Ss # SDT - 065: Site Acceptance Test Report For 22Kv Transformer
Ss # SDT - 065: Site Acceptance Test Report For 22Kv Transformer
SS # SDT - 065
22/0.415 KV TRANSFORMER - 1
1500 KVA
SITE TEST REPORT
SNAG
NIL.
CONTENTS
1. TRANSFORMER DETAILS:
Manufacturer FEDERAL TRANSFOMERS CO.LLC
2. VISUAL CHECKS:
1 Any deformation or damage of the transformer. NO
2 Any looseness of the bolts. NO
3 Any damage of painting. NO
4 Check tightness of the gasket parts. OK
5 Condition of auxiliary equipment and its wiring OK
6 Identification plates etc. fitted. OK
7 Earthing connection. OK
4. WINDING RESISTANCE:
HV Temp: 29 °C
Resistance at Room Temp°C ( Ω ) Resistance at 75°C ( Ω )
Tap No
R-Y Y-B B-R R-Y Y-B B-R
1 1.651 1.652 1.657 1.939 1.940 1.946
2 1.613 1.615 1.616 1.894 1.896 1.898
3 1.575 1.575 1.579 1.849 1.849 1.854
4 1.532 1.534 1.537 1.799 1.801 1.805
5 1.486 1.487 1.490 1.745 1.746 1.750
LV
Resistance at Room Temp°C ( mΩ ) Resistance at 75°C ( mΩ )
r-y y-b b-r r-y y-b b-r
0.647 0.640 0.644 0.760 0.752 0.756
R,r
b n Conditions
y RY=Rn+Yn
2w2w
By > Bb
Yy = Yb
B y
7. EARTH VALUE:
Transformer Body 0.6 Ω Transformer Neutral 0.4 Ω
9. REMARKS:--