Installation and Operating Instruction: Combustion Manager W-FM 50
Installation and Operating Instruction: Combustion Manager W-FM 50
max
L
L
L
L
L
N
N
P max/POC PE
PE
PE
PE
PE
PE
min
LT
X92
IGNITION
V3/PV
SV
P min
MOTOR
P P P
P LT
FLANGE
Installation and operating instruction
ALARM
MOTO
FUEL X54
SIEMENS
230 VAC
LMV27.210A2WH 50 or 60 Hz
FM
W-FM5
-20C to + 60C Best.-Nr.: 600402
1P - 4 F to +140 F
P
SAFETY
Siemens Building Technologies CE-xxxxxxxxxxxxx Geräte-Nr.: 0503020021
LOOP
L VOLTAGE
DIN VDE
HVAC Products GmbH Rg.xxxxxxxxxxxxxx
Made in Germany Refer to data sheet 7543 S
AIR
N LINE
OPERATION
FLAME
P air
V1
PE
RESET
X53
L
V2
+
COUNTER U
X3-0
FUEL
ON/OFF
QRB/C-
QRB/
QRA
QRA
3
2
ION
info
PE
PE
PE
N
L
•
L
L
L
L
FUSE 1
X75 X10-05 X10-06 X3-02 X5-03 X8-0 X8-02 X7-01 T6.3 IEC 60127-2/V
VSD X74
X64
+
h min s %
esc
1 1 1 1 1 1 1 1 1
X75 X10-05 X10-06 X3-02 X5-03 X8-04 X8-02 X7-01 X3-04 PE N L
–
V
A
VSD
S
F
P
i
1 User instructions .............................................................................................................. 5
1.1 Target group .................................................................................................................. 5
1.2 Symbols .......................................................................................................................... 5
1.3 Guarantee and Liability ............................................................................................... 6
2 Safety ..................................................................................................................................... 7
2.1 Designated application ............................................................................................... 7
2.2 When gas can be smelled ......................................................................................... 7
2.3 Safety measures ........................................................................................................... 7
2.3.1 Normal operation ................................................................................................... 7
2.3.2 Electrical connection ............................................................................................ 7
2.3.3 Gas supply .............................................................................................................. 8
2.4 Alterations to the construction of the equipment ................................................. 8
2.5 Noise emission ............................................................................................................. 8
2.6 Disposal ......................................................................................................................... 8
6 Commissioning .............................................................................................................. 46
6.1 Prerequisite ................................................................................................................. 46
6.2 Adjusting the burner .................................................................................................. 46
6.2.1 Adjusting gas side ............................................................................................. 47
6.2.2 Adjust modulation oil side ................................................................................ 61
6.2.3 Adjust multi-stage oil side ................................................................................ 75
6.3 Check combustion ..................................................................................................... 86
6.4 Calculate gas throughput ......................................................................................... 87
7 Servicing ............................................................................................................................ 88
7.1 Notes on servicing ..................................................................................................... 88
7.2 Service plan ................................................................................................................. 89
9 Technical documentation ....................................................................................... 102
9.1 Frequency converter ............................................................................................... 102
9.1.1 Frequency converter Nord size I … III ......................................................... 102
9.1.2 Frequency converter Nord size IV ................................................................ 104
10 Spares ............................................................................................................................... 106
11 Notes ................................................................................................................................. 108
1 User instructions
This manual forms part of the equipment and must be kept on site.
Translation of original Carefully read the manual prior to working on the unit.
operating instructions
1.2 Symbols
Immediate danger with high risk.
Non observance can lead to serious injury or death.
DANGER
Danger with medium risk.
Non observance can lead to environmental damage,
serious injury or death.
WARNING
Danger with low risk.
Non observance can cause damage to the equip-
ment and injury to personnel.
CAUTION
Important information
2 Safety
2.6 Disposal
Dispose of all materials and components in a safe and environmentally friendly way
at an authorised location. Observe local regulations.
3 Product description
3.1 Function
3s 10 s 3s 10 s 1 2
1 V1 V2
2
3
4
5 80 81 82 83 P P 4
1 Valve 1
2 Valve 2
3 Pressure between valve 1 and valve 2
4 Valve proving gas pressure switch
5 Operating phases
3.1.5 Calculation
A calculation can be triggered in modulating commissioning, if P1 and P9 are pro-
grammed. During a calculation, a straight line is generated from the operating point
displayed to P1 or P9. The values on the straight are adopted as the new operating
points.
Initiate a calculation after P9: Press and hold [+] key for 3 … 5 seconds.
Initiate a calculation after P1: Press and hold [–] key for 3 … 5 seconds.
If during commissioning only P1 and P9 are programmed, the combustion manager
initiates an automatic calculation when exiting P1 and calculates P2 to P8.
1 2
P1 P2 P3 P4 P5 P6 P7 P8 P9 P1 P2 P3 P4 P5 P6 P7 P8 P9
1 Automatic calculation
2 Calculation from P5 to P9
0° 1
-8°
2
-6°
90°
108°
112°
4
3
2 X3-03:1, X3-04:1
3 X5-03:1
4 X10-05:2
5 X3-02:1
6 X5-01:2
7 X5-02:2
8 X9-04:2
9 X3-05:1
0 X4-02:3
q X6-03:3
w X8-02:1
e X7-01:3
2 X3-03:1, X3-04:1
3 X5-03:1
4 X10-05:2
5 X3-02:1
6 X5-01:2
7 X5-02:2
8 X9-04:2
9 X3-05:1
0 X4-02:3
q X6-03:3
w X8-02:1
e X7-01:3
r X7-02:3
2 X3-03:1, X3-04:1
3 X5-03:1
4 X10-05
5 X3-02:1
6 X5-01:2
7 X5-02:2
8 X3-05:1
9 X4-02:3 (1
0 X6-03:3
q X8-02:1
w X7-01:3 (2
e X7-02:3
(1
Only with heavy oil and long pre-ignition phase (parameter 281).
