14 Exercises en
14 Exercises en
2
Optional exercises ............................................................................................................................ 3
Exercise 1: Getting to know the training device ................................................................................. 4
Exercise 2: Device activities without PG/PC ..................................................................................... 7
Exercise 3: Configuring a reversing starter ...................................................................................... 9
Exercise 4: Commissioning .............................................................................................................. 14
Exercise 5: Diagnostics with SIMOCODE ES ................................................................................... 20
Exercise 6: Analog value recording .................................................................................................. 24
Exercise 7: Signal interconnection .................................................................................................... 28
Exercise 8: Extended function .......................................................................................................... 31
Exercise 9: Troubleshooting ............................................................................................................. 32
Exercise 10: Safety functions ........................................................................................................... 33
Exercise 11: Communication ............................................................................................................ 43
Exercise 12: Preventing a continuous signal ..................................................................................... 50
Exercise 13: Saving the ON state ..................................................................................................... 52
Exercise 14: Acknowledging an overload fault .................................................................................. 55
Exercise 15: Multi-functional display ................................................................................................. 57
Exercise 16: Automatic acknowledgment of overload ....................................................................... 60
Exercise 17: Limiting the number of starts ........................................................................................ 62
Exercise 18: Latching button with LED indicator ............................................................................... 63
In practice The safety instructions in the relevant product documentation must be followed
at all times when working autonomously on the devices outside the training
course.
Never rely on the training documents alone.
Benefits With these exercises, you can consolidate your knowledge of signal
interconnection and the use of free function blocks.
Power factor The demo case has a simulation of the phase angle (cos phi).
• Depending on the current, the phase angle changes within the range from
approx. 40 % to 80 % (= 0.4 to 0.8).
• From 100 % Is, the phase angle remains constant at 80 %.
This behavior corresponds in a simplified form to the actual behavior of a three-
phase asynchronous motor: At rated load, the power factor does not change
significantly, while operation without load or with a small load can be clearly
seen from the change in cos phi.
Circuit diagram The figure on the next page shows the external wiring. This is already created in
the training configuration with the exception of the bus connection.
Please note that the changeover from left to right (and vice versa) is initially only
possible via "Off".
2. Switch the motor with the buttons on the operator panel with display (OPD):
Manual: ………………..
Manual: ………………..
Manual: ………………..
Manual: ………………..
Manual: ………………..
6. Carry out the three hardware tests of the SIMOCODE pro basic unit
(with load and without load)
- Lamps/LED test
- Device function test
- Relay test
Connect the PC cable with the system interface on the operator panel.
Start the SIMOCODE ES configuring software.
1. Insert the "Extended protection" block. Double-click the block and set the
following parameters:
Set current: Is = 0.5 A
3. So that you don't have to wait 300 s (default value for the cooling time) after
an overload trip in the following exercises, please change the cooling time to
the smallest possible value: 60 s.
To make these settings also visible in the graphical view, change to the graphic
editor, and drag the "Extended protection" block from the parameter tree to the
work sheet.
Do the same with the "Thermistor" block that you have already activated in the
device configuration, and check the settings.
Note The device outputs that control the motor contactors must always be connected
to the QE outputs of the control function (Protection/Control block).
The meaning of the QE outputs (sockets) depends on the control function set.
For the assignment, please refer to Table A1 of the manual, p. A-2.
3. Additionally configure the operator control enable for the local [LC] control
station for the Local 2 operating mode (S1:0; S2: 1).
>> Double-click on the "Control stations" block
1. Select:
>> Device parameters > Motor control > Control function
- Control commands: ON<: Enabled control command On<
- Control commands: OFF: Enabled control command OFF
- Control commands: ON>: Enabled control command ON>
3. Arrange the window in such a way that you can see all the information at the
same time.
4. Start the motor using the pushbutton of the Local control station.
8. Observe the power factor cos phi and the power dependent on the current.
9. Switch the motor off and then on again in the opposite direction.
10. Observe the start counter in the window "Service Data / Statistical Data"
12. Observe the displays in the window "Control / Status messages" and
"Control/Status messages" > "Warnings" tab:
- General warning
- Prewarning overload (I>115 %)
3. Use the potentiometer to set the rated current for current simulation to
approx. 100 %.
4. Observe the power factor cos phi and the power dependent on the current.
5. Switch the motor off and then on again in the opposite direction.
1. Increase the motor current further to approx. 150 % and observe in the
window "Measured values" the value "Time to trip".
After expiry of this time, the motor switches off with a general fault.
