Product Data Sheet Easy: For A Simple Setting
Product Data Sheet Easy: For A Simple Setting
Easy
Control components for VAV terminal units, to be mounted on the terminal unit
for easy operation
■ Simplified ordering and on-site assignment to rooms as selection is based
on the nominal size of the duct
■ Simple volume flow rate setting without additional device
■ Indicator light simplifies functional checking
■ With push button for triggering a function test
■ Proven technology of the Compact volume flow controllers
■ Suitable for constant and variable volume flow rates and qvmin-, qvmax-Switching
1 PD-04/2019 - DE/en
Easy
General information
Application ▪ TROVE-024T-05I-DD15 for TVE
▪ Electronic volume flow controllers of Type Easy are compact,
all-in-one control devices for VAV terminal units Parts and characteristics
▪ Dynamic differential pressure transducer, electronic ▪ Transducer for dynamic measurement principle
controller, and actuator are fitted together in one casing ▪ Mechanical stops for limiting the damper blade positions (not
▪ Suitable for different control tasks depending on how the input for TVE)
for the setpoint value signal is used ▪ Actuators with overload protection
▪ The output signals of the room temperature controller, central ▪ Release button to allow for manual operation (not for TVE)
BMS, air quality controller or similar units control the volume ▪ Transparent protective cover or terminal cover (for TVE)
flow rate setpoint
Interface
▪ Override control by means of switches or relays
Analogue signal 0 – 10V DC
▪ Volume flow rate actual value is available as linear voltage
signal Control concept
▪ Standard filtration in comfort air conditioning systems allows ▪ The volume flow controller works independent of the duct
for use of the controller in the supply air without additional pressure
dust protection. ▪ Differential pressure fluctuations do not result in permanent
volume flow rate changes
With heavy dust levels in the room ▪ To prevent the control from becoming unstable, a dead band
▪ Install appropriate exhaust air filters upstream, as a partial is allowed within which the damper blade does not move.
volume flow is routed through the transducer for volume flow ▪ The factory set volume flow rate parameters can be altered
rate measurement. by the customer
If the air is contaminated with fluff, sticky components or loaded Operating mode
with aggressive operating fluids ▪ Operating mode variable volume flow rate, qvmin: Minimum
▪ Do not use any easy controller volume flow rate, qvmax: Maximum volume flow rate
▪ Operating mode Constant value, qvmin: Constant volume flow
Construction
rate, qvmax: 100 %
▪ LMV-D3AL-F for LVC
▪ 227V-024T-05-013 for LVC Commissioning
▪ LMV-D3A-F for TVR ▪ Operating values qvmin, qvmax to be set on site with
▪ 227V-024T-05-002 for TVR potentiometer on the outside of the housing without additional
▪ 227V-024T-15-002 for TVJ, TVT adjustment tools
▪ SMV-D3A for TVT
▪ LMV-D3A for TZ-Silenzio, TA-Silenzio, TVZ, TVA
2 PD-04/2019 - DE/en
Easy
Function
Functional description nominal volume flow rate (qvnom).
A closed control circuit for regulation of the volume flow rate, i.e. The volume flow rate setpoint value comes from a higher-level
measuring - comparing - adjusting, is characteristic of air terminal controller (e.g. room temperature controller, air quality controller,
units. central BMS) or from switch contacts. Variable volume flow
The volume flow rate is measured by measuring a differential control results in a value between qvmin and qvmax. It is possible to
pressure (effective pressure). This is done via a differential override the room temperature control, e.g. by a complete shut-
pressure sensor. An integrated differential pressure transducer off of the duct.
converts the effective pressure into a voltage signal. The volume The controller compares the volume flow rate setpoint value to
flow rate actual value is hence available as a voltage signal. The the actual value and controls the integral actuator accordingly.
factory setting is such that 10 V DC always corresponds to the Flow rate parameter qvmin and qvmax can be set on potentiometers.
Principle of operation Easy controller: LVC, TVR, TVJ, TVT, TZ-/TA-Silenzio, TVZ, TVA
qv
+ -
① ②
④ ③
① Differential pressure transducer ③ Volume flow controller
② Actuator ④ Setpoint value signal
qv
⑤
- +
① ②
④ ③
3 PD-04/2019 - DE/en
Easy
The Easy principle
4 PD-04/2019 - DE/en
Easy
Specification text
This specification text describes the general properties of the product.
