1 22-06-2020 Interface: Directly Connected Load Total Bus Load
1 22-06-2020 Interface: Directly Connected Load Total Bus Load
* Indicates operating load of a bus exceeds the bus critical limit ( 110.0% of the Continuous Ampere rating).
# Indicates operating load of a bus exceeds the bus marginal limit (100.0% of the Continuous Ampere rating).
Project: ETAP Page: 2
Transformer
CKT / Branch Busway / Cable & Reactor
Loading (input) Loading (output)
Ampacity Loading Capability
ID Type (Amp) Amp % (kVA) kVA % kVA %
Vd
From-To Bus Flow To-From Bus Flow Losses % Bus Voltage
% Drop
C:PCC1_OG1 0.0 0.0 0.0 0.0 0.0 0.0 98.1 98.1 0.00
C:PMCC3_OG1 0.0 0.0 0.0 0.0 0.0 0.0 99.4 99.4 0.00
C:PMCC4_OG1 0.0 0.0 0.0 0.0 0.0 0.0 99.4 99.4 0.00
C:PCC2_OG1 0.0 0.0 0.0 0.0 0.0 0.0 98.6 98.6 0.00
C:Grid -2134.8 -283.4 2134.8 281.5 0.0 -1.8 100.0 100.0 0.00
C:HTP1_OG2 34.4 -4.3 -34.4 2.4 0.0 -1.8 100.0 100.0 0.00
C:HTP1_OG3 979.1 91.8 -979.1 -93.6 0.0 -1.8 100.0 100.0 0.00
C:T1_HV 1121.3 195.9 -1121.3 -197.1 0.0 -1.2 100.0 100.0 0.00
C:T4_HV 979.1 93.6 -979.1 -94.9 0.0 -1.2 100.0 100.0 0.00
C:T2_HV 24.5 -1.2 -24.5 0.0 0.0 -1.2 100.0 100.0 0.00
C:T3_HV 9.8 -1.2 -9.8 0.0 0.0 -1.2 100.0 100.0 0.00
C:PCC1_OG4 -60.1 0.0 60.2 0.0 0.0 0.0 98.1 98.1 0.07
C:PCC1_OG2 -14.7 0.0 14.7 0.0 0.0 0.0 98.1 98.1 0.02
C:PCC1_OG3 -14.7 0.0 14.7 0.0 0.0 0.0 98.1 98.1 0.02
C:PMCC3_OG2 -14.7 0.0 14.7 0.0 0.0 0.0 99.3 99.4 0.02
C:PCC2_OG2 0.0 0.0 0.0 0.0 0.0 0.0 98.6 98.6 0.00
C:PCC1_OG6 23.6 6.5 -23.6 -6.5 0.0 0.0 98.1 98.1 0.03
C:PCC1_OG8 1000.9 146.5 -989.7 -137.4 11.3 9.2 98.1 96.9 1.21
C:PCC2_OG3 150.1 59.0 -149.8 -58.8 0.3 0.2 98.6 98.3 0.21
C:PCC2_OG5 391.9 1.4 -390.3 0.0 1.7 1.4 98.6 98.1 0.42
C:PCC2_OG6 421.8 1.6 -419.8 0.0 1.9 1.6 98.6 98.1 0.46
28.1 78.9
Project: ETAP Page: 4
% Alert Settings
Critical Marginal
Loading
Bus 110.0 100.0
Bus Voltage
OverVoltage 110.0 105.0
Generator Excitation
OverExcited (Q Max.) 100.0 95.0
kW kvar kVA % PF
Number of Iterations: 1