(2
Only with operating mode 12 (oil modulating).
Signal on input / output activated
No signal on input
Input without influence
1 Operating phases
2 Safety circuit
3 Heat demand controller
4 Flame Signal
5 Air pressure switch
6 Minimum pressure switch
7 Max. pressure switch
8 Fan motor
9 Ignition unit
0 Safety valve
q Fuel valve 1
w Fuel valve 2
e Fuel valve 3
2 X3-04:1
3 X5-03:1
4 X10-05
5 X3-02:1
6 X5-01:2
7 X5-02:2
8 X9-04:2 (1
9 X3-05:1
0 X4-02:2
q X6-03:2
w X8-02:1
e X7-01:2
r X7-02:2
(1
Only for evaluation in operating phase PH38 … PH62 (para-
meter 286).
Signal on input / output activated
No signal on input
Input without influence
1 Operating phases
2 Safety circuit
3 Heat demand controller
4 Flame Signal
5 Air pressure switch
6 Minimum pressure switch
7 Max. pressure switch
8 Heavy oil immediate start
9 Fan motor
0 Ignition unit
q Safety valve
w Fuel valve 1
e Fuel valve 2
r Fuel valve 3
3.2 Inputs
PE 3 PE
N 4 N
L 5 L
L 2 Emergency-Off switch
Safety time limiter (STL)
Low water safety interlock, etc.
The burner flange limit switch is connected to input X3-03:1/2.
3.2.3 Reset
(1 (2
1 A reset button can be connected to input X8-04:1. Pressing this button in lockout
X8-04
RESET
OPERATION 2 for 1 … 6 seconds will reset the combustion manager. Pressing the button for a
1 longer or shorter period will be ignored by the combustion manager and therefore
L 2 has no effect.
X3-04
PE 3 PE
N 4 N With lockout function(1
L 5 L
If the push button is also required for manual lockout, it must be connected to
MOTOR 1 mains input X3-04:5 (L). If the combustion manager is in an operating phase,
X3-05
ALARM 2 pressing the push button for 1 to 6 seconds will initiate a manual lockout.
MOTOR CONT 3
Without lockout function(2
If the push button is not required to carry out manual lockout it must be connected
to alarm output X3-05:2.
nal is missing once the fan has started, the combustion manager initiates a lockout.
L 2
The air pressure switch must have been deactivated, contact open, prior to the fan
starting.
min 2 For burners without min. oil pressure switch, a bridge has to be connected to ter-
L 3 minal 2 and terminal 3.
P
min 2 For burners without max. oil pressure switch, a bridge has to be connected to ter-
L 3 minal 2 and terminal 3.
P
min 2 put X9-04. Input X9-04 is only activated during valve proving [ch. 3.1.3]. The time
L 3 of valve proving can be set in parameter 241 .
If the pressure set is not achieved in operating phase Ph81 (test without pres-
sure), the contact closes.
If the pressure set is exceeded in operating phase Ph83 (test with operating
pressure), the contact opens.
min 2 ers. The release contact of the return flow temperature sensor is connected to in-
L 3 put X9-04.
In modulating heavy oil operation, the combustion manager carries out a nozzle cir-
culation for maximum 45 seconds. If the signal is present at X9-04 before this time
has elapsed, the nozzle circulation is shortened accordingly. If the signal is missing
after this time has elapsed, the combustion manager initiates a home run with sub-
sequent repetition.
During operation, the signal is monitored according to the setting of para-
meter 286.
QRA…
BR
The flame sensor QRA… (UV cell) is connected to input X10-06.
X10-06
QRA 1 +
BU
QRA 2 Flame signal
Parameter 954
Response limit extraneous light greater than 18 %
Operation min 24 %
Ionisation electrode
PE 1 The ionisation electrode is connected to input X10-05:2.
ION 2
X10-05
Flame signal
QRB/C 3 Parameter 954
QRB/C-N 4
L 5 Sensor current min.: 4 μA approx. 30 %
Sensor current max.: 16 … 40 μA 100 %
QRB…
PE 1 The flame sensor QRB… (photo resistor) is connected to input X10-05:3/4.
ION 2
X10-05
Flame signal
QRB/C 3 Parameter 954
QRB/C-N 4
L 5 Response limit extraneous light (resistance less than approx. 10 %
400 kΩ)
Operation (resistance less than 230 kΩ) approx. 16 %
Short circuit identification (resistance less than –
0.5 kΩ)
2 °C
The analogue load signal is connected to terminals X64:1 (4 … 20 mA) and
3
+
X64:2 (GND). A signal of less than 3 mA deactivates the analogue input and the
L 4 load pre-setting at input X5-03:2/3 has priority (parameter 942). If no load con-
-
troller is connected to input X5-03:2/3, the combustion manager remains at the
4...20 1 current rating until heat demand is interrupted.
GND 2
X64
3
4
5
Two stage:
Signal on X64:1/2 Load W-FM
3 … 5 … 12 mA Stage 1
13 … 15 … 20 mA Stage 2
Three stage:
Signal on X64:1/2 Load W-FM
3 … 5 … 7 mA Stage 1
8 … 10 … 12 mA Stage 2
13 … 15 … 20 mA Stage 3
2
3 eBUS: Adapter MPA eBUS (Order No.: 743 090).
L 4 To ensure that load pre-setting is carried out by the building management system,
input X5-03:1 (burner ON/OFF) must be connected to voltage output X5-03:4 for
COM
X92
Interface
burner start.
The settings required for Bus communication are set in parameters 141 to 148.
