1 Fresh Air Load Calculation 2 Fresh Air Load Calculation Job: Holiday Inn - Summer Job: Holiday Inn - Monsoon Date 03.10.10 Date 03.10.10
1 Fresh Air Load Calculation 2 Fresh Air Load Calculation Job: Holiday Inn - Summer Job: Holiday Inn - Monsoon Date 03.10.10 Date 03.10.10
Calculation Calculation
DB WB RH
OA 96 78 45 OA
DB WB RH
SA 75.2 60 SA
TR = CFM Del H TR =
11.21362917 4.45 2750 10.996 11.33600417
12000
esh air load calculation
60 Min
13.5 Density of air
Btu / TR
Bangalore
DB WB RH
82 78 82
DB WB RH
75.2 60
2750
41.5 BTU/lb
30.384 BTU/lb
CFM Del H
4.45 2750 11.116
12000
BLOW DOWN = {E-[(C-1) x D]}
C-1
E= Evaporation in GPM (If not accurately known can be approximated as flow rate in gpm x Range
C= Cycles of concentration , depends on quality of water
D= Drift Loss in GPM (approximately Total flow rate x 0.0005)
If levels of Chloride in the make up water is say 250 PPM, and we do not want PPM levels to go beyond 750, then,
Cycles of concentration is 750 / 250 = 3
Example : 600 TR Tower @ 3 USGPM / TR
Flow rate = 600 x 3 = 1800 GPM
Range = 10 ˚ F
Cycles of concentration = 3
2.383 Lts / TR - HR