance records are
P122/3 and P126/7 relays with adjustable closing stored on a non volatile flash memory.
and opening time measurements. All fault phase
currents I or I2 are cumulated to inform about
total interrupted current. These relays allow trip Logic Equations
Gate logic
circuit supervision by using a specific input. The MiCOM P121/2/3 Optos
Relays
contacts
& P126/7 relays
integrate complete Protection
Event Recording logic equations to elements
To insure a compliance with any auxiliary voltage source and minimize • MX3AMxxx: First Numerical overcurrent
variants, a universal power supply board from 24 to 250Vac/dc is available
relay launched in 1995. More than
along the MiCOM P12x/y range.
14.000 devices installed.