2. Determine the cause of the shutdown.
3. Acknowledge the fault with the blue "TEST / RESET" button on the basic
unit.
4. Observe the LED "GEN. FAULT".
Continuous light means: Fault acknowledged but still active.
5. After an overload trip, the motor must cool down before you can switch it on
again.
Observe the remaining cooling time in the window Measured values, and
wait for this time.
6. Switch on the motor again.
7. Increase the temperature by turning the potentiometer T clockwise until the
motor is switched off with a general fault.
8. Determine the cause of the shutdown.
9. To do so, use the operator panel with display, and acknowledge on the
operator panel.
10. Reduce the temperature by turning the potentiometer T counter-clockwise
until the LED "GEN. FAULT" goes out.
The motor is now cooled.
11. Now turn the potentiometer T to the left endstop, and simulate in this way a
short-circuit in the sensor cable of the thermistor.
12. Observe the display in the window:
>> Faults/ warnings / status information > Warnings tab
Task Reset the following values because, for example, the motor or the contactor has
been replaced
Number of starts:
Set to "0" when installing new contactors or contact elements.
2. Transfer the new values to the device by clicking the "Set" button.
……….……….……….……….….……….……….……….……….……….
11. Acknowledge the fault.
Where do you find information in the manual? ………………..
……….……….………….……….……….……….……….……….……….
15. Acknowledge the fault.
Where do you find information in the manual? ………………..
16. Now switch the motor on in the opposite direction (e.g. clockwise) while you
keep the counter-clockwise contactor blocked.
17. What do you find? Why does SIMOCODE pro not switch the clockwise
contactor on?
……….……….………….……….……….……….……….……….……….
Task Set and read the inputs and outputs with the test function.
2. Under "Read function block output", select, for example, the buttons of the
operator panel, and observe their current status.
3. Under "Read and set function block input", select, for example, the outputs
of the basic unit and observe their status.
Note Please note that what is meant here are outputs and inputs of blocks
(= functions), and not outputs or inputs of the SIMOCODE device.
Examples:
• An output of the basic unit (BU output) is
an input of a block (in other words, a "plug")
• A button of the operator panel (OP button) is
an output of a block (in other words, a "socket").
Task Set the outputs of a function block using Test position feedback (TPF).
3. Open the main circuit by switching the circuit breaker off so that no current
can flow as a result of switching on the contactor.
5. Then deactivate the standard function TPF again by deleting the TPF block.
Task Work with the error buffer with SIMOCODE ES and with the operator panel.
3. To check the entries use the "Error buffer" menu in the operator panel with
display.
2. Connect the assigned analog value with the maximum motor current, for
example.
3. Connect the trigger input with the output of the block, for example:
Extended protection > Prewarning "Overload > 115 %"
5. If you also want to record values before the trigger event occurs, set the
parameter Pre-Trigger accordingly:
e.g. 25 %, which would be 7.5 s here.
4. Now increase the motor current slowly and observe the trigger display in the
window.
5. The trigger signal Prewarning overload > 115 % starts analog value
recording. From this point, the course over time of the max. motor current is
recorded for 30 s.
Change the motor current within this time.
6. You can read out the values recorded in the device at any time. This is done
with:
>> Upload values
7. With Save, the recorded values can be exported to a .csv file that can then
be further edited with Microsoft Excel, for example.
Task Record the most important signals with the trend display.
3. Use the "Selection" button to define which analog measured values are to be
represented in the y-t diagram, e.g.,
- Current Imax
- Thermal motor model
- Time to trip
- Voltage UL1
- Active power
Note Please note that the data are only recorded in the software and not in the
device.
3. Now switch the motor on, and increase the motor current with the
potentiometer I, so that a trip due to overload results.
2. Now configure the operator control enable for the operator panel [OP]
control station for the Local 2 operating mode (S1:0; S2: 1).
Note If you are connected to the SIMOCODE pro system interface via the PC cable,
you can use the operator control enable for the operator panel to also
simultaneously activate the buttons for switching the motor on and off in the
online dialog:
>> Target System > Control / status information
4. Then program the memory module with the current device parameters.
5. Remove the memory module again and carry out memory reset.
6. Now read the memory module in again, and check the function.
1. Find out where the function description can be found in the manual:
……….….……….……….……….……….……….……….……….……….
……….….……….……….……….……….……….……….……….……….
1. Open the file "Übung-5" in the path D:\Simocode and download this to your
device.
Save the parameters as a file (Übung-9-0 Today's date) under D:\Simocode\
and establish the function in accordance with Exercise 8.
2. What status display appeared on the device?
……….………….……….……….……….……….……….……….……….