2 °C
3 If none of the two inputs is activated, the burner capacity remains unchanged.
L 4
2
3 At heat demand input X5-03:2 (CLOSED) is activated and the burner drives to par-
P
L 4 tial load. If the temperature drops below the value set, input X5-03:3 (OPEN) is ac-
tivated and the burner drives to full load. If a signal is applied to input X5-03:3, in-
ON/OFF 1 P P
put X5-03:2 is ignored.
X5-03
2 P
3 P P
L 4
2 At heat demand and with the bridge between terminal 1 and 2 the burner ignites in
3 P stage 1 and then automatically drives to stage 2. If input X5-03:3 is also activated
L 4 the burner drives to stage 3.
Change-over release:
ON/OFF 1 P
A bridge connects terminals 2 and 3. At heat demand the burner drives to stage 1.
X5-03
2
3 If inputs X5-03:2/3 are then activated simultaneously the burner drives via stage 2
L 4
P
to stage 3.
2 for this is that no frequency inverter is connected and activated. The meter pulses
per unit volume must be set in parameter 128 . The impulse frequency must not
exceed 300 Hz.
3.3 Outputs
3.3.1 Alarm
MOTOR 1 A mains voltage signal is given at alarm output X3-05:2 in lockout (operating phase
X3-05
ALARM 2 Ph00).
MOTOR CONT 3 In addition, start prevention can also be signaled. To do this, parameter 210
should be set to 1.
3.3.2 Motor
MOTOR 1 Normal operation
X3-05
ALARM 2 M
The fan motor is connected to output X3-05:1 via contactor or star delta switching.
MOTOR CONT 3 L N
Continuous operation
The fan motor is connected to output X3-05:3 via contactor or star delta switching.
MOTOR 1 If an air pressure switch is fitted, continuous running fan is only possible via pres-
X3-05
ALARM 2 sure switch relief. To do this, a vent valve has to be fitted to the air pressure switch
MOTOR CONT 3 and connected to output X3-05:1.
M
L N
3.3.3 Ignition
PE 1 The ignition unit is connected to output X4-02.
X4-02
N 2
L 3 Ignition behaviour Gas
Pre-ignition in operating phase Ph38 can be adjusted in parameter 226 .
0...10 V 3
4
Frequency converter
10 V 5 Terminal Function
X74:1 24 V input; supply from frequency converter
X74:2 Signal acquisition
X74:3 Speed setpoint signal (parameter 645)
Speed measurement
Terminal Function
X74:4 Speed return signal (input actual speed)
X74:5 10 V; supplied by combustion manager
0...10 V 3 put X74:1/2.
4 The values given relate to an analogue signal of 0 … 10 V, if a signal of 2 … 10 V
10 V 5 or 0/2 … 10 V is set in parameter 645 the voltages listed will change.
Conversion: (original value x 0.8) + 2 =new value
Modulating operation
Rating Curve point Analogue signal
Off – 0V
Ignition load P0 1V
Partial load (20 %) P1 2V
Full load (100 %) P9 10 V
Combustion Manager
Mains voltage / Mains frequency 230 V / 50 … 60 Hz
Consumption max 30 W
Internal unit fuse T6.3H, IEC 127-2/5
External fuse max 16 AB
Type of protection IP 00
Actuator
STE 50 1.2 Nm STE 50 3 Nm
Mains voltage DC/AC 24 V / DC/AC 24 V /
50 … 60 HZ 50 … 60 HZ
Consumption max 7.5 W max 10 W
Torque 1.2 Nm 3 Nm
Setting time 5 s / 90° 4 s / 90°
Type of protection IP 54 IP 54
Protection class II II
3.4.3 Dimensions
Combustion manager
230 mm
60 mm 217 mm
135 mm
122 mm
Display and operating unit (ABE)
Recess dimension: 127 x 91 mm ± 0.5 mm
17 mm 96 mm
18 mm 90,6 mm
S
126,4 mm
P
132 mm
info
V h min s %
VSD esc
F A - +
4 Installation
The electrical connection must only be carried out by qualified electricians. Ob-
serve local regulations.
5 Operation
S 1
P
i
V h min s % info
VSD esc
F A - +
5 2
4 3
OFF function
Press [ENTER] and any other key simultaneously.
Immediate lockout.
5.1.2 Display
The black cursor in the display shows the status of the inputs and outputs, the unit
of values and the active level.
1 2 3 4 5 6
S
u P
z i
t
V h min s %
r e w q 0 9 8 7
Display OFF
The parameter setting is missing, incomplete or has been de-
leted.
No heat demand from controller (input X5-03:1).
Display Ph
The combustion manager is in an operating phase and waits for
signals or activates outputs depending on the program se-
quence.
The combustion manager is in an operating phase and shows
the remaining run time programmed (example: pre-purge).
Display Op
The combustion manager is in modulating operation and shows
the current load in percent.
The combustion manager is in multi-stage operation and shows
the current fuel stage.
When the fuel stage is changed, the additional display on or
of indicates the switching of the relevant fuel valve.
Display flashes
Manual load is activated. The combustion manager is in manual
load default.
Deactivate manual load:
Press and hold [esc] key for 5 seconds.
Fault display
During a fault condition, the display alternately shows the error code C and dia-
gnostic code D [ch. 8.3].
The combustion manager is in lockout.
Once the fault has been rectified, the combustion manager has
to be reset [ch. 8.1.4].
Next parameter
Press [+] key. Press [+] key.
– or –
Briefly press [Enter].
Previous parameter
Press [–] key. Press [–] key.
Change value
Press [+] or [–] key. not possible
Save value
Press [Enter]. not possible
5.2.1 Password
Enter password
Press [F] and [A] simultaneously for approx. 2 seconds.
The display shows CodE.
Enter the first digit using [+] or [–] and confirm with [ENTER].
Repeat procedure until the password has been entered.
