Site Acceptance Test Report For MV Panel-J03

The ammeter test report for the 11 kV MV panel J03 at the Al Hudayriyat Island TMP4 substation summarizes the following: The nameplate ratings and % errors for the analog ammeters with designations R, Y, and B were tested and found to be within specifications. Test currents from 0.5A to 1A were injected and the actual readings matched the expected readings with 0% error. The secondary injection kit used for testing was also within its calibration validity date.

Uploaded by

Gajendran Sriram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
275 views1 page

Site Acceptance Test Report For MV Panel-J03

The ammeter test report for the 11 kV MV panel J03 at the Al Hudayriyat Island TMP4 substation summarizes the following: The nameplate ratings and % errors for the analog ammeters with designations R, Y, and B were tested and found to be within specifications. Test currents from 0.5A to 1A were injected and the actual readings matched the expected readings with 0% error. The secondary injection kit used for testing was also within its calibration validity date.

Uploaded by

Gajendran Sriram
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 1

SITE ACCEPTANCE TEST REPORT FOR MV PANEL-J03

PROJECT WO # DC 3131344 EQUIPMENT 11 kV MV PANEL


CLIENT ADDC DATE 30.05.2020
CONTRACTOR HILALCO SUBSTATION AL HUDAYRIYAT ISLAND TMP4
TESTING COMPANY ALPHA POWER LLC PAGE Page 1 of 1

AMMETER TEST
1. NAME PLATE RATING DETAILS OF THE AMMETER
Switch Board Ref J02 CT Ratio 50–100/1A
Make: SIEMENS Range 0-120 A
R BU37285070263
Type ANALOG
Serial
Y BU37285070195
Number
Class 1.5
B BU37285070166

2.%ERROR TEST
INJECTED EXPECTED ACTUAL %
METER REF.
CURRENT (A) READING (A) READING(A) ERROR
R 0.5 50 50 0
R 1.0 100 100 0
Y 0.5 50 50 0
Y 1.0 100 100 0
B 0.5 50 50 0

B 1.0 100 100 0

3. REMARKS:

4. TEST EQUIPMENT DETAILS:

Description of Test Equipment Serial Number Calibration Due Date

Secondary Injection Kit 1100491 09.12.2020

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC HILALCO ADDC
NAME GAJENDRAN
SIGNATURE
DATE 30.05.2020
Page1 of 1