Site Acceptance Test Report For LV Panel

1) An acceptance test report was prepared for an LV panel installed at the Saadiyat Beach Residences & Villas project in Abu Dhabi by Alpha Power LLC. 2) The report documents the results of general checks, busbar contact resistance tests, busbar high voltage tests, and operational tests of meters and switches performed on the 27th of October 2019. 3) The tests confirmed that the LV panel was properly assembled and installed, with tight busbar and cable connections, and it passed both the contact resistance and high voltage insulation tests according to specifications.

Uploaded by

Saran Saravanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
598 views14 pages

Site Acceptance Test Report For LV Panel

1) An acceptance test report was prepared for an LV panel installed at the Saadiyat Beach Residences & Villas project in Abu Dhabi by Alpha Power LLC. 2) The report documents the results of general checks, busbar contact resistance tests, busbar high voltage tests, and operational tests of meters and switches performed on the 27th of October 2019. 3) The tests confirmed that the LV panel was properly assembled and installed, with tight busbar and cable connections, and it passed both the contact resistance and high voltage insulation tests according to specifications.

Uploaded by

Saran Saravanan
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as DOCX, PDF, TXT or read online on Scribd
You are on page 1/ 14

SITE ACCEPTANCE TEST REPORT

FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 1 of 14

SDT - 65

SITE ACCEPTANCE TEST


FOR 415V LV SWITCHGEAR

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 2 of 14

CONTENTS

1. GENERAL CHECKS.
2. BUSBAR CONTACT RESISTANCE TEST.
3. BUSBAR HIGH VOLTAGE TEST.
4. VOLTMETER TEST REPORT.
5. AMMETER TEST REPORT.
6. CURRENT TRANSFORMER TEST.

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 3 of 14

GENERAL CHECKS:
Not
S.No Description Yes No Remarks
Applicable
I Physical and Visual checks

1 Distribution panel is properly assembled

2 Possible for damages
Check the panel for cleanliness including 
3
interior

4 Earthing for apparatus

5 Feeder identification labels are provided

6 Cable gland plates and Cable supports

7 Painting
Busbar/Cable connection

8 checked(Tightness,Torque,lockwasher,ma
rking)
II Mechanical Operational checks
9 Circuit breaker 

10 MCBs and Switches

11 Operating Devices

12 Door,Cover plates and their locks.
III Electrical Operational Checks

13 Phase Sequence

14 Main and Auxiliary voltage

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 4 of 14

Wiring checks performed(including 


15
electrical function test,if applicable)
Electrical function of all Switching
16 
devices tested
Interlock check according to 
17
Schematic/logic diagrams.

18 Operating of Meters.

LV SWITCHGEAR DATA
AL HASSAN
MAKE SWITCHGEAR RATED CURRENT 600A
BUSBARCURRENT
RATED VOLTAGE 400V RATING 2500A
SERIAL NO. 07 FREQUENCY 50Hz
YEAR OF RATED SHORT
MANUFACTURE 2010 CIRCUIT CURRENT 50KA FOR 1SEC

BUSBAR CONTACT RESISTANCE TEST:


1. Contact Resistance Measurement: Current Injected-100A DC.

Ref. Point R(µΩ) Y(µΩ) B(µΩ) N(µΩ)


INCOMER-1TO
54 52 49 80
OUTGOING-1
INCOMER-1 TO
92 88 86 105
INCOMER-2

INCOMER-2 TO
56 53 50 83
OITGOING-2

2. TEST EQUIPMENT DETAILS:


TESTED BY CONTRACTOR WITNESS/APPROVED BY
COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 5 of 14

Due date for


Description Make Type Serial No
calibration
Micro ohm
MEGGER MOM200A 1202852 28.05.2020
meter

3. Remarks:

BUSBAR HIGH VOLTAGE TEST


1.IR measurement before HV test:1000V DC for 1 minute.

S.No Test Combination IR value in GΩ Remarks


1 R-Y+B+N+E 4.21 OK
2 Y-B+R+N+E 4.68 OK
3 B-R+Y+N+E 3.99 OK
4 N-R+Y+B+E 2.45 OK
2.HVTest:Voltage applied 2000V AC for 1 minute.

S.No Test Combination Leakage current in mA Remarks


1 R-Y+B+N+E 3.5 OK
2 Y-B+R+N+E 3.5 OK
3 B-R+Y+N+E 3.5 OK
4 N-R+Y+B+E 3.5 OK
3. IR measurement after HV test:1000V DC for 1 minute.

S.No Test Combination IR value in GΩ Remarks


1 R-Y+B+N+E 4.87 OK
2 Y-B+R+N+E 4.74 OK
3 B-R+Y+N+E 4.05 OK
4 N-R+Y+B+E 2.56 OK
4.Test Equipment Details:
TESTED BY CONTRACTOR WITNESS/APPROVED BY
COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 6 of 14

Due date for


Description Make Type Serial No
calibration
HV Test Kit VLF PFT-503CMF 1110 22.10.2020
Insulation Tester Megger MIT 515 101574096 10.03.2020

5.Remarks:

INCOMER-1

VOLTMETER TEST REPORT:

1. Name Plate Details:


Make MISURE Class 1.5
Range 0-500V Type ANALOG

2. Secondary Injection test on Meter:


Injected Voltage reading on voltmeter
% error
Voltage(V) Expected Reading(V) Actual Reading(V)
R-100 100 100 0
R-250 250 250 0
Y-100 100 100 0
Y-250 250 250 0
B-100 100 100 0
B-250 250 250 0
% error=(Actual-Expected)/Full scale reading *100.

