BMS Io Datapoint Schedule
BMS Io Datapoint Schedule
ZONE-01-WASTE BUNKER
FLAP VENTILATORS 13
Flaps Open/Close Command 13 ACTUATOR ON/OFF
Flaps Open/Close Status 13 VOLT FREE CONTACT TO DDC
Common Fault Alarm 13 Soft Integration
CO&CH4 SENSORS 7
CO & CH4 Gas Monitoring 14 SENSORS TO DDC
Alarm 14 VFC FROM DDC
ELV CONTROL PANELS
Access Control System 1 Soft Integration
CCTV 1 Soft Integration
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 14 26 0 27 67
TIPPING BAY
ELV CONTROL PANELS
CCTV 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 0 0 0 0 0
ZONE-02-BOILER AREA
ELV CONTROL PANELS
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 0 0 0 0 0
ZONE-03-FLUE GAS TREATMENT
ELV CONTROL PANELS
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 0 0 0 0 0
ZONE-410-UREA STORAGE
AIR HANDLING UNITS 1
Fresh air Damper Open/Close Command 1 On/Off Damper Actuator
Fresh air Damper Open/Close Status 1 On/Off Damper Actuator
Mixed air temperature and Humidity 2 Duct T +RH Sensor
Clog Status ‐ Pre‐Filter 1 Differential Pressure Switch ‐ Air
Clog Status ‐ Bag ‐Filter 1 Differential Pressure Switch ‐ Air
Temperature after cooling coil 1 Duct Temperature Sensor ‐ Air
AHU Supply Fan Airflow Status 1 Differential Pressure Switch ‐ Air
AHU Supply Fan Start/Stop Command 1 RELAY FROM DDC
HOA status (Auto) ‐ Supply Fan 1 VOLT FREE CONTACT TO DDC
AHU Trip Status ‐ Supply Air Fan 1 VOLT FREE CONTACT TO DDC
AHU Supply Fan Run Status 1 VOLT FREE CONTACT TO DDC
Supply Air pressure 1 Duct Pressure Sensor ‐ Air
Supply Air Temperature and Humidity 2 Duct Temperature Sensor ‐ Air
Return Air Damper Open/Close Command 1 On/Off Damper Actuator
Return Air Damper Open/Close Status 1 On/Off Damper Actuator
Smoke Detector Soft Integration with FA
Fire Signal from FAP Soft Integration with FA
AHU CONDENSER UNIT 1
Compressor Stage 1 FROM CONDENSER UNIT CONTROL PANEL
DUCTED INLINE EXHAUST FAN (DUTY+STANDBY) 2
Damper open/close Command 1 On/Off Damper Actuator
Damper open/close status 1 VOLT FREE CONTACT TO DDC
Fan Start/Stop Command 2 RELAY FROM DDC
HOA status (Auto) 2 VOLT FREE CONTACT TO DDC
Fan Trip Alarm 2 VOLT FREE CONTACT TO DDC
Fire Alarm Status 2 Soft Integration with FA
ELV CONTROL PANELS
Access Control syatem 1 Soft Integration
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 6 16 0 6 28
ZONE-420-11KV COMPRESSOR ROOM
ELV CONTROL PANELS
Access Control System 1 Soft Integration
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 0 0 0 0 0
ZONE-430-WATER TREATMENT
FRESH AIR HANDLING UNITS 1
Fresh air Damper Open/Close Command 1 On/Off Damper Actuator
Fresh air Damper Open/Close Status 1 On/Off Damper Actuator
Fresh air temperature and Humidity 2 Duct T +RH Sensor
Clog Status ‐ Pre‐Filter 1 Differential Pressure Switch ‐ Air
Clog Status ‐ Bag ‐Filter 1 Differential Pressure Switch ‐ Air
Temperature after cooling coil 1 Duct Temperature Sensor ‐ Air
FAHU Supply Fan Airflow Status 1 Differential Pressure Switch ‐ Air
FAHU Supply Fan Start/Stop Command 1 RELAY FROM DDC
HOA status (Auto) ‐ Supply Fan 1 VOLT FREE CONTACT TO DDC
FAHU Supply Fan Trip Status 1 VOLT FREE CONTACT TO DDC
FAHU Supply Fan Run Status 1 VOLT FREE CONTACT TO DDC
Supply Air pressure 1 Duct Pressure Sensor ‐ Air
