0% found this document useful (0 votes)
37 views

Supporting Documents: Aviation Quality Formats: QC Checks Form: Static

This document outlines quality control checks for aviation fuel storage tanks and filters. It describes 3 checks to be performed: 1) checking fuel storage tanks for water using water detection capsules after each fuel receipt, daily in the morning, and after heavy rainfall; 2) examining filter samples for water and sediment daily from gauge filters and filter separators/microfilters on tankage inlets; and 3) examining additional filter samples daily from outlets. Records of samples taken and any issues found are to be recorded on the form, with notes on allowing settling time before testing and documenting any water or sediment found.

Uploaded by

Pratiek Raul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
37 views

Supporting Documents: Aviation Quality Formats: QC Checks Form: Static

This document outlines quality control checks for aviation fuel storage tanks and filters. It describes 3 checks to be performed: 1) checking fuel storage tanks for water using water detection capsules after each fuel receipt, daily in the morning, and after heavy rainfall; 2) examining filter samples for water and sediment daily from gauge filters and filter separators/microfilters on tankage inlets; and 3) examining additional filter samples daily from outlets. Records of samples taken and any issues found are to be recorded on the form, with notes on allowing settling time before testing and documenting any water or sediment found.

Uploaded by

Pratiek Raul
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOC, PDF, TXT or read online on Scribd
You are on page 1/ 2

Section No.

6 (Q -8)
Issue: 1 Date: 01.08.2014
Rev No. Rev Date:
SUPPORTING DOCUMENTS: Page No. 1 of 2
AVIATION QUALITY FORMATS Issued By P.K. Jain
GM Aviation Services HQ & QCM
Akash Tiwari Approved By:
Chief Executive Officer

QC CHECKS FORM: STATIC


LOSS OF LIFE MAY EASILY RESULT FROM YOUR FAILURE TO OBSERVE STANDING INSTRUCTIONS

QUALITY CONTROL : WATER/CLEANLINESS CHECKS


NO.________________

CHECK 1 : STORAGE TANKS


All aviation fuel tankage must be checked for water at tank sump with Water Detector Capsules as follows :

(i) After each receipt., the receiving tank should be tested and certified water free. Such testing should be done only after stocks have
settled.
(ii) After start of morning/each shift.
(iii) After heavy rainfall.
.

Date Tank No. Grade Time Occasion SAMPLE CHECK Checked Remarks
Water W.D. Test Sediment by

CHECK II : GAUZE FILTERS/MICRO FILTER/FILTER SEPARATORS-EQUIPMENT ON TANKAGE INLET


Gauge Filters : Draw a sample daily from the bottom cock, if excessive solid contaminants is present, dismantle and clean, establish
reason for excessive contamination and take remedial action.
Microfilters/Filter Separators : Daily at start of morning shift, draw atleast a 1/2 litre sample after draining pipeline Qty. from the water drain
connection and examine for the presence of water and sediment.

Date Filter No. Grade Time Occasion SAMPLE CHECK Checked Remarks
Water W.D. Test Sediment by
Section No. 6 (Q -8)
Issue: 1 Date: 01.08.2014
Rev No. Rev Date:
SUPPORTING DOCUMENTS: Page No. 2 of 2
AVIATION QUALITY FORMATS Issued By P.K. Jain
GM Aviation Services HQ & QCM
Akash Tiwari Approved By:
Chief Executive Officer

CHECK III : GAUZE FILTERS/MICRO FILTER/FILTER SEPARATORS-EQUIPMENT ON TANKAGE OUTLET


Gauge Filters : Draw a sample daily from the bottom cock, if excessive solid contaminants is present, dismantle and clean, establish
reason for excessive contamination and take remedial action.
Microfilters/Filter Separators : Daily at start of morning shift, draw atleast a 1/2 litre sample after draining pipeline Qty from the water drain
connection and examine for colour and presence of water and sediment..

Date Filter No. Grade Time Occasion SAMPLE CHECK Checked Remarks
Sediment by
Water W.D. Test

Notes : CHECKS I, II & III.


Adequate settling must be allowed before testing.
When no water is detected in sample, the word NIL should be written.
When any sediment is found it should be so mentioned and action taken to clear it, should also be stated in the remarks column.
All entries to be made in ink or indelible pencil.

STATION___________________________ _____________________________________
QC INCHARGE/LOCATION INCHARGE