Exit password entry using [ENTER].
The display shows PArA (parameter level) for a short time and then changes
over to 400: SEt (setup).
S
P
i
S S
V h min s %P P
i i
S
V h min s % V h min s %P
i
V h min s %
Deactivating password
If no key is activated for 30 minutes, the combustion manager automatically deac-
tivates the password and blocks the level.
In the password level, the password can be aborted early:
Press [esc] key until the display shows CLr CodE.
Let go of the [esc] key.
The combustion manager blocks the password level and changes to the operat-
ing display.
S
P
i
V h min s %
S S
P P 3s
i i
V h min s % V h min s %
S S
P P
i i
V h min s % V h min s %
S S
P P
i i
V h min s %
5s V h min s %
5.3 Parameters
Parameter Function
124 Flame failure test (TÜV test)
The flame failure test can only be carried out in operating setting 1 (operating phase Ph60). The flame
failure test closes the fuel valves and calculates the time up to flame failure. The calculated time is dis-
played in the diagnostic code in multiples of 0.2 seconds (example Loc.D: 8 = 1.6 seconds).
For the flame failure test the burner drives to the load defined under parameter 133 . If no load is
defined in parameter 133 , the flame failure test is carried out at the current load.
Press [Enter].
Set value 1 using [+] key and confirm with [Enter].
Following successful execution, the display alternately shows the error code Loc.c: 7 and dia-
gnostic code Loc.d: x.
125 Mains frequency
0: 50 Hz
1: 60 Hz
126 Display illumination
128 Fuel meter
The value must correspond to the number of impulses per unit of volume (l, m³) of the fuel meter. If the
value is set to 0 , the fuel meter stops.
130 Delete error history [ch. 8.1]
133 Load for flame failure test
141 Operating mode building management
0: OFF
1: Modbus, the combustion manager operates as Slave, the RTU transfer mode is used (Remote Ter-
minal Unit)
2: eBUS
142 Recurrence time if communication is interrupted (setting range: 0 … 7200 s)
If communication to the building management system fails, the next load controller according to priority
will be activated once this time has elapsed. If no other load controller is connected, the burner re-
mains at the current load or it drives to the load defined in parameter 148.
Priority 1: Load controller building management
Priority 2: Load controller on analogue input X64
Priority 3: Load controller on input X5-03
143 Unit address of combustion manager as eBUS participant
1: Address 03
2: Address 13
3: Address 33
4: Address 73
5: Address F3
6: Address 1F
7: Address 3F
8: Address 7F
144 Send cycle in seconds for the eBUS 05 and 09
145 Unit address of combustion manager as Modbus participant
146 Baud rate Modbus
The Baud rate of the combustion manager and the building management system must be identical.
0: 9600
1: 19200
147 Parity Modbus
The parity of the combustion manager and the building management system must be identical.
0: no Parity bit
1: odd Parity bit
2: even Parity bit
Parameter Function
148 Replacement load (setting range: 0 … 100 %)
Load default for communication failure with building management system.
–––: no replacement load
0 … 19.9: burner OFF
161 Number of lockouts
162 Operating hours since last reset
Reset:
Press [Enter].
Press [–] key.
The display shows 0, operating hours have been reset.
163 Total operating hours (voltage applied to combustion manager)
164 Start-ups since last reset
Reset:
Press [Enter].
Press [–] key.
The display shows 0, start-ups have been reset.
166 Total start-ups
167 Fuel volume since last reset
Reset:
Press [Enter].
Press [–] key.
The display shows 0, the fuel volume has been reset.
190 Position of actuators at lockout
0: Standby position
1: Post-purge position
191 … 193 not used
195 Repetition counter for heavy oil immediate start
Number of heavy oil start attempts with missing signal at input X9-04 until lockout.
Parameter Function
233 Post burn time Gas (setting range: 0.2 … 60 s)
The combustion manager remains in operating phase Ph70 for the duration of the time set, the flame
sensor is ignored during this time.
234 Post-purge time Gas (setting range: 0.2 … 6480 s)
Once the post-purge position has been reached, the combustion manager remains in operating
phase Ph74 for the duration of the time set, the flame sensor is ignored during this time.
236 Low gas pressure switch input / installation position
0: OFF
1: Low gas pressure switch fitted upstream of valve 1 (factory setting)
2: Low gas pressure switch fitted between valve 1 and valve 2, valve proving via low gas pressure
switch
237 High gas pressure switch
If a high gas pressure switch is fitted, set parameter to 1.
0: OFF
1: high gas pressure switch
2: valve closing contact
239 With forced intermittent activated, a controlled shutdown with subsequent restart is initiated after 23
hours and 45 minutes uninterrupted burner operation.
0: OFF
1: forced intermittent activated
241 Valve proving
In accordance with DIN EN 676 valve proving is not necessary if pre-purge is activated and the burner
rating is less than 1200 kW.
0: valve proving OFF (only with capacity < 1200 kW, parameter 222 must be set to 1: ON)
1: valve proving at stat-up
2: valve proving at shutdown (factory setting)
3: valve proving at stat-up and shutdown
248 Post-purge time 3 Gas (setting range: 0.2 … 6480 s)
The combustion manager remains in operating phase Ph78 for the duration of the time set except if a
new heat demand interrupts the post-purge time 3 in operating phase Ph78.
261 Flame sensor Oil
0: QRB
1: QRA
265 Pre-purge time Oil in operating phase Ph30 (setting range: 15 … 3600 s)
Once the pre-purge positions have been reached, the combustion manager remains in operating
phase Ph30 for the duration of the time set.
266 Pre-ignition time Oil (setting range: 0.6 … 3600 s)
Once the ignition positions have been reached, the combustion manager remains in operating phase
Ph38 for the duration of the time set.
