Pump Bypass Example

This document describes a parallel pipe network and pump bypass system used to maintain a constant downstream volume flow rate. The system consists of a pump line and bypass line connected in parallel. An oversized pump supplies fluid through the pump line, while a computer-controlled bypass valve directs some fluid through the bypass line. Varying the bypass valve opening adjusts the flow rates through each line, keeping the total downstream flow constant. The document provides details of the system and fluid properties, and asks to calculate and plot how the flow rates vary with the bypass valve opening from fully open to closed.

Uploaded by

ali ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
203 views4 pages

Pump Bypass Example

This document describes a parallel pipe network and pump bypass system used to maintain a constant downstream volume flow rate. The system consists of a pump line and bypass line connected in parallel. An oversized pump supplies fluid through the pump line, while a computer-controlled bypass valve directs some fluid through the bypass line. Varying the bypass valve opening adjusts the flow rates through each line, keeping the total downstream flow constant. The document provides details of the system and fluid properties, and asks to calculate and plot how the flow rates vary with the bypass valve opening from fully open to closed.

Uploaded by

ali ali
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Example: Parallel Pipe Network and Pump Bypass System

Background: In some applications (e.g., nuclear reactor cooling), it is critical that the
volume flow rate of a fluid remains constant, regardless of head changes in the system
downstream (within specified limits, of course). One method of ensuring a constant volume
flow rate is to install an oversized pump to drive the flow. A bypass line is then installed in
parallel with the pump so that some of the fluid (bypass volume flow rate Vb ) recirculates
through the bypass line as shown. Based on feedback from a downstream volume flowmeter,
the bypass valve is then adjusted by a computer to control both Vb and the volume flow rate
through the pump V such that the volume flow rate V downstream of the system remains
p d

constant.
Bypass line (subscript b)

Vb
Computer-controlled valve
Db
Dp Vp Vd
Pump 2

1 Pump line (subscript p)

Given: In this particular case, water (ρ = 998 kg/m3, µ = 1.00 × 10-3 kg/m·s) needs to be
supplied at a constant downstream volume flow rate of Vd = 0.20 m3/s. The pump’s
performance curve is given by the pump manufacturer as h pump,u,supply (
= a b − cV 2 where a = p )
100 m, b = 1.0, and c = 1.0 s2/m6. The units of hpump,u,supply are [m] and the units of Vp are
[m3/s]. The pump line has a diameter Dp = 0.50 m and length Lp = 3.0 m, while the bypass
line has a diameter Db = 0.50 m and length Lb = 5.0 m. All pipes have roughness ε = 0.002 m.
Minor losses in the system include two flanged 90o bends (KL = 0.20 each) and a gate valve
(0.2 < KL < ∞) in the bypass line, and two flanged tees (line flow KL = 0.20, and branch flow
KL = 1.00).

To Do: Calculate and plot how volume flow rates Vp , Vb , and Vd vary with the minor loss
coefficient of the valve as it goes from fully open (KL,valve = 0.20) to fully closed (KL,valve →
∞).

Solution:
• First, as always, we need to pick a control volume. In this case, we need two control
volumes since there are two branches in the parallel pipe system. After careful thought
(and experience), we decide that the most appropriate control volumes go between
points (1) and (2) as labeled on the above sketch. We re-draw the flow system
including the two control volumes. In this parallel pipe system it is useful to imagine
that the fluid in the bypass line (CVb) is colored red, while that in the pump line (CVp)
is colored blue. This is an artificial separation of the fluid into the two branches since
the fluid mixes because of turbulence. However, it is useful as an aid to drawing the
control volumes. Note that CVp has its inlet at (1) and its outlet at (2), while CVb has
its inlet at (2) and its outlet at (1).
CVb

Vb

Vp 2 Vd

1 CVp

• We apply conservation of mass at either tee:


V=
p Vb + Vd
Note: This equation couples the two control volumes together. Other than this, we treat
the two control volume separately in the analysis below.
• We apply the head form of the energy equation for CVp from inlet (1) to outlet (2),
assuming that the flow at both (1) and (2) is fully developed turbulent pipe flow so that
both velocity and kinetic energy correction factor are the same at (1) as at (2):
z1 = z2
2
P1 V P2 V2 2
+ α1 1
+ z1 + hpump,u = + α 2 + z2 + htuρbine,e + hL , p
ρg 2g ρg 2g

V1 = V2 and α1 = α2 We call this hpump,u,system since it is the required


pump head for the given piping system.
P2 − P1
Or, hpump,u,system
= + hL , p .
ρg
• We next apply the head form of the energy equation for CVb from inlet (2) to outlet
(1), recognizing again that V1 = V2 and α1 = α2, and that there is no pump in this CV:
P2 V2 P1 V2 Note: P2 − P1 is the
+ α 2 2 + z2 + hpump,u
= + α1 1 + z1 + htuρbine,e + hL ,b
ρg 2g ρg 2g same regardless of
P2 − P1 whether we are
Or, hL ,b = . considering the pump
ρg line or the branch line.
• Combining the above two results, we get hpump,u,system
= hL ,b + hL , p .
• We note that since the velocities (and therefore the Reynolds numbers) in the pump
line and the bypass line are not the same, we therefore need two Colebrook or
Churchill equations to solve the problem, one for the pump line and one for the bypass
line.
• We write all the equations, and solve them simultaneously [I used EES].

Here is what I typed into the main “Equations Window” of EES:


I created a parametric table, and selected four of the variables (Table-New Parametric Table):

I specified the values


of KL,valve, ranging
from the minimum of
0.2 (fully open gate
valve) to a very large
number (valve nearly
closed).

The rest of the


values are
automatically
calculated and filled
in when you click
on the green arrow
at the upper left.

Finally, I plotted all three of the dependent volume flow rates as functions of KL,valve:

When the valve is fully


open, we get the
maximum flow rate
through both the pump
V=
d Vp − Vb = and bypass lines.
constant = 0.20
Verify: Vd m3/s at any value of
remains constant KL valve.
regardless of the When the valve is
valve setting. nearly closed, there is
hardly any flow
through the bypass line
– nearly all the flow is
through the pump line.