Supply Air Temperature and Humidity 2 Duct Temperature/Humidity Sensor ‐ Air
Smoke Detector Soft Integration with FA
Fire Signal from FAP Soft Integration with FA
FAHU CONDENSER UNIT 1
compressor stage 1 FROM CONDENSER UNIT CONTROL PANEL
DECORATIVE SPLIT UNIT 1
Space/ Room Temperature 1 THERMOSTAT TO DDC
Space/ Room Setpoint 1 DDC TO THERMOSTAT
Fan Start/Stop Command 1 RELAY FROM DDC
Fan Start/Stop Status 1 VOLT FREE CONTACT TO DDC
Compressor Status 1 FROM CONDENSER UNIT CONTROL PANEL
DUCTED INLINE EXHAUST FAN 2
Damper open/close Command 1 On/Off Damper Actuator
Damper open/close status 1 VOLT FREE CONTACT TO DDC
Fan Start/Stop Command 2 RELAY FROM DDC
HOA status (Auto) 2 VOLT FREE CONTACT TO DDC
Fan Run Status 2 VOLT FREE CONTACT TO DDC
Fan Trip Alarm 2 VOLT FREE CONTACT TO DDC
Fire Alarm Status 2 Soft Integration with FA
ELV CONTROL PANELS
Access Control syatem 1 Soft Integration
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 7 19 1 6 33
ZONE-450-11KV ELECTRICAL SUBSTATION
FAN COIL UNITS 6
Space/ Room Temperature 6 THERMOSTAT TO DDC
Space/ Room Setpoint 6 DDC TO THERMOSTAT
Cooling Command 6 VOLT FREE CONTACT FROM DDC
Fan Start/Stop Command 6 RELAY FROM DDC
Fan Run Status 6 VOLT FREE CONTACT TO DDC
Compressor Status 6 FROM CONDENSER UNIT CONTROL PANEL
DUCTED INLINE EXHAUST FAN 4
Damper open/close Command 1 On/Off Damper Actuator
Damper open/close status 1 VOLT FREE CONTACT TO DDC
Fan Start/Stop Command 4 RELAY FROM DDC
HOA status (Auto) 4 VOLT FREE CONTACT TO DDC
Fan Trip Alarm 4 VOLT FREE CONTACT TO DDC
Fire Alarm Status 4 Soft Integration with FA
LOUVRE WITH MOTORIZED DAMPERS 1
Damper open/close Command 1 On/Off Damper Actuator
Damper open/close status 1 VOLT FREE CONTACT TO DDC
ELV CONTROL PANELS
Access Control syatem 1 Soft Integration
CCTV 1 Soft Integration
Public Address System 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 6 26 6 18 56
ZONE-460-33KV ELECTRICAL SUBSTATION
PACKAGE UNITS (DUTY+STANDBY) 3
Mixed air temperature and Humidity 6 Duct T +RH Sensor
Mixed air Damper Open/Close Command 6 ON/OFF Damper Actuator
Fresh/Return air Damper Open/Close Status 3 ON/OFF Damper Actuator
Clog Status ‐ Filter 3 Differential Pressure Switch ‐ Air
Air Temperature Before Cooling Coil 3 Duct Temperature Sensor ‐ Air
Air Temperature after cooling coil 3 Duct Temperature Sensor ‐ Air
AHU Supply Fan Airflow Status 3 Differential Pressure Switch ‐ Air
AHU Supply Fan Start/Stop Command 3 RELAY FROM DDC
HOA status (Auto) ‐ Supply Fan 3 VOLT FREE CONTACT TO DDC
AHU Supply Fan Trip Status 3 VOLT FREE CONTACT TO DDC
AHU Supply Fan Run Status 3 VOLT FREE CONTACT TO DDC
Supply Air pressure 3 Duct Pressure Sensor ‐ Air
Supply Air Temperature and Humidity 6 Duct Temperature Sensor ‐ Air
Supply Air Damper Open/Close Command 3 Modulating Damper Actuator
Supply Air Damper Open/Close Status 3 Modulating Damper Actuator
Smoke Detector 3 Soft Integration with FA
Fire Signal from FAP 3 Soft Integration with FA
PACKAGE UNIT CONDENSER (DUTY+STANDBY) 3
compressor stage 3 FROM CONDENSER UNIT CONTROL PANEL
DECORATIVE SPLIT UNIT 2
Space/ Room Temperature 2 THERMOSTAT TO DDC
Space/ Room Setpoint 2 DDC TO THERMOSTAT
Fan Start/Stop Command 2 RELAY FROM DDC