270 Interval time 1 Oil
The interval time 1 in operating phase Ph44 acts as stabilisation time following flame formation.
272 not used
273 Post-burn time Oil (setting range: 0.2 … 60 s)
The combustion manager remains in operating phase Ph70 for the duration of the time set, the flame
sensor is ignored during this time.
274 Post-purge time Oil (setting range: 0.2 … 6480 s)
Once the post-purge position has been reached, the combustion manager remains in operating
phasePh74 for the duration of the time set, the flame sensor is ignored during this time.
Parameter Function
276 Minimum oil pressure switch
0: OFF
1: active from operating phase Ph38
2: active from operating phase Ph40 with solenoid valve upstream of pressure switch (e.g. pump
with valve)
277 Max. oil pressure switch
If a max. oil pressure switch is fitted set parameter to 1.
0: OFF
1: oil pressure switch
2: valve closing contact
279 With forced intermittent activated, a controlled shutdown with subsequent restart is initiated after 23
hours and 45 minutes uninterrupted burner operation.
0: OFF
1: forced intermittent activated
281 Point of ignition Oil
0: ignition on in operating phase Ph38 (short pre-ignition)
1: ignition on in operating phase Ph22 (long pre-ignition at fan start)
284 Post-purge time 3 Oil (setting range: 0.2 … 6480 s)
The combustion manager remains in operating phase Ph78 for the duration of the time set except if a
new heat demand interrupts the post-purge time 3 in operating phase Ph78.
286 Evaluation of heavy oil immediate start
If the signal is missing during the operating phase set, the W-FM initiates a shutdown with a sub-
sequent restart (repetition). The number of repetitions can be set in parameter 195 .
0: signal only required in operating phase Ph38
1: signal required in operating phases PH38 … PH62
287 Maximum waiting time for signal for heavy oil immediate start in operating phase PH38 (setting
range: 1 … 45 s)
Parameter Function
542 Activation of frequency converter
0: not activated
1: activated
544 Operating ramp modulating
Time for the actuators to drive from low load to high load.
Recommended factory setting: 32 s
545 Lower load limit (setting range: 20 … 100 %)
Defines the lower modulating limit (partial load). If no limit has been defined, the lower load limit in op-
eration is automatically set to 20 %.
– – – –: no load limit defined (20 %)
546 Upper load limit (setting limit: 20 … 100 %)
Defines the upper modulating limit (full load). If no limit has been defined, the upper load limit in opera-
tion is automatically set to 100 %.
– – – –: no load limit defined (100 %)
Parameter Function
652 Activation of the frequency converter with safety circuit open
0: no activation
1: frequency converter is activated with 0
653 Speed monitoring in standby, standby speed 0 %
0: no speed monitoring
1: speed monitoring activated
Parameter Function
950 Relay nominal condition (Bit coded output)
1: alarm
2: safety valve
4: ignition
8: fuel valve 1
16: fuel valve 2
32: fuel valve 3 / pilot valve
951 Mains voltage (standardised)
Value displayed x factor = current voltage
Factor 230 V: 1.683
Factor 120 V: 0.843
954 Current flame signal in percent [ch. 3.2.9]
960 Current fuel throughput
961 Current operating phase [ch. 3.1.8]
981 Fault history: fault codes
982 Fault history: diagnostic codes
992 Fault flags
6 Commissioning
6.1 Prerequisite
Commissioning must only be carried out by qualified personnel.
Only correctly carried out commissioning ensures the operational safety.
Observe the prerequisites for commissioning in the installation and operating
manual of the burner. This manual contains detailed information about:
general installation regulations,
nozzle selection,
connecting measuring devices,
replacing filter inserts,
checking the gas connection pressure,
carrying out soundness test,
venting the gas valve train,
setting the gas pressure regulator,
pre-setting the pressure switch.
Prerequisite
Open gas isolating valve.
Pressure in gas valve train increases.
Close isolating valve.
Switch on voltage supply.
The display shows either OFF UPr or OFF.
S S
P P
i i
V h min s % V h min s %
1. Enter password
Press [F] and [A] simultaneously for approx. 2 seconds.
The display shows CodE.
Enter the first digit using [+] or [–] and confirm with [ENTER].
Repeat procedure until the password has been entered.
Exit password entry using [ENTER].
The display shows PArA (parameter level) for a short time and then changes
over to 400: SEt (setup).
S
P
i
S S
V h min s %P P
i i
S
V h min s % V h min s %P
i
V h min s %
2. Switch on burner
Ensure there is a demand for heat.
A black dash appears below the S symbol (start).
A heat demand from the boiler controller is required for the duration of commission-
ing, that means signal on input X5-03:1.
S
P
i
V h min s %
3. Start setup
Press [ENTER].
If the combustion manager has been pre-programmed, the display shows run 1.
Select type of setting (from step 9).
If the combustion manager has not been programmed, the display shows parameter
201 2.
Define parameters 201, 542 and 641 and set P0 (from step 4).
201: Operating mode
542: Activation of frequency converter
641: Speed standardisation
S
P
1 i
S V h min s %
P
i
V h min s % S
P
2 i
V h min s %
The following steps must only be carried out if the combustion manager is not pro-
grammed. If the combustion manager has been pre-programmed, proceed with
step 9.
Press [ENTER].
The display shows only the parameter value.
Set operating mode using [+] or [–] keys and confirm with [Enter].
1: direct ignition
2: pilot ignition
Exit entry using [esc].
The display shows parameter 201 with the current operating mode.
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S S
P P P
i i i
S S
V h min s % P % P % m 3 m 3/h l l/h
i i
V h min s % V h min s %
S
P
i
V h min s %
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
h min s %
S
P
i
V h min s %
Press [+] key.
Exit pre-setting.
The display changes to run.