……….………….……….……….……….……….……….……….……….
……….………….……….……….……….……….……….……….……….
……….….……….……….……….……….……….……….……….……….
………….……….……….……….……….……….……….……….……….
………….……….……….……….……….……….……….……….……….
Sequence For this motor feeder, you will create the parameterization in the following.
Circuit diagram The figure below shows the external wiring as found in the training
configuration.
1. Connect the PC cable with the system interface on the operator panel and
with the serial interface of the PC.
3. In the application selection dialog, select the tab "Safety engineering" and
then the application Direct starter (DM-F Local).
Note When the application is selected, a series of connections and parameters are
already preset.
Example:
• The inputs of the control stations are connected with the inputs of the basic
unit and the operator panel.
• The contactor control is connected with the output of the DM-F.
1. Start the Graphic Editor by double-clicking the entry in the parameter tree.
Notes Please note that the contactors that are to be shut down in a fail-safe manner
must always be connected to the DM-F.
This is ensured with your demo case.
1. Plan the setting of the safety relay function by creating the following target
configuration with SIMOCODE ES:
EMERGENCY OFF sensor (2-channel with 2 NC contacts)
Cross-circuit monitoring of the sensor circuit
Sensor circuit with monitored start
No checking of the sensors following power failure
No automatic connection of the enabling circuits following power failure
If this is not the case, you can find the appropriate information under:
>> Target system > Faults / warnings / status information > Status
information tab
Note Regardless of the settings that can be configured with SIMOCODE ES, the
relay enabling circuits and relay outputs of the DM-F module are always
switched off when the safety function is requested.
The setting "Response: tripping" results in SIMOCODE pro shutting down
the QE outputs and displaying a general fault.
3. Observe the state with the inputs and outputs of the DM-F with SIMOCODE
ES Online:
>> Target System > Hardware inputs and outputs
6. Observe the state with the inputs and outputs of the DM-F with SIMOCODE
ES online:
>> Target System > Hardware inputs and outputs
7. Observe the LED indicators and the display of the operator panel.
1. Simulate a welded motor contactor by placing the Control Kit (yellow plastic
part) on the motor contactor.
……….………….……….……….……….……….……….……….……….
3. Now actuate the EMERGENCY STOP button to shut down the motor.
4. Again observe the state with the inputs and outputs of the DM-F with
SIMOCODE ES online:
>> Target System > Hardware inputs and outputs
5. Observe the LED indicators and the display of the operator panel.
……….………….……….……….……….……….……….……….……….
7. Why can the enabling circuits not be closed while the motor contactor is
welded?
……….………….……….……….……….……….……….……….……….
1. Open the SIMOCODE pro parameter file from the previous exercise, or read
out the parameters from the device online.
2. Agree your bus address with the other course participants to avoid
duplication of addresses.
2. Remember here also the operator control enables for this PLC/PCS control
station.
Enable switching on and off in remote mode (S1=1; S2=2).
5. Allow SIMOCODE pro to be controlled via the PLC, and test the functions.
2. Select at the Engineering station from the overview picture your training
device and check the function
……….….……….……….……….……….……….……….……….……….
……….….……….……….……….……….……….……….……….……….
Task How can the device be made to return to the previous operating state following
failure and restoration of the control voltage of the motor feeder?
In addition, it must also be possible to reset the saved state using the OFF
command and the general fault.
……….….……….……….……….……….……….……….……….………
……….……….……….…………….……….……….……….……….………
6. Insert this block into the signal flow for the OFF signal.
Task How can you ensure that only the blue reset button can be used to acknowledge
a subsequent fault?
Overload and / or thermistor
……….….……….……….……….……….……….……….……….………
……….….……….……….……….……….……….……….……….………
……….…………….……….……….……….……….……….……….………
……….….……….……….……….……….……….……….……….………
……….…………….……….……….……….……….……….……….………
Task One overload trip per hour (5 minutes in the example) is to be automatically
acknowledged by the SIMOCODE device immediately
If an overload occurs again within one hour, the cooling time must be allowed to
elapse. Only then can the Reset button be used to acknowledge.
Parameterize the signal interconnection
……….…………….……….……….……….……….……….……….………
……….…………….……….……….……….……….……….……….………
……….…………….……….……….……….……….……….……….………
……….….……….……….……….……….……….……….……….………
……….….……….……….……….……….……….……….……….………
……….….……….……….……….……….……….……….……….………
……….….……….……….……….……….……….……….……….………
3. Connect the input of signal conditioner 4 with button 1 of the operator panel.