Fan Start/Stop Status 2 VOLT FREE CONTACT TO DDC
Compressor Status 2 FROM CONDENSER UNIT CONTROL PANEL
DUCTED INLINE EXHAUST FAN 5
Damper open/close Command 2 On/Off Damper Actuator
Damper open/close status 2 VOLT FREE CONTACT TO DDC
Fan Start/Stop Command 5 RELAY FROM DDC
HOA status (Auto) 5 VOLT FREE CONTACT TO DDC
Fan Run Status 5 VOLT FREE CONTACT TO DDC
Fan Trip Alarm 5 VOLT FREE CONTACT TO DDC
Fire Alarm Status 5 Soft Integration with FA
ELV CONTROL PANELS
CCTV 1 soft integration
UPS 1 soft integration
Access Control System 1 soft integration
Public Address System 1 soft integration
Fire Alarm Panel 1 soft integration
TOTAL IO POINTS FOR BUILDING 23 56 2 21 102
ZONE-470-11KV ELECTRICAL ROOM
VERTICAL AIR HANDLING UNITS 10
Room Temperature and Humidity 20 THERMOSTAT TO DDC
Clog Status ‐ Filter 10 Differential Pressure Switch ‐ Air
AHU Supply Fan Airflow Status 10 Differential Pressure Switch ‐ Air
AHU Supply Fan Start/Stop Command 10 RELAY FROM DDC
HOA status (Auto) ‐ Supply Fan 10 VOLT FREE CONTACT TO DDC
AHU Supply Fan Trip Status 10 VOLT FREE CONTACT TO DDC
AHU Supply Fan Run Status 10 VOLT FREE CONTACT TO DDC
Supply Air pressure 10 Duct Pressure Sensor ‐ Air
Supply Air Temperature and Humidity 20 Duct Temperature Sensor ‐ Air
Smoke Detector Soft Integration with FA
Fire Signal from FAP Soft Integration with FA
VAHU CONDENSER UNIT 10
compressor stage 10 FROM CONDENSER UNIT CONTROL PANEL
DUCTED INLINE EXHAUST FAN 1
Fan Start/Stop Command 1 RELAY FROM DDC
HOA status (Auto) 1 VOLT FREE CONTACT TO DDC
Fan Run Status 1 VOLT FREE CONTACT TO DDC
Fan Trip Alarm 1 VOLT FREE CONTACT TO DDC
Fire Alarm Status 1 Soft Integration with FA
ELV CONTROL PANELS
Lighting Control Panel 1 Soft Integration
Access Control syatem 1 Soft Integration
Public Address System 1 Soft Integration
UPS 1 Soft Integration
Fire Alarm Panel 1 Soft Integration
TOTAL IO POINTS FOR BUILDING 50 64 0 11 125
ZONE-480-OH CRANE ELECTRICAL ROOM
VERTICAL AIR HANDLING UNITS 2
Room Temperature and Humidity 4 THERMOSTAT TO DDC
Clog Status ‐ Filter 2 Differential Pressure Switch ‐ Air
AHU Supply Fan Airflow Status 2 Differential Pressure Switch ‐ Air
AHU Supply Fan Start/Stop Command 2 RELAY FROM DDC
HOA status (Auto) ‐ Supply Fan 2 VOLT FREE CONTACT TO DDC
AHU Supply Fan Trip Status 2 VOLT FREE CONTACT TO DDC
AHU Supply Fan Run Status 2 VOLT FREE CONTACT TO DDC
Supply Air pressure 2 Duct Pressure Sensor ‐ Air
Supply Air Temperature and Humidity 4 Duct Temperature Sensor ‐ Air
Smoke Detector Soft Integration with FA
Fire Signal from FAP Soft Integration with FA
VAHU CONDENSER UNIT 2
compressor stage 2 FROM CONDENSER UNIT CONTROL PANEL
DUCTED INLINE EXHAUST FAN 1
Fan Start/Stop Command 1 RELAY FROM DDC
HOA status (Auto) 1 VOLT FREE CONTACT TO DDC
Fan Run Status 1 VOLT FREE CONTACT TO DDC
Fan Trip Alarm 1 VOLT FREE CONTACT TO DDC
Fire Alarm Status 1 Soft Integration with FA
ELV CONTROL PANELS
Access Control syatem 1 soft iontegration
Public Address System 1 soft iontegration
Fire Alarm Panel 1 soft iontegration
TOTAL IO POINTS FOR BUILDING 10 16 0 3 29
ZONE-005-CONTROL BUILDING
VRF OUT-DOOR UNITS 4 Soft Integration wih the BMS based on BACnet/IP
ZONE-940-FUEL FACILITIES