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S S
P P
1 i i
S V h min s % S %
P P
i i
V h min s % S V h min s %
P
2 i
V h min s %
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P
i
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i S
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P S
i P S
i
P
V h % S
i
P
V h % S
i l
P
V h %
i
V h min %
V h min s %
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P m
i
V h min s %
S
P
i S
P m l l/h
i
V h min s %
V h min s %
S
P
i S
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
The setting pressure must not be altered once this work has been completed.
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
This step should only be carried out on burners in version ZMI. On burners of differ-
ent version, skip this step and proceed with step 20.
S
P
i S
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
S
V h min s % V h min s %
P
i
V h min s %
S S
P P
i i
S
V h min s % V h min s %
P
i
V h min s %
If the [–] key is pressed again for more than 4 seconds, a calculation is started from
the point shown to P1.
Briefly press [–] key, to ensure points calculated or set are not overwritten.
The operating points should only be adjusted via the fuel supply [F]. Changes to the
air quantity influence the linearity, which has a negative effect on the load control
and VSD.
Check combustion values
Press and hold [F] key and using [+]/[–] optimise combustion values.
Optimise combustion values at each operating point, until P1 has been
reached.
S
P
i S
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S S
P P P
i i i
Prerequisite
Open oil shut off devices.
Switch on voltage supply.
The display shows either OFF UPr or OFF.
S S
P P
i i
V h min s % V h min s %
1. Enter password
Press [F] and [A] simultaneously for approx. 2 seconds.
The display shows CodE.
Enter the first digit using [+] or [–] and confirm with [ENTER].
Repeat procedure until the password has been entered.
Exit password entry using [ENTER].
The display shows PArA (parameter level) for a short time and then changes
over to 400: SEt (setup).
S
P
i
S S
V h min s %P P
i i
S
V h min s % V h min s %P
i
V h min s %
2. Switch on burner
Ensure there is a demand for heat.
A black dash appears below the S symbol (start).
A heat demand from the boiler controller is required for the duration of commission-
ing, that means signal on input X5-03:1.
S
P
i
V h min s %
3. Start setup
Press [ENTER].
If the combustion manager has been pre-programmed, the display shows run 1.
Select type of setting (from step 9).
If the combustion manager has not been programmed, the display shows parameter
201 2.
Define parameters 201, 542 and 641 and set P0 (from step 4).
201: Operating mode
542: Activation of frequency converter
641: Speed standardisation
S
P
1 i
S V h min s %
P
i
V h min s % S
P
2 i
V h min s %
The following steps must only be carried out if the combustion manager is not pro-
grammed. If the combustion manager has been pre-programmed, proceed with
step 9.
Press [ENTER].
The display shows only the parameter value.
Set operating mode using [+] or [–] keys and confirm with [Enter].
12: fuel oil EL modulating
23: medium and heavy oil modulating
Exit entry using [esc].
The display shows parameter 201 with the current operating mode.
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S S
P P P
i i i
S S
V h min s % P % P % m 3 m 3/h l l/h
i i
V h min s % V h min s %
S
P
i
V h min s %
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
h min s %
S
P
i
V h min s %
Press [+] key.
Exit pre-setting.
The display changes to run.
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S S
P P
1 i i
S V h min s % S %
P P
i i
V h min s % S V h min s %
P
2 i
V h min s %
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P
i
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i S
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
3 3
1
+
3 2 2 3
S
P S
i P S
i
P
V h % S
i
P
V h % S
i l
P
V h %
i
V h min %
V h min s %
Press [+] key.
The display shows the operating point P1.
Check combustion values and correct if necessary.
Press [+] key.
The display shows operating point P2.
If no other points have been defined, the combustion manager carries out a cal-
culation and calculates all missing points up to P9, the display briefly shows
CALC.
S
P
i S
P
i S
V h min s %
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P m
i
V h min s %
S
P
i S
P m l l/h
i
V h min s %
V h min s %
S
P
i S
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
The burner has been factory pre-sized for a specific oil throughput, see burner data
sheet.
Set pump pressure and oil quantity regulator position to the data given on the
burner data sheet.
Determine oil throughput, if necessary adjust position of oil quantity regulator [F]
until the oil throughput required is achieved.
Check combustion values
Determine combustion limit and set excess air [ch. 6.3].
S
P
i S
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
The pump pressure must not be altered once this work has been completed.
S S
P P
i i
S
V h min s % V h min s %
P
i
V h min s %
If the [–] key is pressed again for more than 4 seconds, a calculation is started from
the point shown to P1.
Briefly press [–] key, to ensure points calculated or set are not overwritten.
The operating points should only be adjusted via the fuel supply [F]. Changes to the
air quantity influence the linearity, which has a negative effect on the load control
and VSD.
Check combustion values
Press and hold [F] key and using [+]/[–] optimise combustion values.
Optimise combustion values at each operating point, until P1 has been
reached.
S
P
i S
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S S
P P P
i i i
Prerequisite
Open oil shut off devices.
Switch on voltage supply.
The display shows either OFF UPr or OFF.
S S
P P
i i
V h min s % V h min s %
1. Enter password
Press [F] and [A] simultaneously for approx. 2 seconds.
The display shows CodE.
Enter the first digit using [+] or [–] and confirm with [ENTER].
Repeat procedure until the password has been entered.
Exit password entry using [ENTER].
The display shows PArA (parameter level) for a short time and then changes
over to 400: SEt (setup).
S
P
i
S S
V h min s %P P
i i
S
V h min s % V h min s %P
i
V h min s %
2. Switch on burner
Ensure there is a demand for heat.
A black dash appears below the S symbol (start).
A heat demand from the boiler controller is required for the duration of commission-
ing, that means signal on input X5-03:1.
S
P
i
V h min s %
3. Start setup
Press [ENTER].
If the combustion manager has been pre-programmed, the display shows run 1.
