What Is Air Conditiong
What Is Air Conditiong
Complete air conditioning provides automatic control of the Air conditioning (for space or machines)
above factors for the outdoor weather conditions for BOTH Split air conditioners
summer and winter conditions. Fan coil units in a larger system
Air handling units in a larger system
EVAPORATOR or COOLING UNIT WHATARE THE AIR CONDITIONING SYSTEMS? WHAT IS DIRECT EXPANSION TYPE OF SYSTEM?
• The liquid refrigerant from the condenser is led through the AIR CONDITIONINGSYSTEMS .AIR IS DIRECTLY COOLED, BY PASSING OVERTHE REFRIGERANT
liquid line to the cooling unit.
• Expansion valve is fitted just before the evaporator to WHAT IS CHILLED WATER TYPEOF
DIRECT EXPANSIONTYPE CHILLED WATER
reduce the pressure. SYSTEM?
• This low pressure results in low boiling/evaporating . WATER IS CHILLED IN COILS INTERWOVEN WITH
temperature for the refrigerant. EVAPORATOR COILS, BEFORE DISTRIBUTED TO AHU’SOR
FCU’S
• As a result it evaporates and ABSORBS considerable heat. UNITARY
• In DIRECT EXPANSION SYSTEM the heat is absorbed
directly from the surrounding air.
• While in chilled water system the heat is taken from the water
coils that surround the evaporator which in turn gets SPLITSYSTEMS
chilled and is circulated to the required spaces for cooling.
PACKAGED
DX SYSTEMCOIL CHILLED WATER SYSTEM COIL
31-08-2019
DIFFERENCESBETWEEN DX SYSTEM & CHILLED WATER SYSTEM Superior air quality than
Not as good as central plant. DX system. Localized areas cannot be
OVERVIEW OF DX & CENTRAL PLANT SYSTEM Cannot do close humiditycontrol. Better control over the
DX SYSTEM CENTRALSYSTEM AIR QUALITY shutdown completely under
Cannot give high efficiency temperature, humidity,
Separate building space tohouse filtration. air distribution and any condition.
chillers, boilers, pumps, AHU’s, filtration.
No separate plant room Can have a control point for Local systems can be turned off in Can operate on part load
BUILDING SPACE distribution network andcontrol each zone wired to the
required. unoccupied spaces like dormitories, conditions.
panel. Basic controls integrated withthe control panel.
REQUIREMENTS Space temperature control
Less bulky unit; off the shelf hotels etc ; energy savings potential. Can give individualized control
Impacts the structural loads, can be achieved by using
Thermostat.
VAV systems. (Vaiable air Self contained system, a local HVAC by giving a VAV system and
vibration control, noise controletc Room by room zone avoidsover flow volume) system, can
cooling. alter the air deliveryrates. can provide greater thermal comfort localized thermostats.
Less appealing, may notblend Concealedsystem. Only occupied zones can be EFFICIENCY
CAV (constant air volume) through individualized heating and VAV systems on block load
AESTHETICS with aesthetics. Only visible supply /return air grille conditioned. systems alter temperature
CONTROLS Other areas turned down or shut while keeping air delivery cooling options. calculations for centralized.
Equipment seen which can be blended
off. rates constant.
Relies on reheat coilsto Limited option to operate on part Can borrowair from areas with
Serves one zone,major Limited capacity control, limited
control the delivered load, as they are designed for full low load, excellent savings in
components located withinthe capability to reduce air flowsduring
Can serve multiple thermalzones. cooling; energywastage
low load situations.
zone. Major components located outside due to simultaneous peak load. power.
Limitation in saving the fanenergy. heating and cooling.
ZONING Multiple units formultiple Considerable space temperature Proper zoning can avoid
the zone at a central location. AHU’s with VAV’s can
fluctuation provide energy efficient
zones. More flexibility in terms ofzoning. conflicting demand for heating
cooling, eliminate theneed
Less flexibility for zoning. for reheat. and cooling.