5 PD-04/2019 - DE/en
Easy
Order code
TVE – D / 200 / D2 / Easy
| | | | |
1 2 5 6 7
1 Type
TVE VAV terminal unit 6 Accessories
No entry: none
2 Acoustic cladding D2 Lip seals on both ends
No entry: none G2 Matching flanges for both ends
D With acoustic cladding
7 Attachments (control component)
3 Material
Easy Easy controller
5 Nominal size [mm]
100
125
160
200
250
_____________________________________________________________________________________________________________________
6 PD-04/2019 - DE/en
Easy
Variants
Easy controller
⑥ ⑦ ⑧
⑤ ④ ③ ② ①
① Easy controller
② qᵥmaxPotentiometer
③ qᵥminPotentiometer
④ Indicator light
⑤ Service button
⑥ Connections for effective pressure sensor
⑦ Protective cover
⑧ Shaft clamp
Application
▪ LVC
▪ TVR
▪ TVJ
▪ TVT
▪ TZ-Silenzio
▪ TA-Silenzio
▪ TVZ
▪ TVA
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
7 PD-04/2019 - DE/en
Easy
Easy controller TVE
①
① ② ③ ④ ⑤ ⑥
① Terminal cover
① Easy controller
② Release button and damper blade position indicator
③ qvminPotentiometer
④ qvmaxPotentiometer
⑤ Test push button and LED to display the operating states
⑥ Terminals
Application
▪ TVE
-----------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
8 PD-04/2019 - DE/en
Easy
Technical data
Easy controllers for VAV terminal units
9 PD-04/2019 - DE/en
Easy
10 PD-04/2019 - DE/en
Easy
11 PD-04/2019 - DE/en
Easy
12 PD-04/2019 - DE/en
Easy
Product details
Different terminal designation for Easy controller TVE
▪ Terminal without numbering
▪ Symbol Y instead of w
500 Ω
0,5 W
0.5 ①
1 2 1 2 3 4
⊥ ~ ⊥ ~
− + − + w U
1 2 1 2 3 4
Easy ⊥ ~ ⊥ ~ w U
− + − +
Easy
24 V Raumtemperatur-Regler
⊥ ~ y
24 V
1 2 1 2 3 4
⊥ ~ ⊥ ~ w U
1 2 1 2 3 4 − + − +
⊥ ~ ⊥ ~ w U
− + − + Easy
Easy
The supply voltage and the remote room temperature controller As soon as the 24 V supply voltage has been applied, the
must be connected as shown. controller uses the set qᵥmin value as a constant volume flow rate.
13 PD-04/2019 - DE/en
Easy
Switching for one controller qᵥmin/qᵥmax Override control OPEN/CLOSED
24 V AC
24 V
S2
S1 S3
①
1 2 1 2 3 4 1 2 1 2 3 4
⊥ ~ ⊥ ~ w U ⊥ ~ ⊥ ~ w U
− + − + − + − +
Easy Easy
① Diode 1N 4007
Switch S1 enables switching between the two constant volume External switches (volt-free contacts) can be used to OPEN or
flow rates qᵥmin and qᵥmax. CLOSE the damper blade, thereby overriding other control
Switch S1 open: qᵥmin settings (only for AC voltage).
Switch S1 closed: qᵥmax Switch S2 closed: Damper blade CLOSED
When several Easy controllers are connected in parallel, Switch S3 closed: Damper blade OPEN
switch S1 must be used as changeover switch and the contact All override controls can be combined both with each other and
for qᵥmin operation must be connected to the ground (terminal 1). with the different switching options.