Select type of setting (from step 9).
If the combustion manager has not been programmed, the display shows parameter
201 2.
Define parameters 201, 542 and 641 and set P0 (from step 4).
201: Operating mode
542: Activation of frequency converter
641: Speed standardisation
S
P
1 i
S V h min s %
P
i
V h min s % S
P
2 i
V h min s %
The following steps must only be carried out if the combustion manager is not pro-
grammed. If the combustion manager has been pre-programmed, proceed with
step 9.
Press [ENTER].
The display shows only the parameter value.
Set operating mode using [+] or [–] keys and confirm with [Enter].
5: two stage
6: three stage
Exit entry using [esc].
The display shows parameter 201 with the current operating mode.
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S
P P
i i
S
V h min s % P %
i
V h min s %
S
P
i
V h min s %
S S S
P P P
i i i
S S
V h min s % P % P % m 3 m 3/h l l/h
i i
V h min s % V h min s %
S
P
i
V h min s %
S
P
i S
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S S
P P
1 i i
S V h min s % S %
P P
i i
V h min s % S V h min s %
P
2 i
V h min s %
S
P
i S
P
i
V h min s %
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i
V h min s %
S
P
i S
P
i S
V h min s %
P
i
V h min s %
V h min s %
S
P
i
V h min s %
3 3
1
+
3 2 2 3
S
P S
i P S
i
P
V h % S
i
P
V h % S
i l
P
V h %
i
V h min %
V h min s %
S
P
i
S
V h Pl l/h %
i
S
P m 3 m h min s %
i
V h min s %
S
P
i
S
V h Pl l/h %
i
S
P m 3 m h min s %
i
V h min s %
S
P
i
S
V h Pl l/h %
i
S
P m 3 m h min s %
i
V h min s %
S
P
i
S
V h Pl l/h %
i
S
P m 3 m h min s %
i
V h min s %
S S S
P P P
i i i
The pump pressure must not be altered once this work has been completed.
The switch point determines, at which air damper setting the valve of the stage
above closes. The point itself can not be activated.
S
P
i
S
V h Pl l/h %
i
S
P m 3 m h min s %
i
V h min s %
S S
P P
i i
V h min s % V h min s %
The operating point P1 must be activated once, otherwise the display shows
OFF UPr when exiting commissioning and the combustion manager remains un-
programmed.
S S S
P P P
i i i
A2
qA = (tA - tL ) ( )+B
21- O2
QN 6000 kW
VN = VN = = 630.1 m³/h
η Hi 0.92 10.35 kW/m³
VN 630.1 m³/h
VB = VB = = 548.9 m³/h
f 1.148
7 Servicing
Servicing must only be carried out by qualified personnel. The combustion plant
should be serviced annually. Depending on site conditions more frequent checks
may be required.
Components, which show increased wear and tear or whose design lifespan is or
will be exceeded prior to the next service should be replaced as a precaution.
The design lifespan of the components is listed in the service plan [ch. 7.2].
The following components must only be replaced and must not be repaired:
combustion manager
flame sensor
actuator
gas valve
oil solenoid valve
nozzle head (shut off needle),
pressure regulator
pressure switch
Following servicing
Check tightness of oil and gas carrying components.
Check function of:
adjustable mixing head,
ignition,
flame monitoring,
gas carrying components (gas connection pressure and setting pressure),
oil pump (pump pressure and suction resistance),
pressure switch
Check control and safety devices.
Check combustion values, if necessary re-adjust the burner.
Enter combustion values and settings in the commissioning record and/or test
sheet.
8 Troubleshooting
8.1.3 Fault
If a fault occurs, the combustion manager initiates a controlled shutdown.
The display and operating unit alternates between Err.c: (error code) and
Err.d: (diagnostic code).
The burner restarts automatically as soon as the fault condition has been rectified.
Example
8.1.4 Lockout
If a lockout condition occurs, the combustion manager initiates a fault shutdown
and burner lockout.
The display and operating unit alternates between Loc.c: (error code) and
Loc.d: (diagnostic code).
Once the fault has been rectified, the combustion manager has to be reset for re-
start.
Example
Resetting
Display faults
Select service level or password level [ch. 5.2]
Select parameter 700 using the [+] key and confirm with [Enter] (password level
only).
Select faults in sequence using [+] or [–] key.
press [Enter] (press service level 1 … 3 s).
Fault level flashes.
Select fault level in sequence using [+] or [–] key.
If fault levels 05 and 06 show ·-·- in the display:
press [Enter] (press service level 1 … 3 s).
Value is displayed.
S
P
i
V h min s %
S S
P P
i i
V h min s % V h min s %
S S
P P
i i
V h min s % V h min s %
Delete faults
Only the fault history in the service level can be deleted. The fault history in the
password level is not affected by the deleting process.
Enter password [ch. 5.2.1].
Select parameter 130.
Press [Enter].
The display shows value 0.
Set value to 1 within 3 seconds using [+] key, confirm with [Enter] key, then set
value to 2 and confirm again with [Enter] key.
When the display changes to 0 the delete process has been completed. If the
display shows -1 the duration of 3 seconds was exceeded and the delete pro-
cess was aborted.
S S
P P
i i
S
V h min s % P V h min s %
i
V h min s %
S
P
i 3s
S
P V h min s %
i
V h min s %
2 … 3 Modulating operation: Curve gradient fuel The position change between two operat-
actuator too steep ing points must not exceed maximum 31°:
4 … 7 Modulating operation: Curve gradient air Adjust operating points.
actuator too steep
85 0 Fuel actuator referencing error Check, if actuators have been mixed up.
1 Air actuator referencing error Check, if actuator is blocked.
128 … 255 Parameter settings of one actuator have –
been changed.
86 0 Position error fuel actuator Check, if actuator is blocked.