3. TEST INSTRUMENTS DETAILS:


Description Make Model Serial No. Calibration
TESTED BY CONTRACTOR WITNESS/APPROVED BY
COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 7 of 14

Due Date
GE SVERKER76
Relay Test Kit 9602829 18.08.2020
PROGRAMMA 0

4. Remarks:

AMMETER TEST REPORT:


1. Name Plate Details:
Make MISURE Class 1.5
Ratio 2500/5A Type ANALOG

2. Secondary Injection test on Meter:


Injected Current reading on Ammeter
% error
Current(A) Expected reading(A) Actual Reading(A)
R-2.5 1250 1250 0
R-5.0 2500 2500 0
Y-2.5 1250 1250 0
Y-5.0 2500 2500 0
B-2.5 1250 1250 0
B-5.0 2500 2500 0
% error=(Actual-Expected)/Full scale reading *100.

3. TEST INSTRUMENTS DETAILS:


Calibration
Description Make Model Serial No.
Due Date
GE SVERKER76
Relay Test Kit 9602829 18.08.2020
PROGRAMMA 0

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 8 of 14

4. Remarks:

CURRENT TRANSFORMER:
1. Name Plate Details:

Make/Type MBS/ASK105.6 Class 1 FS 10


Ratio 2500/5A Burden 15VA
Serial No T1 10D 93205611 T2 10D 93205703 T3 10D 93205652

2. Insulation Resistance Test:

Test points Applied voltage(V) T1(GΩ) T2(GΩ) T3(GΩ)

Primary to earth ------- ----- ------ -------

Primary to secondary 1000 561 595 569

Secondary to Earth 500 100.4 115.2 124.3

PRIMARY INJECTION TEST

Phase Injected AMMETER DISPLAY(A) Remarks

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 9 of 14

Reference current R Y B

R-N 500A 500A --- --- OK

Y-N 500A --- 500A --- OK

B-N 500A ---- ---- 500A OK

R-Y 500A 500A 500A --- OK

Y-B 500A ---- 500A 500A OK

B-R 500A 500A ---- 500A OK

3. TEST INSTRUMENTS DETAILS:

Calibration Due
Description Make Model Serial No.
Date
Clamp Meter FLUKE 87 V 31780307 21.01.2020
GEPROGRAMM SVERKER76
Relay Test Kit 9602829 18.08.2020
A 0

4. Remarks:

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 10 of 14

INCOMER-2

VOLTMETER TEST REPORT:


1. Name Plate Details:
Make MISURE Class 1.5
Range 0-500V Type ANALOG

2. Secondary Injection test on Meter:


Injected Voltage reading on voltmeter % error
Voltage(V) Expected reading(V) Actual Reading(V)
R-100 100 100 0
R-250 250 250 0
Y-100 100 100 0
Y-250 250 250 0

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 11 of 14

B-100 100 100 0


B-250 250 250 0
% error=(Actual-Expected)/Full scale reading *100.

3. TEST INSTRUMENTS DETAILS:


Calibration
Description Make Model Serial No.
Due Date
GEPROGRAMM SVERKER76
Relay Test Kit 9602829 18.08.2020
A 0

4. Remarks:

AMMETER TEST REPORT:


1. Name Plate Details:
Make MISURE Class 1.5
Ratio 2500/5A Type ANALOG

2. Secondary Injection test on Meter:


Injected Current reading on Ammeter
% error
Current(A) Expected reading(A) Actual Reading(A)
R-2.5 1250 1250 0
R-5.0 2500 2500 0
Y-2.5 1250 1250 0
Y-5.0 2500 2500 0
B-2.5 1250 1250 0
B-5.0 2500 2500 0
TESTED BY CONTRACTOR WITNESS/APPROVED BY
COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 12 of 14

% error=(Actual-Expected)/Full scale reading *100.

3. TEST INSTRUMENTS DETAILS:


Calibration
Description Make Model Serial No.
Due Date
RELAY TEST GE SVERKER76
9602829 18.08.2020
KIT PROGRAMMA 0

4. Remarks:

CURRENT TRANSFORMER:
1. Name Plate Details:
Make/Type MBS/ASK105.6 Class 1 FS 10
Ratio 2500/5A Burden 15VA
Serial No T1 10D 93205704 T2 10D 93205648 T3 10D 93205613

2. Insulation Resistance test:

Test points Applied voltage(V) T1(GΩ) T2(GΩ) T3(GΩ)

Primary to earth ------- ----- ------ -------

Primary to secondary 1000 358 407 532

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 13 of 14

Secondary to Earth 500 174.6 181.5 158.6

PRIMARY INJECTION TEST:

Phase Injected AMMETER DISPLAY(A) Remarks


Reference current
R Y B

R-N 500A 500A --- --- OK

Y-N 500A --- 500A --- OK

B-N 500A ---- ---- 500A OK

R-Y 500A 500A 500A --- OK

Y-B 500A ---- 500A 500A OK

B-R 500A 500A ---- 500A OK

3. TEST INSTRUMENTS DETAILS:

Calibration Due
Description Make Model Serial No.
Date
Clamp Meter FLUKE 87 V 31780307 21.01.2020
GEPROGRAMM SVERKER76
Relay Test Kit 9602829 18.08.2020
A 0

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019
SITE ACCEPTANCE TEST REPORT
FOR LV PANEL

PROJECT SAADIYAT BEACH RESIDENCES & VILLAS EQUIPMENT LV PANEL


CLIENT ADDC DATE 27.10.2019
CONTRACTOR MULTIPLEX SUBSTATION SDT - 065
TESTING COMPANY ALPHA POWER LLC PAGE Page 14 of 14

4. Remarks:

TESTED BY CONTRACTOR WITNESS/APPROVED BY


COMPANY ALPHA POWER LLC
NAME MUTHUSAMY.Vn
SIGNATURE
DATE 27.10.2019