WHATARE THE TYPES OF INDOOR SPLIT UNITS? THE CHARACTERISTICS FOR INDOORUNIT TYPES PACKAGED SYSTEMS – MULTIPLE SPLITS (PAC’S)
INDOOR UNITTYPES
CEILING MOUNTED WHAT ARE PAC’S?
CHARACTERISTICS WALL MOUNTED
EXPOSED SEMI EXPOSED CONCEALED
INDOOR INSTALLATIONS
Mounting Height Abovr 2.5 mtapprox On ceiling Within ceiling Within ceiling •Compressor + Condenser + Compressor fan + Air
SPLIT
Operation
Corded /cordless Corded /cordless
Corded /cordless remote Corded /cordless remote handling
UNITS remote remote
Condensat Gravity, tray concelaed Drain pump (upto
Smallpump Small pump (upto850mm)
e within 600mm)
WALL CEILING
drainage
MOUNTED MOUNTED
Not there, usesand Not there, usesand Can be ducted forfresh
Fresh air intake Can be ducted for freshair FACTS ABOUT PAC’S
circulates room air circulates room air air
Thickness 250mm 210mm 200mm 200mm
SEMI EXPOSED Upto 5 tons(turbo
EXPOSED (CASSETTE) CONCEALED Tonnage available Upto 3 tons Upto 5 tons (turbosplits) Upto 5 tons (turbosplits)
splits) •Available from 3 ton – 16.5 ton
Upto 70deg rotationof
Air throw 1 way 1 way, 2 way, 4way 1 way •Getting more popular againstchilled
blades
Efficiency very high COP available very high COPavailable very high COP available very high COPavailable
water plants.
Can detect movement,
can be computer
direct air flow, can be computer •Cheaper installation costs againstcentral
controlled, email for can be computer controlled,
automatic filter cleaning controlled, email for
malfunctioning,filter email for malfunctioning,filter
Intelligentcontrols device, filter clean malfunctioning, filter chilled water plants.
clean indication, clean indication, variable
indication, star ratingi.e
variable refrigerant clean indication,variable refrigerantinput
very high energy refrigerantinput •Better temperature and humiditycontrol
input
efficiency
commercial, retail, commercial, retail, commercial, retail, residential than unitary splits or multiple splits.
Applications Small rooms, homesetc
residentialetc residentialetc etc
31-08-2019
VENTILATION
1 WAY
N AT U R A L FORCE D AIR A I R CO N D I TI O N I N G
CO OLI N G H E AT I N G
2 WAY
UNIT S Y S T E M
4 WAY
C E N T R AL S Y S T E M
D I R E C T E X PA N S I O N S Y S . CHILLED WAT E R S Y S T E M
UNIT • U s e d in smaller areas. • U s e d in huge installment
SY STEMS
• Air is p a s s e d directly • Air is p a s s e d over chilled
over chilledrefrigerant. water which are chilled
PACKAGE
UNIT
SP LI T
UNIT
W IND OW
UNIT
• Usually t h e s e are air by refrigerant.
cooled c ondensers a s
s ys . is for small units. • Usually water cooled
A I R COOLED condensers.
A I R COOLED W A T E R COOLED A I R COOLED W I TH D U CT • Expensive
5 , 7 .5 , 1 0 , 1 5 T. 5 , 1 0 , 1 5 , TR. 1 , 1 .5 , 2 , 3 TR. 3 , 5 , 7 .5 , 1 0 , 1 5
TR
• A n A H U is n o t generally • These t o o are expensive.
req • A n A H U is a necessity.
Floor
mou n t e d
• Refrigerant is circulated • Chilled water is
in the coils over which circulated t o A H U from
fan is blowed t o cool air. A C plant room.
Ceiling
mount ed
• Huge d u c t s are used t o • N o bulky ducting from
carry cooled air from A C
A.C. plant room.
plant room t o spac es.
Wall • Air is cooled in A C plant • Air is cooled a t A H U
M ou n t e d
room level.
31-08-2019
A.C. CENTRAL PLANT. DIRECT EXPANSION AND CHILLED WATER SYSTEM DIRECT EXPANSION AND CHILLED WATER SYSTEM
CHILLER