1 Fuel actuator line break min 0.5 V between Pin 5 and 2 or 6 and
2:
Check wiring
8 Modulating operation: Curve gradient fuel The position change between two operat-
actuator too steep ing points must not exceed maximum 31°:
Adjust operating points.
16 … 255 Fuel actuator overloaded or mechanically Check, if actuator is blocked.
twisted
9 Technical documentation
1 2
1 2
ON
3
1 Interfaces
2 DIP switches
3 Diagnostic LED's
Interface
The interface is used to access the frequency converter via a PC.
The Software required can be found on the Frequency Converter CD.
A connection cable RJ12 to SUB-D9 is required for the connection (Order No. 743
361). A readily available USB interfaces converter USB to RS232 is also required
for the connection to the USB port.
DIP switches
The analogue inputs AIN1 and AIN2 are configured via setting of the DIP switches.
Factory setting (2 … 10 V):
Switch 1: OFF
Switch 2: OFF
Diagnostic LED's
LED Signal Description
1 (BUS-S) – System bus status (not used)
2 (BUS-E) – System bus fault (not used)
3 (DS) OFF No mains voltage and no control voltage
Green Operation, FC operating
Flashing green 0.5 Hz(1 Ready for operation
4 Hz(1 Start blocked
Flashing red/green 4 Hz(1 Warning
1 … 25 Hz(1 Intensity overload
Flashing red Fault, flashing codes see Frequency
Number ≙ flashing codes converter CD
(1
1 Hz ≙ once per second
2 3
1 4
9 0 B A
8 5
7 6
1 Interfaces
2 Diagnostic LED's
3 Status LED's
Interface
The interface is used to access the frequency converter via a PC.
The Software required can be found on the Frequency Converter CD.
A connection cable RJ12 to SUB-D9 is required for the connection (Order No. 743
361). A readily available USB interfaces converter USB to RS232 is also required
for the connection to the USB port.
Diagnostic LED's
LED Signal Description
1 (DOUT1 ) yellow Alarm from frequency converter (digital
output 1)
2 (DOUT2) yellow Signal at digital output 2
3 (BRAKE) yellow Mechanical brake
4 (TEMP) yellow Excess temperature at motor
5 (DIN4) yellow Signal at digital input 4
6 (DIN3) yellow Signal at digital input 3
7 (DIN2) yellow Signal at digital input 3
8 (DIN1) yellow Frequency converter start release (digital
input 1)
9 (BUS-S) OFF No Bus communication (system bus)
Green Bus communication
Flashing green Bus warning
0 (BUS-E) OFF System bus is operating correctly
Flashing red Monitoring fault
red No system bus
Status LED's
LED Signal Description
A (AS-i) – Status AS interface (not used)
B (DS) OFF No mains voltage and no control voltage
Green Operation, FC operating
Green ON + Frequency converter not ready for oper-
red flashing ation,
control voltage applied but no mains
voltage
Flashing green 0.5 Hz(1 Ready for operation
4 Hz(1 Start blocked
Flashing red/green 4 Hz(1 Warning
1 … 25 Hz(1 Intensity overload
Flashing red Fault, flashing codes see Frequency
Number ≙ flashing codes converter CD
(1
1 Hz ≙ once per second
10 Spares
1.01
1.03
1.04
1.02
11 Notes
P T
Parameter ........................................ 36, 38, 41, 42, 43, 44 Temperature ......................................................................... 26
Parity ...................................................................................... 37 Thermostat............................................................................ 23
Partial load...................................................... 42, 59, 73, 84 Three stage .......................................................................... 39
Password ........................................................ 34, 47, 61, 75 Throughput ........................................................................... 71
Password level..................................................................... 33 Torque ................................................................................... 26
Photo resistor....................................................................... 21 Transport............................................................................... 26
Pilot ignition.......................................................................... 39 Tree stage............................................................................. 22
U
Unit address......................................................................... 37
UV cell ................................................................................... 21
V
Valve proving................................................................ 10, 20
Valve proving gas pressure switch ................................. 20
Valve proving pressure switch ......................................... 20
Voltage supply ..................................................................... 18
VSD........................................................................................ 43
X
X5-02..................................................................................... 17
These legendary industrial burners are durable The floor-standing condensing boilers
and versatile. WTC-GB (up to 300 kW) and WTC-OB
Numerous variations of oil, gas and dual fuel (up to 45 kW) are efficient, low in pollutants
burners meet a wide range of applications and and versatile in use.
capacity requirements. Even the largest capacities can be covered by
cascading up to four gas condensing boilers.
The WKmono 80 burners are the most The stylish flat-plate collectors are the ideal
powerful monoblock burners from Weishaupt. complement for any Weishaupt heating
They are available as oil, gas or dual fuel system. They are suitable for solar water
burners and are designed for tough industrial heating and for combined heating support.
application. With versions for on-roof, in-roof and flat roof
installations, solar energy can be utilised on
almost any roof.
These industrial burners of modular The diverse program of potable water and
construction are adaptable, robust and energy storage for various heat sources
powerful. includes storage volumes of 70 to 3,000 litres.
Even on the toughest industrial applications In order to minimize storage losses, potable
these oil, gas and dual fuel burners operate water cylinders from 140 to 500 litres are
reliably. available with highly efficient insulation using
vacuum insulation panels.
Weishaupt customers can be assured that With its daughter company, BauGrund Süd,
specialist knowledge and tools are available Weishaupt also offers geothermal probe and
whenever they are needed. Our service well drilling. With the experience of more than
engineers are fully qualified and have 10,000 systems and more than 2 million meters
extensive product knowledge, be it for burners, of drilling, BauGrund Süd offers a
heat pumps, condensing boilers or solar comprehensive service program.
collectors.
83250302 1/2018-08 La