Ss # SDT - 065: Site Acceptance Test Report For 22Kv Transformer

The document is a site acceptance test report for a 22kV transformer. It details testing done on September 26, 2019 including visual checks, insulation resistance measurements, winding resistance measurements at room and elevated temperatures, transformer turn ratio testing with measured currents and errors, alarm and trip settings and operations, and earth value measurements. All tests were witnessed and approved by representatives of the client, contractor, and testing company.

Uploaded by

Saran Saravanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
125 views6 pages

Ss # SDT - 065: Site Acceptance Test Report For 22Kv Transformer

The document is a site acceptance test report for a 22kV transformer. It details testing done on September 26, 2019 including visual checks, insulation resistance measurements, winding resistance measurements at room and elevated temperatures, transformer turn ratio testing with measured currents and errors, alarm and trip settings and operations, and earth value measurements. All tests were witnessed and approved by representatives of the client, contractor, and testing company.

Uploaded by

Saran Saravanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 6

SITE ACCEPTANCE

TEST REPORT FOR 22KV


TRANSFORMER

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT 22KV TRANSFORMER-1


CLIENT ADDC DATE 26.09.2019
CONTRACTOR POWER LINES LLC SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 1 of 6

SS # SDT - 065
22/0.415 KV TRANSFORMER - 1
1500 KVA
SITE TEST REPORT

SNAG
 NIL.

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC POWER LINES LLC ADDC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 26.09.2019
SITE ACCEPTANCE
TEST REPORT FOR 22KV
TRANSFORMER

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT 22KV TRANSFORMER-1


CLIENT ADDC DATE 26.09.2019
CONTRACTOR POWER LINES LLC SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 2 of 6

CONTENTS

1. TRANSFORMER NAME PLATE DETAILS.


2. VISUAL CHECKS.
3. MEASUREMENT OF INSULATION
RESISTANCE AND PI VALUE.
4. MEASUREMENT OF WINDING RESISTANCE.
5. TRANSFORMER TURNS RATIO TEST.
6. TRANSFORMER ALARM & TRIP OPERATION.
7. EARTH VALUES.
8. TEST EQUIPMENT DETAILS.
9. REMARKS.

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC POWER LINES LLC ADDC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 26.09.2019
SITE ACCEPTANCE
TEST REPORT FOR 22KV
TRANSFORMER

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT 22KV TRANSFORMER-1


CLIENT ADDC DATE 26.09.2019
CONTRACTOR POWER LINES LLC SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 3 of 6

1. TRANSFORMER DETAILS:
Manufacturer FEDERAL TRANSFOMERS CO.LLC

Maker’s Serial No 25625 Type OIL Vector group Dyn11

KVA 1500 KVA Voltage (HV) 22000 V Voltage (LV) 415 V

Frequency 50 Hz Current (HV) 39.36 A Current (LV) 2086.81 A

No of Taps 5 Impedance Volt% 6.10 % Year of Mfrg 2010

Type of cooling ONAN Phases 3 Normal Tap 3

2. VISUAL CHECKS:
1 Any deformation or damage of the transformer. NO
2 Any looseness of the bolts. NO
3 Any damage of painting. NO
4 Check tightness of the gasket parts. OK
5 Condition of auxiliary equipment and its wiring OK
6 Identification plates etc. fitted. OK
7 Earthing connection. OK

3. INSULATION RESISTANCE AND PI VALUE:

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC POWER LINES LLC ADDC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 26.09.2019
SITE ACCEPTANCE
TEST REPORT FOR 22KV
TRANSFORMER

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT 22KV TRANSFORMER-1


CLIENT ADDC DATE 26.09.2019
CONTRACTOR POWER LINES LLC SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 4 of 6

Applied Duration Duration


Combination PI Value Remarks
voltage(V) 15 sec 60 sec
HV-LV+E 5000 4.15 GΩ 6.91 GΩ 1.66 OK
HV-LV 2500 5.62 GΩ 9.15 GΩ 1.62 OK
LV- HV+E 1000 2.56 GΩ 4.73 GΩ 1.84 OK

4. WINDING RESISTANCE:
HV Temp: 29 °C
Resistance at Room Temp°C ( Ω ) Resistance at 75°C ( Ω )
Tap No
R-Y Y-B B-R R-Y Y-B B-R
1 1.651 1.652 1.657 1.939 1.940 1.946
2 1.613 1.615 1.616 1.894 1.896 1.898
3 1.575 1.575 1.579 1.849 1.849 1.854
4 1.532 1.534 1.537 1.799 1.801 1.805
5 1.486 1.487 1.490 1.745 1.746 1.750

LV
Resistance at Room Temp°C ( mΩ ) Resistance at 75°C ( mΩ )
r-y y-b b-r r-y y-b b-r
0.647 0.640 0.644 0.760 0.752 0.756

Winding Calculation at 75ºC


R75°=Ramp X (235+ t 75/235+t amp)

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC POWER LINES LLC ADDC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 26.09.2019
SITE ACCEPTANCE
TEST REPORT FOR 22KV
TRANSFORMER

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT 22KV TRANSFORMER-1


CLIENT ADDC DATE 26.09.2019
CONTRACTOR POWER LINES LLC SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 5 of 6

5. TRANSFORMER TURNS RATIO TEST& HV MAGNETISING


CURRENT TEST

Vector group selected: Dyn11

R,r

b n Conditions
y RY=Rn+Yn
2w2w
By > Bb
Yy = Yb
B y

Tap TURN RATIO CURRENT (mA) % ERROR


No
A B C A B C A B C
1 96.379 96.407 96.424 1.0369 0.8502 0.6534 -0.0330 -0.0040 -0.0169
2 94.156 94.149 94.141 1.0764 0.8994 0.6787 0.0440 0.0370 0.0270
3 91.818 91.826 91.827 1.1351 0.9473 0.7121 -0.0020 0.0060 0.0080
4 89.472 89.482 89.486 1.1894 1.0119 0.7537 -0.0580 -0.0470 -0.0430
5 87.235 87.251 87.239 1.2530 1.0614 0.7953 0.0070 0.0260 0.0120

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC POWER LINES LLC ADDC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 26.09.2019
SITE ACCEPTANCE
TEST REPORT FOR 22KV
TRANSFORMER

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT 22KV TRANSFORMER-1


CLIENT ADDC DATE 26.09.2019
CONTRACTOR POWER LINES LLC SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 6 of 6

6. TRANSFORMER ALARM & TRIP OPERATION:


a) TEMPERATURE INDICATOR:

DESCRIPTION SETTINGS REMARKS


Alarm 95 ºC OK
Trip 105 ºC OK

b) TRIP TEST CHECK:

SR.NO DESCRIPTION REMARKS


1 Winding Temperature Trip OK
2 Pressure Relief Device Trip OK
3 Hermetic Trip OK

7. EARTH VALUE:
Transformer Body 0.6 Ω Transformer Neutral 0.4 Ω

8. TEST EQUIPMENT DETAILS:


DUE DATE FOR
DESCRIPTION MAKE TYPE SERIAL NO
CALIBRATION
Digital Multimeter Fluke 87 V 31780307 21.01.2020
Insulation Tester Megger MIT 515 101574096 10.03.2020
Earth Tester Fluke 1663 3567075 06.08.2020
Transformer Winding
Vanguard TRM 203 MO-300180 28.05.2020
Resistance Meter
Transformer Turns
Megger TTR310 604601012 06.08.2020
Ratio

9. REMARKS:--

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC POWER LINES LLC ADDC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 26.09.2019