24 V
min mₐₓ
1 2 3 1 2 3 1 2 3
⊥ ~ w ⊥ ~ w ⊥ ~ w
− + − + − +
Easy Easy Easy
14 PD-04/2019 - DE/en
Easy
Characteristics
Characteristic of the setpoint value signal Calculation of the volume flow rate setpoint value
6
w [Volt]
0
0 10 20 30 40 50 60 70 80 90 100
[%]
Characteristic of the actual value signal Calculation of the volume flow rate actual value
6
U [Volt]
Ist = U Nenn
4 10
3
2
0
0 10 20 30 40 50 60 70 80 90 100
[%]
Commissioning
▪ Use the potentiometer to set the minimum or maximum volume flow rate on site
▪ Take the adjustment value from the volume flow rate scale (sticker on each VAV terminal unit)
▪ Comply with the volume flow rate control range, do not set a volume flow rate which is below the minimum flow rate
▪ Volume flow rate control range TVE: 4 – 100 %
▪ Volume flow rate range of LVC, TVR, TZ-Silenzio, TA-Silenzio, TVZ and TVA: 10 – 100%
▪ Volume flow rate range of TVJ and TVT: 20 – 100%
▪ Once the VAV terminal unit has been installed and wired, and the volume flow rate has been set, the unit is ready for operation
▪ Only briefly remove the transparent protective cap or terminal cover of the Easy regulator during wiring and commissioning
15 PD-04/2019 - DE/en
Easy
Volume flow rate scale for TVR-Easy Variable volume flow control
TVR-Easy D 200
0 10 20 30 40 50 60 70 80 90 100
%
m³/h
0 200 400 600 800 1000 1200 1400
l/s
0 50 100 150 200 250 300 350 400 min mₐₓ
Each VAV terminal unit with Easy controller carries a sticker with The required volume flow rates must be set by others. If qᵥmin
a volume flow rate scale to determine the setting values at the higher than qᵥmax is set, then qᵥmin as a constant volume flow rate
customer's site (see example: TVR Easy, nominal size 200). The even if a setpoint value signal is transmitted.
percentages refer to the control range that can be used.
If qᵥmin is set on 0 %, then control is between shut-off and qᵥmax. If
the setpoint value signal falls below 0.5 V DC, the damper blade
closes (shut-off).
Constant volume flow control Control input signal from the central BMS
The constant volume flow rate is set using the qᵥmin potentiometer. To have the central BMS determine the volume flow rate, the
The setting of the qᵥmax potentiometer is in this case irrelevant. qᵥmin potentiometer must be set to 0 % and the qᵥmax
potentiometer to 100 %. If the setpoint value signal falls below
0.5 V DC, the damper blade closes (shut-off). In practice, falling
below 0.5 V DC is not always safe to realise. This is why
override control is recommended for shut-off.
16 PD-04/2019 - DE/en
Easy
Factory setting
min mₐₓ
Units are delivered with settings qᵥmin = 40 % and qᵥmax = 80% set.
17 PD-04/2019 - DE/en
Easy
Explanation
qvnom [m³/h]; [l/s]
[m³/h]; [l/s] Lower limit of the operating range for the VAV terminal unit that
Nominal volume flow rate (100 %): The value depends on can be set by customers: qvmin should be smaller than or equal
product type and nominal size. Values are published on the to qvmax. Do not set qvmin smaller than qvmin unit, otherwise
internet and in technical leaflets, and stored in the Easy Product the control may become unstable or the damper blade may
Finder design software. Reference value for calculating close. qvmin may equal zero. In case of analogue signalling to
percentages (e.g. qvmax). Upper limit of the setting range and volume flow controllers (which are typically used), the set
maximum volume flow rate setpoint value for the VAV terminal minimum value (qvmin) is allocated to the setpoint signal
unit. minimum (0 or 2 V) (see characteristic).
qvmin Unit qv
[m³/h]; [l/s] [m³/h]; [l/s]
Technically possible minimum volume flow rate: The value Volume flow rate
depends on product type, nominal size and control component
(attachment). Values are stored in the Easy Product Finder Δpst
design software. Lower limit of the setting range and minimum [Pa]
volume flow rate setpoint value for the VAV terminal unit. Static differential pressure
Depending on the controller, setpoint values below qvmin unit (if
Δpst min
qvmin equals zero) may result in unstable control or shut-off.
[Pa]
Static differential pressure, minimum: The static minimum
qvmax
[m³/h]; [l/s] differential pressure is equal to the pressure loss of the VAV
Upper limit of the operating range for the VAV terminal unit that controller when the damper blade is open, caused by flow
can be set by customers: qvmax can only be smaller than or resistance (damper blade). If the pressure on the VAV controller
equal to qvnom. In case of analogue signalling to volume flow is too low, the setpoint volume flow rate may not be achieved,
controllers (which are typically used), the set maximum value not even when the damper blade is open. Important factor in
(qvmax) is allocated to the setpoint signal maximum (10 V) (see designing the ductwork and in rating the fan including speed
characteristic). control. Sufficient differential pressure must be ensured for all
operating conditions and for all controllers, and the measurement
qvmin point or points for speed control must have been selected
accordingly to achieve this.
18 PD-04/2019 - DE/en