Transformer Protection and Control RET620
Transformer Protection and Control RET620
G U I D E F O R M S P EC I F I C AT I O N
• The relay shall be able to eliminate the zero- • The relay shall have two separate non-directional
sequence current from the measured current. earth-fault (50N/51N) stages for remote earth-
Elimination of the zero-sequence current shall be faults and internal transformer earth-faults. The
possible for either the HV or LV winding or both. operation characteristic of the low and high-set
• Tap changer position compensation shall be stages shall be settable to either definite time (DT)
included to enable more sensitive settings to be or inverse definite minimum time (IDMT),
used. The correction of the transformation ratio sup¬porting various types of inverse curves,
due to changing tap changer positions shall be including a user-definable one.
done automatically based on the tap changer • The number of overcurrent and earth-fault
position information. elements shall be available for the LV and HV-side
respectively. It shall be possible to select the
Restricted earth-fault protection number of started phases for overcurrent
• The relay shall have both high-impedance (87NH) operation, either one, two or all three phases.
and low-impedance (87NL) restricted earth-fault • The relay shall include two negative-sequence
protection, freely selectable for both the HV and overcurrent protection (46) stages settable
LV-side. between 0.01 and 5 times pu.
• The stabilized restricted low-impedance earth-
fault protection (87NL) shall be based on the Overload protection
numerically stabilized differential current principle • The relay shall include three-phase thermal
and the neutral-current second harmonic shall be overload protection (49T) and shall protect the
used for blocking the function in a transformer transformer mainly from short-time overloads. The
inrush situation. No external stabilizing resistors protection shall be able to utilize either one or two
or non-linear resistors shall be required. The time constants, which shall be selectable.
operating characteristics shall be according to the • To protect the generator and turbine from the
definite time mode. harmful effect of excessive power/motoring, the
relay shall have reverse power/directional
Backup protection overpower protection (32R/32O).
• The relay shall have three separate non-directional • The relay shall have overexitation (V/Hz) protection
overcurrent (50/51) stages settable between 0.05 (24) to protect the generators and power
and 40 times pu. The operation characteristic of transformers against an excessive flux density and
the low and high-set stages shall be settable to saturation of the magnetic core.
either definite time (DT) or inverse definite • The relay shall have temperature supervision to
minimum time (IDMT), supporting various types of monitor the thermal behavior of the transformer
inverse curves, including a user-definable one. The windings and cooling oil.
instantaneous stage shall support the peak-to-
peak measurement mode and include a possibility
to introduce a dedicated two-times setting value
peak detection for fast operation in conditions
when the current transformers have saturated.
3
Other protections • The relay must have an option include manual and
• The relay shall have comprehensive voltage automatic voltage regulation (90V) of power
protection, including at least overvoltage (59), transformers with a motor-driven on-load tap-
undervoltage (27), positive-sequence undervoltage changer. The voltage regulator function shall have
(47U+), negative-sequence overvoltage (47O-) and the following features:
residual overvoltage (59G) protection. -- Parallel operation of up to four power
• The relay shall have six-stage frequency (81) transformers
protection. The frequency shall be measured using -- Parallel operation modes according to master-
the positive-sequence voltage. It shall be possible follower, minimizing circulating current and
to set each stage individually to operate based on negative reactance principles
underfrequency, overfrequency or rate-of-change -- Support for necessary data exchange between
of frequency. relays using IEC 61850-8-1 GOOSE messaging
• The relay shall have two-stage directional phase when power transformers are running in parallel
overcurrent protection (67) with voltage memory -- Line drop compensation for both single power
and positive and negative-sequence polarization. transformers and transformers running in
• The relay must have two-stage directional earth- parallel
fault protection (67N) with selectable negative and -- Out-of-step supervision for followers in the
zero-sequence polarization. I0 and U0 shall be master-follower mode
derived either from the phase voltages and -- Possibility to apply reduced set-point voltage
currents or from the measured neutral current and setting in case of a temporary power shortage
residual voltage. within the supplying network
• The relay shall have arc protection based on -- Both definite time (DT) and inverse definite
simultaneous detection of current and light. minimum time (IDMT)-based time delay modes
During maintenance work at the substation, it shall for the tap-changer steptimer. This allows either
be possible to change the operation criteria to a fixed time delay or an inverse time delay, based
light only via a binary input. on the difference between the measured and the
• The relay shall support local and remote control of target voltage level, to be applied for the step-
circuit breakers and motor operated timer.
disconnectors/earthing switches. The relay shall -- Fast lowering feature that is activated when a
provide status indication for manually operated specific set voltage value is exceeded due to
disconnectors/earthing switches. large load rejection. In this case, the voltage
• The relay shall have circuit breaker failure regulator drives the on-load tap-changer to
protection (51BF/51NBF) including independent reach the desired LV-side voltage as fast as
timers for repeated tripping of the same breaker possible.
and back-up tripping of the upstream breaker. The -- Blocking of the operation in an overcurrent
function shall allow higher selectivity by avoiding situation
tripping of the upstream breaker if the repeated -- Blocking of the operation in case the measured
tripping of the breaker closest to the fault is voltage is too low to be regulated by the tap-
successful. changer
-- Supervision of the tap-changer response to the
given control command and issuing of an alarm if
the performance is not within the set
performance limits
4
Additional information
For more information, please contact your local ABB
representative or visit our website at:
www.abb.com/substationautomation
www.abb.com/mediumvoltage
— —
The information in this document is subject to change without ABB is a registered trademark of the ABB Group. All other brand or
abb.com/mediumvoltage notice and should not be construed as a commitment by ABB. ABB product names mentioned in this document may be trademarks or
assumes no responsibility for any errors that may appear in this registered trademarks of their respective holders.
document.