Below Grade: 1.) A.) Project Data
Below Grade: 1.) A.) Project Data
CLIENT
PROJ NO.
JOB NO.
DOC.
JOB TITLE WALL FORMWORK DESIGN
LOC.
Analysis ref; Formwork For Concrete - 7th edition Wall Location Below Grade
Design ref; Formwork_A_Guide_To_Good_Practice - 2nd edition External Lateral Force Yes.
Whale Circular
D - 50.00 mm Depth N.A!!
B - 50.00 mm Width N.A!!
φ - 50.00 mm Diameter OK!!
t - 1.25 mm Thickness
N - 2.00 nos. Number
Sw - 400.00 mm Assumed whale spacing
lw - 600.00 mm Whale length (same as strong back spacing)
2.) Output
Cw - 1.04 - Unit weight coefficient (Table 5-4)
Cc - 1.00 - Chemistry coefficient (Table 5-4)
H - 8.56 kN/m Minimum external lateral force (SEI/ ASCE 37)
[100 lb/ft or (100 psf for below grade) x 1 x h x (1/2)]
Pmax - 29.85 kN/m 2
Maximum lateral pressure (Eq; 2.4)
[Cw x Cc x (150 + 9000 x (R/T)]
hps - 2.34 m Height of pressure stable point from bottom [h - Pmax / wc]
hts - 1.26 m Height of pressure stable point from top [Pmax / wc]
Properties of plywood
wp - 9.10 kN/m Distributed load on plywood per feet
Mu - 0.17 kN-m/m Design moment for plywood [wpSv2/9]
Mn - 0.19 kN-m/m Moment capacity OK!!
3.) Check
Axial (kN) Moment (kN-m) Delfection (mm) Remark Spacing (mm)
Pu Pn Mu Mn δact δallow C/C
- - 0.17 0.19 - -
a.) Plywood - 0.912 - OK!! -
- - 1.90 3.34 - -
b.) Vertical strut - 0.570 - OK!! 228.60
12.9 45.1 - - - -
e.) Inclined strut 0.3 - - OK!! 600.00
PROJECT NAME
CLIENT
PROJ NO.
JOB NO.
DOC.
JOB TITLE WALL FORMWORK DESIGN
LOC.