MOTOR SOFT STARTERS - Air Core Reactors
MOTOR SOFT STARTERS - Air Core Reactors
INTRODUCTION:-
In the motor and motor starting theory issue, we had a glance at various motor types and motor starting
methods.
We also had a look at the Soft Starters, its advantages and types.
In this document, we are going to focus on the core technology of series reactor type Soft Starter and the
variants available as per IS 5553[part 3]/IEC 289.
In the previous issue, we learnt about the series reactor and types of reactors, which are
1. AIR CORE.
2. IRON CORE.
In this document, we will see the application advantages of Air core for motor starting.
If a motor (6.6 KV 500 KW, Is = 6 X FLC, and 1.0 X LRT) is started with
reactor Soft Starter by applying 50% voltage then the starting current
will be 3XFLC and torque will be .25XFLT.
Fig.1. Show the typical arrangement for the line side series Soft Starter
with line side and bypass arrangement.
SERIES REACTOR-:
In Series Reactor Soft Starter, to reduce the motor terminal voltage, a wound conductor (Reactor Coil)
is used as series impedance. The advantages of using Series Reactor are as below.
1. No energy is consumed.
2. No mechanical moving parts.
3. Light in weight.
4. Natural Air Cooled, No oil or forced cooling is required.
5. The impedance of reactor is a function of current passing through it, Hence a constant acceleration
torque is achieved till the motor reaches its full speed.
6. Linear acceleration [only achieved with Air Core Technology]
7. Multiple taps helps to select the motor starting current and torque (adjustable at site)
8. With air core , there is an added advantages, i.e. air core reactors act like filter and do not allow the
harmonics generated by motor to be passed on to the supply system.
-----
-----
Some Manufactures also use iron core for the designing of series Reactor of motor Soft Starter as it is
more easy to design and economical. But iron core technology is best suited for transformer manufacturing but
not the right choice for motor Soft Starter designing for the following reasons.
a. Iron Losses.
b. Eddy Current Losses.
c. Losses due to saturation of iron core.
All the above mentioned problem gets eliminated by the use of air core, hence Air core is a right choice
for motor Soft Starter application.
SR. PARAMETER AIR CORE [CORE LESS] REACTOR IRON (MAGNETIC) CORE REACTOR.
NO.
1 CHARACTERISTICS PURELY LINEAR OVER THE NON LINEAR DUE TO IRON CORE.
COMPLTE RANGE
5 WEIGHT & PHYSICAL LIGHT WEIGHT,SMALL IN SIDE HEAVY, BULKEY, BIGGER IN SIZE
DIAMENTIONS
To know more about the Air core design and Soft Starter application, please contact JAYASHREE ELECTRON,
(INDIA), E-mail your questions to [email protected].